Detailed Specifications & Technical Data
ENGLISH MEASUREMENT VERSION
8772NH Multi-Conductor - GreenChoice Multiconductor
For more Information
please call
1-800-Belden1
General Description:
20 AWG stranded (7x28) tinned copper conductors, conductors cabled, polyethylene insulation, overall
Beldfoil® shield (100% coverage), 20 AWG stranded tinned copper drain wire, LSZH jacket.
Physical Characteristics (Overall)
Conductor
AWG:
# Conductors AWG Stranding Conductor Material
3
20
7x28
TC - Tinned Copper
3
Total Number of Conductors:
Insulation
Insulation Material:
Insulation Material Wall Thickness (in.)
PE - Polyethylene
0.017
Outer Shield
Outer Shield Material:
Outer Shield Trade Name Type Outer Shield Material
Beldfoil® (Z-Fold®)
Coverage (%)
Tape Aluminum Foil-Polyester Tape 100
Outer Shield Drain Wire AWG:
AWG Stranding Drain Wire Conductor Material
20
7x28
TC - Tinned Copper
Outer Jacket
Outer Jacket Material:
Outer Jacket Material
Nom. Wall Thickness (in.)
LSZH - Low Smoke Zero Halogen 0.033
Overall Cable
Overall Cabling Lay Length & Direction:
Length (in.) Twists (twist/ft)
2.000
6.000
Overall Cabling Color Code Chart:
Number Color
1
2
3
Black
Red
Clear
0.218 in.
Overall Nominal Diameter:
Mechanical Characteristics (Overall)
Operating Temperature Range:
UL Temperature Rating:
Bulk Cable Weight:
Max. Recommended Pulling Tension:
Min. Bend Radius/Minor Axis:
-20°C To +60°C
60°C
28 lbs/1000 ft.
45 lbs.
2 in.
Applicable Specifications and Agency Compliance (Overall)
Applicable Standards & Environmental Programs
NEC/(UL) Specification:
CEC/C(UL) Specification:
EU Directive 2011/65/EU (ROHS II):
EU CE Mark:
EU Directive 2000/53/EC (ELV):
CMG
CMG
Yes
Yes
Yes
Page 1 of 2
08-26-2016
Detailed Specifications & Technical Data
ENGLISH MEASUREMENT VERSION
8772NH Multi-Conductor - GreenChoice Multiconductor
EU Directive 2002/95/EC (RoHS):
EU RoHS Compliance Date (mm/dd/yyyy):
EU Directive 2002/96/EC (WEEE):
EU Directive 2003/11/EC (BFR):
CA Prop 65 (CJ for Wire & Cable):
MII Order #39 (China RoHS):
Other Specification:
Yes
05/07/2012
Yes
Yes
Yes
Yes
UL AWM 21307
Flame Test
UL Flame Test:
C(UL) Flame Test:
UL1685 FT4 Loading
FT4
Suitability
Suitability - Indoor:
Non-halogenated:
Yes
Yes
Plenum/Non-Plenum
Plenum (Y/N):
No
Electrical Characteristics (Overall)
Nom. Capacitance Conductor to Conductor:
Capacitance (pF/ft)
27
Nom. Capacitance Cond. to Other Conductor & Shield:
Capacitance (pF/ft)
51
Nom. Conductor DC Resistance:
DCR @ 20°C (Ohm/1000 ft)
10.0
Nominal Outer Shield DC Resistance:
DCR @ 20°C (Ohm/1000 ft)
8.9
Max. Operating Voltage - UL:
Voltage
300 V RMS
Max. Recommended Current:
Current
4 Amps per conductor @ 25°C
Put Ups and Colors:
Item #
8772NH 0601000
8772NH 060500
Putup
1,000 FT
500 FT
Ship Weight
31.000 LB
16.000 LB
Color
CHROME
CHROME
Notes
Item Desc
3 #20 PO FS NHFRPO
3 #20 PO FS NHFRPO
Revision Number: 0
© 2016 Belden, Inc
All Rights Reserved.
Revision Date: 08-16-2016
Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications described herein are subject to error or omission and to
change without notice, and the listing of such information and specifications does not ensure product availability.
Belden provides the information and specifications herein on an "AS IS" basis, with no representations or warranties, whether express, statutory or implied. In no event will Belden be liable for
any damages (including consequential, indirect, incidental, special, punitive, or exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether
in an action under contract, negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein.
All sales of Belden products are subject to Belden's standard terms and conditions of sale.
Belden believes this product to be in compliance with EU RoHS (Directive 2002/95/EC, 27-Jan-2003). Material manufactured prior to the compliance date may be in stock at Belden facilities
and in our Distributor’s inventory. The information provided in this Product Disclosure, and the identification of materials listed as reportable or restricted within the Product Disclosure, is
correct to the best of Belden’s knowledge, information, and belief at the date of its publication. The information provided in this Product Disclosure is designed only as a general guide for the
safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. This Product Disclosure is not to be considered a warranty or quality specification.
Regulatory information is for guidance purposes only. Product users are responsible for determining the applicability of legislation and regulations based on their individual usage of the
product.
Belden declares this product to be in compliance with EU LVD (Low Voltage Directive 2014/35/EU).
Page 2 of 2
08-26-2016