EEWORLDEEWORLDEEWORLD

Part Number

Search

7.2KVOEFMA100

Description
Electric Fuse, 100A, 7200VAC, 7200VDC, 45000A (IR), Inline/holder
CategoryCircuit protection   
File Size70KB,1 Pages
ManufacturerCooper Industries
Download Datasheet Parametric View All

7.2KVOEFMA100 Overview

Electric Fuse, 100A, 7200VAC, 7200VDC, 45000A (IR), Inline/holder

7.2KVOEFMA100 Parametric

Parameter NameAttribute value
MakerCooper Industries
Reach Compliance Codeunknown
Is SamacsysN
body height254 mm
Body length or diameter63.5 mm
Circuit protection typeELECTRIC FUSE
Manufacturer's serial numberOEFMA
Installation featuresINLINE/HOLDER
physical size63.5mm x 254mm
Rated breaking capacity45000 A
Rated current100 A
Rated voltage (AC)7200 V
Rated voltage (DC)7200 V
GuidelineBS 2692-1; ESI; IEC
surface mountNO
Terminal shapeEND CAP
Base Number Matches1
Medium Voltage Fuses
British Standard IEC fuses for use in oil filled distribution
switchgear
OEFMA
Specifications
Description:
BS 2692-1 medium
voltage fuses for use on the primary
circuit of three-phase 50Hz trans-
formers in oil field switchgear. Fitted
with powerful pyrotechnic striker pin.
Ratings:
Volts: — 3.6-24kV
Amps: — 6.3-200A
IR: — 25-50kA (See Catalog Number table below)
Agency Information:
Fuses comply with IEC 60282-1,
BS2692-1 and ESI Standard 12-8. 7.2 and 12kV fuses tested
at highest system voltage and approved by the UK Electricity
Association approvals panel.
Featues and Benefits
• Physically sized for replacement of British Standard fuse
links
Typical Applications
• Medium Voltage BS designed equipment
Code Number Reference
O
Type
O = Oil tight
_
_
M
A
Diameter
E = 63.5mm
H = 63.5mm
L = 63.5mm
Length
F = 254mm
G = 359mm
Striker
M = As specified in BS 2692 table 11
Tags
A = None (plain caps)
Dimensions:
Current-limiting fuse for use in oil switchgear
Fuse types: OEF, OEG, OHF, OHG, OLG
254mm (10 in) or 359mm (14 in)
44
68 Max
63.5
Catalog Numbers
Transformer
kVA
200
250
300/315
400
500
630
750/800
1000
1250
1600
Catalog Numbers
Transformer Primary Voltage
3.3kV
6.6kV
3.6kV OEFMA 63
12kV OEFMA 31.5
3.6kV OEFMA 80
12kV OEFMA 40
3.6kV OEFMA 100
12kV OEFMA 50
3.6kV OEFMA 125
12kV OEFMA 63
3.6kV OEFMA 160
12kV OHFMA 71
3.6kV OEFMA 200
7.2kV OEFMA 100
3.6kV OLGMA 250
7.2kV OHGMA 125
3.6kV OLGMA 250*
7.2kV OHGMA 140
7.2kV OHGMA 160*
10 Min — 16 Max striker travel after operation, if fitted.
11kV/ESI 12-8 Ref.
12kV OEFMA 25/01
12kV OEFMA 25/—
12kV OEFMA31.5/02
12kV OEFMA 40/—
12kV OEFMA 50/03
12kV OEFMA 63/—
12kV OHFMA 80/04
12kV OHGMA 90**/05
12kV OHGMA 100/—
12kV OLGMA 125*/—
13.8kV
15.5kV
15.5kV
15.5kV
15.5kV
15.5kV
15.5kV
15.5kV
15.5kV
15.5kV
15.5kV
OEFMA 16
OEFMA 20
OEFMA 25
OEFMA 31.5
OEFMA 40
OEFMA 50
OEFMA 63
OHGMA 71
OHGMA 90
OLGMA 100*
This Catalog Number selection table is based upon the following criteria:
1. Withstand against magnetizing inrush current taken as 12 times full-load current for 0.1 second.
2. Withstand against 150% permissible overload current. Recommendations marked with asterisks have the following significance:-
*Limited to permissible overloads of 130%.
**Permits use of a 12kV OHFMA 80A fuse with a 100kVA transformer where permissible overload does not exceed 130%.
3. For 6.6kV systems, 12kV fuses are recommended where possible in the interests of standardization.
4. Wherever possible, 10 inch long FO1 fuses are offered rather than equivalent 14 inch FO2 types.
