Part Number:
8455
Portable Cordage, (3) 20 AWG (26x34) TC, (2) 18 AWG (41x34) TC,
EPDM/Rubber, 300V, 60°C
Product Description
Three 20 AWG stranded (26x34) tinned copper conductors, two 18 AWG stranded (41x34) tinned copper conductors, EPDM insulation, rubber jacket.
Technical Specifications
Physical Characteristics (Overall)
Conductor
AWG Stranding
20
18
26x34
41x34
Material
No. of Conductors
TC - Tinned Copper 3
TC - Tinned Copper 2
5
20 AWG
Conductor Count:
Conductor Size:
Insulation
Material
Nominal Wall Thickness
EPDM - Ethylene Propylene Diene Monomer Rubber 0.018 in
Color Chart
Number Color
1
2
3
4
5
Brown
Green
White
Black
Red
Outer Shield Material
Material
Unshielded
Outer Jacket Material
Material Nominal Diameter Nominal Wall Thickness Separator Material
Rubber
0.28 in
0.031 in
Paper Tape
Construction and Dimensions
Stranding
Lay Length
Black mm
Cabling
Filler
Jute
Print Legend:
BELDEN 8455 (UL logo) AWM 4256 E12683
Electrical Characteristics
Shielding:
Current
Unshielded
Element Max. Recommended Current [A]
20 AWG 4 Amps
18 AWG 5.6 Amps
Voltage
Dielectric Withstand Voltage UL Voltage Rating
1500 V AC Applied for 1 Min.
Electrical Characteristics Notes:
Other Electrical Characteristic 2:
300 V RMS
20 AWG MAX CURRENT 4A
18 AWG MAX CURRENT 5.6A
Temperature Range
UL Temp Rating:
60°C
Mechanical Characteristics
Bulk Cable Weight:
Min Bend Radius/Minor Axis:
48 lbs/1000ft
3 in
Standards
UL AWM Style:
UL Style 4256 (300 V 60°C)
Applicable Environmental and Other Programs
EU Directive 2000/53/EC (ELV):
EU Directive 2003/96/EC (BFR):
EU Directive 2011/65/EU (ROHS II):
EU Directive 2012/19/EU (WEEE):
EU Directive Compliance:
EU CE Mark:
Yes
Yes
Yes
Yes
EU Directive 2003/11/EC (BFR)
Yes
EU RoHS Compliance Date (yyyy-mm-dd): 2005-10-13
CA Prop 65 (CJ for Wire & Cable):
MII Order #39 (China RoHS):
Yes
Yes
Flammability, LS0H, Toxicity Testing
UL voltage rating:
300 V RMS
Plenum/Non-Plenum
Plenum (Y/N):
No
Part Number
Variants
Item #
8455 010250
Color Footnote
Black
C
8455 010U1000 Black
8455 010U500
Footnote:
Black
C - CRATE REEL PUT-UP.
© 2018 Belden, Inc
All Rights Reserved.
Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications described here in are subject to error or omission and to change without
notice, and the listing of such information and specifications does not ensure product availability.
Belden provides the information and specifications herein on an "ASIS" basis, with no representations or warranties, whether express, statutory or implied. In no event will Belden be liable for any damages
(including consequential, indirect, incidental, special, punitive, or exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether in an action under contract,
negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein.
All sales of Belden products are subject to Belden's standard terms and conditions of sale.
Belden believes this product to be in compliance with all applicable environmental programs as listed in the data sheet. The information provided is correct to the best of Belden's knowledge, information and belief
at the date of its publication. This information is designed only as a general guide for the safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. The Product
Disclosure is not to be considered a warranty or quality specification. Regulatory information is for guidance purposes only. Product users are responsible for determining the applicability of legislation and
regulations based on their individual usage of the product.