LC-PD1217
For standby power supplies
Expected trickle life: 6 years at 25℃
10 years at 20℃
■Dimensions(mm)
Terminal type (option)
11
12.5
M5
11.8
M5
※Contents
indicated (including the recycle
marking,etc) are subject to change without notice.
Battery case resin: Flame-retardant (UL94V-0)
■Specification
Nominal Voltage
Rated Capacity(20HR)
Length
Width
Dimensions
Height
Total height
Approx. Mass
Terminal
12V
17Ah
181 mm
76 mm
167 mm
167 mm
5.45 kg
M5 threaded post
■Duration
of discharge vs. discharge current
30
20
10
(hour)
5
3
25℃
40
℃
■Characteristics
Capacity
(25
℃)
Internal Resistance
(25
℃)
Temperature
Dependency of
Capacity
(20 hour rate)
Self Discharge
(25
℃)
20 hour rate
10 hour rate
3 hour rate
1 hour rate
Fully charged battery
40
℃
25
℃
0
℃
-15
℃
After 3 months
After 6 months
After 12 months
17Ah
16Ah
13Ah
11Ah
17 mΩ
102%
100%
85%
65%
91%
82%
64%
Duration of discharge
60
30
0℃
(minute)
10
5
3
-15℃
1
0.1
0.3
1
3
10
30
100
Discharge current(A)
(Wattage/Battery)
1h
142
140
139
136
134
1.5h
97.6
95.6
93.7
91.7
89.2
2h
75.5
74.9
73.0
70.4
67.1
3h
56.2
55.9
55.4
54.5
53.4
4h
43.2
42.9
42.6
42.3
41.8
5h
35.6
35.4
35.1
34.8
33.9
6h
28.6
28.5
28.3
28.0
27.5
10h
19.0
18.9
18.7
18.6
18.4
20h
10.3
10.3
10.2
10.2
10.1
■Watt
Table(25℃)
Cut-off V
9.6V
9.9V
10.2V
10.5V
10.8V
5min
806
756
708
634
561
10min 15min 20min 30min 45min
526
516
502
465
415
402
399
391
364
339
337
331
326
309
301
251
249
246
240
232
177
176
175
172
169
■Ampere
Table(25℃)
Cut-off V
9.6V
9.9V
10.2V
10.5V
10.8V
5min
72.2
67.8
63.5
56.9
50.3
10min 15min 20min 30min 45min
47.0
46.0
44.9
41.6
37.1
34.9
34.7
34.0
31.6
29.5
29.0
28.6
28.1
26.7
26.0
21.5
21.2
21.0
20.5
19.8
15.1
15.0
14.9
14.6
14.4
1h
12.0
11.9
11.7
11.6
11.3
1.5h
8.26
8.10
7.93
7.77
7.56
2h
6.37
6.33
6.16
5.95
5.67
3h
4.72
4.70
4.65
4.58
4.49
4h
3.61
3.59
3.57
3.54
3.49
5h
2.97
2.95
2.93
2.90
2.83
(Ampere/Battery)
6h
2.39
2.38
2.36
2.33
2.29
10h
1.65
1.64
1.63
1.62
1.60
20h
0.857
0.855
0.852
0.850
0.845
1/2
■Charging
Method
Trickle use
Control voltage:13.6-13.8V
Initial current:2.55A or smaller
(25℃)
■Cut
off voltage
Discharge current
Cut off voltage(V)
0.850A-
3.40A- 8.50A- 17.0A-
3.40A 8.50A 17.0A 34.0A
10.5
10.2
9.9
9.3
34.0A-
51.0A
8.7
■Influence
of Temperature on Trickle life
100
Service Life (Years)
①Charging
Voltage
2.275V/Cell
10
■Residual
capacity test result
Capacity Retention Ratio (%)
120
100
80
60
40
20
0
40℃
(104℉)
30℃
(86℉)
25℃
(77℉)
5℃
(41℉)
1
0.1
0
10
20
30
40
Temperature (℃)
50
60
0
2
4
6
8
10 12 14 16
Storage Period (Month)
18
20
■
Constant-voltage constant-current charge characteristics for Trickle use
160
0.3
Charge Current(CA)
140
Charge Quantity(%)
120
100
80
60
40
20
0
0
0
4
8
12
16
20
Char ge Tim e (H)
24
B attery Voltage
■
Discharge capacity by temperature and by discharge current
120
100
0.05CA
0.10CA
0.25CA
0.50CA
1.00CA
2.00CA
3.00CA
16.0
14.0
Battery Voltage(V)
12.0
10.0
8.0
6.0
4.0
2.0
0.0
Charge Quan tity (to-D ischarge Quantity
①
Discharge
—
100% (0.05CA*20H)
—
—
50% (0.05CA*10H)
—
②
Charge
Charge Voltage
:
13.7V(2.28V/Cell)
Charge Current
:
0.15CA
③
Temperature
:
25
℃
(77
℉
)
0.2
Capacity(%)
80
60
40
20
0
-15
0
15
30
Battery temperature(℃)
45
0.1
C harge Cu rren t
■Discharge
characteristics(25℃)
20.0
Terminal voltage(V)
15.0
10.0
51.0A
5.0
34.0A
17.0A
4.25A
0.850A
0.0
0
1
2
4
6
8
(minute)
10
20
40
60
2
4
6
8 10
20
40
(hour)
Duration of discharge
!
Caution
Due to the potential energy stored in the batteries, Please read
《Precautions
for handling the Rechargeable Valve Regulated Lead Acid Batteries
》
before using batteries. If improper handling or use of the batteries without understanding
《Precautions
for handling the Rechargeable Valve
Regulated Lead Acid Batteries》may result in bodily injury caused by electrolyte leakage, heat generation, or explosion.
Panasonic Storage Battery (Shenyang) Co., Ltd
NO. 51 Kunminghu Street, Shenyang Economic & Technical Development Zone,110141 China
Tel: 86 24 25818921
Fax: 86 24 62786318
Website:
http://www.panasonicbattery.cn
2/2
2010.03