EMC/EMI Filter for Installations with Residual Current Device (RCD)
Full functionality with RCDs according to IEC
61008 and new VDE 0664-110*
Approvals
Compatible with 30 mA RCDs up to 30 m motor
cable for electric shock protection according to
IEC 61008
Compatible with 300 mA RCDs up to 100 m
motor cable for fire protection according to IEC
60364-4-42 (VDE 0100-482)
Features and benefits
Innovative low-leakage current filter with same
smallest dimensions as FN 3258
Significant reduction of leakage and ground
currents caused by long motor cables
Prevents unwanted fault shut-downs from RCDs in
machines and process automation equipment
Patented filter design avoiding early saturation and
ringing effects
Excellent attenuation compliant with: C1 limits EN
61800-3 with 30 meter motor cable and 30 mA RCD
(electric shock protection)**
C2 limits EN 61800-3 with 100 meter motor cable
and 300 mA RCD (fire protection)
Typical applications
Three-phase variable speed drives (VSD), servo
drives, and inverters
Machinery and process automation equipment
Technical specifications
Design corresponding to
Flammability corresponding to
High potential test voltage
Maximum continuous operating voltage
MTBF @ 50°C/400V (Mil-HB-217F)
Operating frequency
Overload capability
UL 1283, CSA 22.2 No. 8 1986, IEC/EN 60939
UL 94 V-2 or better
P –> E 2650 VDC for 2 sec
Building automation, HVAC equipment, pumps,
ventilation, and elevators
Conveyors, handling and storage systems, and
cranes
Machine tools, wood working machines, and
printing machines
P –> P 2100 VDC for 2 sec
3x 520/300 VAC
>300,000 hours
dc to 60 Hz
Typical electrical schematic
Protection category
Rated currents
4x rated current at switch on,
1.5x rated current for 1 minute, once per hour
IP20
7 to 180 A @ 50 °C
** If supply voltage is contaminated with harmonics according to IEC 61000-2-4, class 2,
**
where odd-numbered multiplies of three are limited to 30%.
** Filter types 7 A up to 42 A: C1, 30 m, 30 mA; 55 A: C2, 30 m, 30 mA; 75 A up to 180 A: C2, 100m, 300 mA
Temperature range (operation and storage)
-25 °C to +100 °C (25/100/21)
2
EMC/EMI Products
Schaffner Group
Datasheets
2014
Filter selection table
Filter
@ 50 °C (40 °C)
7 (7.7)
[A]
Rated current
power rating*
Typical drive
[kW]
Leakage current**
@ 400 VAC/50 Hz
[mA]
4.5
@ 25 °C/50 Hz
[W]
4.5
Power loss
Input/Output
connections
-44
Weight
[kg]
FN 3268-16-44
FN 3268-7-44
FN 3268-30-33
FN 3268-42-33
FN 3268-55-34
FN 3268-75-34
FN 3268-100-35
FN 3268-130-35
FN 3268-180-40
16 (17.5)
30 (32.9)
42 (46.0)
55 (60.2)
100 (109.5)
130 (142.4)
180 (197.1)
75 (82.2)
18.5
22
37
45
55
75
7.5
4
4.7
4.6
4.7
7.8
4.6
17.4
18.1
25.3
13.5
6.1
-44
0.5
-33
-34
-34
-33
0.8
1.4
2.2
2.9
1.2
20.5
30.4
37.0
30.0
38.0
48.6
-35
-35
-40
4.1
4.6
6.0
110
* Calculated at rated current, 440 VAC and cos phi = 0.8. The exact value depends upon the efficiency of the drive, the motor and the entire application.
** Maximum leakage under normal operating conditions. Note: if two phases are interrupted, worst case leakage could reach 5.4 times higher levels.
Typical filter attenuation
7 to 42 A types
Per CISPR 17; A = 50 Ω/50 Ω sym; B = 50 Ω/50 Ω asym; C = 0.1 Ω/100 Ω sym; D = 100 Ω/0.1 Ω sym
55 to 100 A types
130 and 180 A types
Installation
EMC/EMI filter FN 3268
Filter types from 7 to 55 A are designed to be
compatible with 30 mA RCDs according to IEC
61008 and new VDE 0664-110 standards. Filters
from 75 up to 180 A are designed to be
compatible with 300 mA RCDs. Install the filter as
close as possible at line side of the motor drive.
Regarding correct EMC installation, please refer to
the EMC installation guide in the manual from
motor drive supplier.
Typical installation with RCD, EMC/EMI filter and motor
drive system
Motor cable length
Motor cable length should not exceed 30 meters for
7 up to 55 A filter types to fulfill class C1 of
recommended standard EN 61800-3. For 75 up to
180 A filters, cable length should not exceed 100
meters to fulfill class C2.
Internal EMC/EMI components
Please disconnect all internal Y-capacitors (internal
EMC/EMI filters) in the motor drive, because these
capacitors cause additional leakage currents.
Harmonics on line voltage
High voltage harmonics can create additional
system leakage currents. FN 3268 filters are tested
under following conditions: Supply voltage is
contaminated with harmonics according to IEC
61000-2-4, class 2, where odd-numbered multiplies
of three are limited to 30%.
