V-EA-Series - UL508 Manual Motor Controller -
2 pole E-Trip
UL508 Listed
E137938
Standard Pack:
6
Weight:
0.3A - 32A
1.8kg (3.97 lb.)
40A - 63A
1.98kg (4.37 lb.)
Two Pole
35 mm
(1.38 in.)
93.3 mm
(3.67 in.)
Minutes
74.7 mm
(2.94 in.)
35 mm
(1.38 in.)
Rated
Current
0.3A
0.5A
0.75A
0.8A
1.0A
1.6A
2.0A
2.5A
3.0A
3.5A
4.0A
5.0A
6.0A
8.0A
10A
12A
13A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
Type/
Cat. No.
2E03UM
2E05UM
2E075UM
NA
2E1UM
2E1.6UM
2E2UM
2E2.5UM
2E3UM
2E3.5UM
2E4UM
2E5UM
2E6UM
2E8UM
2E10UM
2E12UM
2E13UM
2E15UM
2E16UM
2E20UM
2E25UM
2E30UM
2E32UM
2E40UM
2E50UM
2E60UM
2E63UM
Approvals
V-EA-D Trip
0.3A Through 10A Rated Current
1.13-1.45xI
N
60
40
Minutes
10
4
1
Thermal Overload
“Must Trip” < 1 hr = 145% RC
“Must Not Trip” > 1 hr = 113% RC
Tripping time t
10
4
1
0.4
10
-1
4x10
-2
Seconds
10
-2
4x10
-3
10
-3
1
2
3 4 5 6 8
10 16
20
40
100
Multiple of Rated Current
V-EA-D Trip
13A Through 63A Rated Current
1.13-1.45xI
N
60
40
10
4
1
Thermal Overload
“Must Trip” < 1 hr = 145% RC
“Must Not Trip” > 1 hr = 113% RC
Voltage Rating
Short Circuit Withstand Rating
(UL/CSA - Ratings)
Group Short Circuit Withstand Rating
(UL/CSA - Ratings)
Interrupting Capacity (VDE - Ratings)
Calibration Temperature
Operating Temperature
Storage Temperature
Terminal Size Acceptability
Terminal Torque
Terminal Protection Degree
480Y/277VAC
0.3-25A: 1 pole - 42VDC; 2 Pole - 80VDC
30-60A: 1 pole - 24VDC; 2 Pole - 60VDC
0.3-60A (RC): 10kA with UL-listed
RK5 back-up fuse or MCCB
0.3-10A (RC): 10kA; 13-60A (RC): 5kA
no branch circuit protection required
0.3-63A (RC): 10kA
40°C (104°F)
-25°C to 55°C (-13°F to 131°F)
-40°C to 70°C (-40°F to 158°F)
Top: 18-3 AWG; Bottom: 18-2 AWG (Line/Load reversible)
20 lb.in.
IP20
Tripping time t
10
4
1
0.4
10
-1
4x10
-2
Seconds
10
-2
4x10
-3
10
-3
1
2
3 4 5 6 8
10 16
20
40
100
Multiple of Rated Current
Standard Dual
Connection Terminal
All parts are ring tongue compatible.
short circuit Withstand ratings for v-ea manual motor controller
Trip
Curve
all
all
all
all
Backup
Protection
Amp Range
0.3 - 10A
12 - 30/32A
40 - 50A
60 / 63A
UL-Listed
RK5-Fuse
up to 10kA
4xRC*
min 15A, max 70A
4xRC*
max 125A
4xRC*
max 200A
4xRC*
max 250A
UL-Listed
MCCB
up to 10kA
4xRC*
min 15A, max 70A
4xRC*
max 125A
4xRC*
max 200A
4xRC*
max 250A
No BCP
Required
up to:
10kA
5kA
5kA
5kA
Ring
tongue
Box
clamp
*up to nearest rated current