Telaire 6613 CO
2
Module
Small, Compact CO
2
Module Designed to
Integrate Into Existing
Controls and Equipment
The Telaire
®
6613 CO
2
Module is designed to meet
the volume, cost, and delivery expectations of
Original Equipment Manufacturers (OEMs). The
module is ideal for customers who are familiar
with the design, integration, and handling of
electronic components.
All units are factory calibrated to measure CO
2
concentration levels up to 2000 and 5000 ppm.
Telaire dual channel sensors are available for
higher concentrations.
Telaire
®
offers high-volume manufacturing
capabilities, a global sales force, and additional
engineering resources to support your sensing
application needs.
Features
•
An affordable gas sensing solution for OEMs.
•
A reliable sensor design based on 15 years of
engineering and manufacturing expertise.
•
Flexible CO
2
sensor platform designed to interact
with other microprocessor devices.
•
Eliminates the need for calibration in most
applications with Telaire’s patented ABC Logic™
software. Lifetime calibration warranty.
Amphenol
Advanced Sensors
Telaire 6613 CO
2
Module
Specifications
Method
Non Dispersive Infrared (NDIR), gold plated optics,
diffusion or flow through sampling (with Telaire’s
Patented ABC Logic Self Calibrated Algorithm)
0.38 in
(9.65 mm)
1.75 in
(44.45 mm)
2 Mounting Holes Ø.105 (2.667)
0.062 in
(0.1575 mm)
1.365 in
(34.67 mm)
1.24 in
(31.5 mm)
0.15 in (3.81 mm)
Measurement Range
0 to 2000 ppm**
2.25 in
(57.15 mm)
1.125 in
(28.575 mm)
0.54 in
(13.7 mm)
0.60 in
(15.24 mm)
Dimensions
2.25 in X 1.365 in X 0.60 in
(57.15 mm X 34.67 mm X 15.24 mm)
Output
Digital
UART @ 19200 Baud (Please call for detailed product
specifications).
I
2
C slave up to 100 kHz
Accuracy*
• 400-1250 ppm ± 30 ppm or 3% of reading,
whichever is greater*
• 1250-2000 ppm ±5% of reading + 30ppm*
Analog
0 to 4 VDC
Temperature Dependence
0.2% FS per °C
Power Supply Requirements
5 VDC regulated (±5%)
Stability
< 2% of FS over life of sensor (15 year typical)
Power Consumption
• 0.90 watts peak
• 0.165 watts average
Pressure Dependence
0.13% of reading per mm Hg
Calibration Interval
Not required
Interface Connections
Designed for 12 pin male header with 0.1 in (2.54 mm)
spacing. Header not included.
Response Time
< 2 minutes for 90% step change typical
Flow Rates (Via Flow Ports)
Flow through version 40 to 50 cc/min
Signal Update
Every 4 seconds
Warranty Terms
12 months
*Tolerance based on span gas of ±2%
** Subjecting sensors to environments less than 400
ppm for more than 15 minutes may affect accuracy
due to ABC Logic algorithm.
Warm Up Time
• < 2 minutes (operational)
• 10 minutes (maximum accuracy)
Operating Conditions
• 32°F to 122°F (0°C to 50°C)
• 0 to 95% RH, non condensing
Storage Conditions
-40°F to 158°F (-40°C to 70°C)
Automatic Background Logic, or ABC Logic, is a
patented self-calibration technique that is designed to
be used in applications where concentrations will drop
to outside ambient conditions (400 ppm) at least three
times in a 14 day period, typically during unoccupied
periods.
*Full accuracy to be achieved utilizing ABC Logic. With
ABC Logic enabled, the sensor will typically reach its
operational accuracy after 25 hours of continuous
operation at a condition that it was exposed to ambient
reference levels of air at 400 ppm ±10 ppm CO
2
. Sensor
will maintain accuracy specifications with ABC Logic
enabled, given that it is at least four times in 21 days
exposed to the reference value and this reference
value is the lowest concentration to which the sensor
is exposed. ABC Logic requires continuous operation of
the sensor for periods of at least 24 hours. Note: Applies
when used in typical residential ambient air. Consult
Telaire if other gases or corrosive agents are part of the
application environment.
Module 6613-F (Flow Through)
The diffusion membrane is replaced with a non-
permeable seal. The two flow ports can be used
for flow through sampling. Flow rate of 50 cc/min
recommended.
Handling and Installation
The T6613 CO
2
OEM modules are infrared gas sensors
on a printed circuit board and should be treated
carefully. Precautions should be taken to observe
specified limits and prevent damage from electrostatic
discharge or rough handling. Please refer to ANSI/ESD
S20. 20-1999 for more information on preventing ESD
damage and IPC 610 Rev D for more information on
proper electronic assembly practices.
Calibration
Telaire does not recommend the customer recalibrate
the T6613 module after installation. The sensor ABC
Logic algorithm will begin after 24 hours, adjusting the
sensor measurement resulting in sensor-to-sensor
consistency. If immediate consistency is desired, the
sensors may be single point calibrated using pre-mixed
reference gas or ambient air measured by a reference
sensor.
Pin Designations
Connector Pinout
A
B
C
1
2
3
4
5
6
7
8
9
10
11
12
Function
TX (UART)
RX (UART)
V+ (5 VDC)
V+ (5 VDC)
GND
GND
AV OUT (0 to 4 VDC)
I
2
C SCL
No Connect
I
2
C SDA
No Connect
No Connect
TX (UART)
RX (UART)
GND
Available Models
Part Number
T6613
T6613-F
T6613-C
T6613-R12
T6613-5K
T6613-5KF
T6613-5KC
Sampling Method
Diffusion
Flow Through
Diffusion with gas ports
Diffusion, 12 second rate
Diffusion
Flow through
Diffusion with gas ports
Measurement Range
0-2,000 ppm
0-2,000 ppm
0-2,000 ppm
0-2,000 ppm
0-5,000 ppm
0-5,000 ppm
0-5,000 ppm
Amphenol
Advanced Sensors
www.telaire.com
www.amphenol-sensors.com
© 2014 Amphenol Corporation. All Rights Reserved. Specifications are subject to change without notice.
Other company names and product names used in this document are the registered trademarks or
trademarks of their respective owners.
AAS-920-448J-09/2014
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Amphenol
:
T6613 T6613-F T6613-C T6613-R12 T6613-5K T6613-5KF T6613-5KC T6613-EVAL