RCD
Please note that for electrical devices with 6-pulse
rectifiers at line input, like three-phase motor
drives, a RCD type B or B+ is required. RCD with
time delay are needed to prevent unwanted fault
trip at switch on or voltage spikes. These RCD
types B with time delay have often an added letter
“S” or “K”, please ask the supplier for correct type.
Caution: Please validate system with chosen RCD
to guarantee functionality.
Motor drive
Please set the PWM pulse pattern of the variable
speed motor drive fixed to 4 kHz. Other pulse
patterns cause higher leakage currents. Filter
designs with other pulse pattern than 4 kHz are
possible upon request.
3
EMC/EMI Products
Schaffner Group
Datasheets
2014
Mechanical data
FN 3268
Note: in favour of a better readability, connectors and earth studs are not shown in
the horizontal projection.
Dimensions
A
B
C
E
F
7A
190
40
70
16 A
250
45
70
30 A
270
50
85
42 A
310
50
85
55 A
250
85
90
75 A
270
80
100 A
270
90
130 A
270
90
180 A
D
160
180
4.5
22
20
20
220
235
5.4
22
25
240
255
5.4
25
30
280
295
5.4
25
30
220
235
5.4
39
60
135
240
255
6.5
39
60
150
240
255
6.5
45
65
150
120
380
240
255
6.5
45
65
170
350
365
6.5
G
H
I
J
102
1.5
M10
1
1
1
1
1
1.5
M6
1.5
M10
1.5
M10
K
L
M5
29.5
22.5
M5
M5
29.5
39.5
25
M6
37.5
25
42.5
M6
51
60
26.5
70.5
40
45
64
45
64
47
All dimensions in mm; 1 inch = 25.4 mm
Tolerances according: ISO 2768-m / EN 22768-m
Filter input/output connector cross sections
-33
-34
-35
-40
-44
Solid wire
Flex wire
AWG type wire
Recommended torque
16 mm
2
10 mm
2
1.5-1.8 Nm
AWG 6
35 mm
2
25 mm
2
4.0-4.5 Nm
AWG 2
50 mm
2
AWG 1/0
7-8 Nm
50 mm
2
95 mm
2
AWG 4/0
95 mm
2
10 mm
2
6 mm
2
17-20 Nm
1.5-1.8 Nm
AWG 8
Please visit www.schaffner.com to find more details on filter connectors.
Let's talk about power-off reset first. [font=Verdana] Power-off reset: When the voltage suddenly drops during the operation of the microcontroller, the microcontroller will have many uncertain phenom...
I recently learned to use AD. I have a strain gauge pressure sensor with a maximum range of 20 kg. If voltage is applied to two wires, there will be a signal of about 5mV/V on the other two wires.Assu...
In circuit design, there are always various power symbols, which often confuse people. Today, I have sorted out more than 20 commonly used power symbols to share with you. Collect them quickly.1. VBB ...
Do you often have to add brake fluid to your car's brakes? The fact that you need to pump out the brake fluid to make sure there is no gas in the brake fluid line may not be done by the car owner h...[Details]
The Portable Digital Data Acquisition System (PDDAS) uses LabVIEW Real-Time and PXI to control the wind tunnel test and record air pressure data from 128 different channels.
"The LabVIEW Real-...[Details]
For a long time, due to the limitation of hardware conditions, the display devices of traditional small handheld devices such as PDA are usually monochrome LCD, and the user interface is very simpl...[Details]
Battery life is critical for portable applications. For applications such as smoke detectors, security devices, and thermostats, factory-installed batteries need to last for more than 10 years. The...[Details]
My colleague and I spent the day chatting in the hotel bar. We had met with several customers. We were both wondering how come these engineers we were meeting knew almost nothing about analog techn...[Details]
Editor's note: In order to help technicians or engineers who have knowledge of PIC microcontroller assembly language quickly master the method of using C language to program PIC microcontrollers, t...[Details]
Instrument stepper motor
The stepper motor is an open-loop control element that converts electrical pulse signals into angular displacement or linear displacement. In the case of non...[Details]
1 Introduction
PROFIBUS is an international, open, and manufacturer-independent fieldbus standard. It is widely used in manufacturing automation, process industry automation, and automatio...[Details]
In the analysis of electronic circuits, static analysis (also known as DC analysis) is the basis of circuit analysis. However, it is well known that electronic components are nonlinear, so the anal...[Details]
RS-422 and RS-485 are both serial data interface standards, which were developed and published by the Electronic Industries Association (EIA). RS-422 defines a balanced communication interface with a ...[Details]
1 Introduction
There have been many studies on the detection and protection of power grid short circuit and line fault. The short circuit, overload and overvoltage protectors on the market have ...[Details]
Single-chip microcomputers are widely used because of their small size, powerful functions and low price. This article introduces the method of designing a micro electronic piano using the AT89C51 sin...[Details]
Describe how to meet the challenges of complexity with a modern wiring design toolset. Option codes and expressions can simulate the variables of an automotive project. A full-featured tool suite c...[Details]
The rectified DC voltage is then converted back to AC using power electronics such as insulated gate bipolar transistors.
The output voltage is switched on and off at a high frequency, control...[Details]
0 Introduction
Under normal circumstances, the three-phase power in the power system is symmetrical, and they meet certain amplitude and phase conditions; but when the load changes, the syst...[Details]