5. The above recommendations are not generally applicable to transformers feeding motor circuits with starting currents in excess of the transformer full load current. In this event, please consult
Cooper Bussmann.
Catalog Numbers
Basic Cat.
Number
OEFMA
OEGMA
OLGMA
OEFMA
OHGMA
OEFMA
OHFMA
OHGMA
OLGMA
OEFMA
OHGMA
OLGMA
OHGMA
OEGMA
Voltage
3.6kV
3.6kV
3.6kV
7.2kV
7.2kV
12.0kV
12.0kV
12.0kV
12.0kV
15.5kV
15.5kV
15.5kV
17.5kV
24.0kV
Dimensional
Ref. BS 2692
FO1
FO2
FO2
FO1
FO2
FO1
FO1
FO2
FO2
FO1
FO2
FO2
FO2
FO2
Amp Ratings
6.3, 10, 16, 20, 25,
100, 125, 160, 200
250
80, 100, 112
125, 140, 160
6.3, 10, 16, 20, 25,
71, 80
6.3, 10, 16, 20, 25,
125
6.3, 10, 16, 20, 25,
71, 80, 90
100
6.3, 10, 16, 20, 25,
6.3, 10, 16, 20, 25,
31.5, 40, 50, 63, 80, 100, 125, 160, 200
Breaking
Capacity (kA)
50
50
50
45
45
40
40
40
40
40
40
40
35
25
31.5, 40, 50, 63
31.5, 40, 50, 63, 71, 80, 90, 100
31.5, 40, 50, 63
Catalog Number Build-A-Code
kV
Basic
Amps
Catalog Number
___
_____
___
31.5, 40, 50, 63, 80
31.5, 40, 50
Contact Cooper Bussmann for complete specifications on medium voltage fuses.
84
For product Data Sheets, visit www.cooperbussmann.com/products/datasheet.asp
The difference between ds18b20 and ds1820
I only have the ds1820 sensor and I don't know what the difference is between this sensor and the ds18b20 when writing programs. I used the ds18b20 program I had adjusted before, but it doesn't displa...
melodyooo MCU
[Xiaomeige SOPC Learning Notes] Several settings that need to be paid attention to in the software after switching the main memory of NIOS II CPU
[b][align=center][b][size=5]Sometimes, we may face such a situation:[/color][/size] [size=4][color=#000]1. We create a SOPC system and set the reset address and exception address of NIOS II to SRAM in...
芯航线跑堂 FPGA/CPLD
AECQ Op Amp Cost Issues
Recently, something like this happened to me. The quad op amps LM2904 and LM2902 that we often use are very mature in technology, have a large output, and are relatively cheap. In the design, the volt...
yulzhu Analog electronics
Is it necessary to use a synchronization signal to generate three-phase PWM by 28335?
I still don't understand why the synchronization signal is only needed when the epwm of different DSPs work together. The epwm of the same DSP all use the same system clock. They should be synchronize...
jonny0811 Microcontroller MCU
CE6.0 about shared interrupts
I'd like to ask about the problem of shared interrupts in CE6.0. I want to make a GPIO shared interrupt and use an X86 architecture board. I wrote an ISR imitating GIISR and called the LoadIntChainHan...
istbchbn Embedded System
RTP test program freezes
I downloaded an RTP test program, compiled it, but it can't run under WINCE--EVC. It freezes when I run it. I don't know why. Can experts who have used JRTPLIB send me the library files and project di...
scliujun Embedded System

EEWorld
subscription
account

EEWorld
service
account

Automotive
development
circle

Robot
development
community

Index Files: 844  1364  1418  1379  916  17  28  29  19  48 
Datasheet   0 1 2 3 4 5 6 7 8 9 A B C D E F G H I J K L M N O P Q R S T U V W X Y Z
Room 1530, 15th Floor, Building B, No. 18 Zhongguancun Street, Haidian District, Beijing Telephone: (010) 82350740 Postal Code: 100190
Copyright © 2005-2026 EEWORLD.com.cn, Inc. All rights reserved 京ICP证060456号 京ICP备10001474号-1 电信业务审批[2006]字第258号函 京公网安备 11010802033920号