EEWORLDEEWORLDEEWORLD

Part Number

Search

DHR400C420

Description
AC/DC Current transducer
File Size771KB,3 Pages
ManufacturerLEM
Websitehttp://www.lem.com
Download Datasheet Compare View All

DHR400C420 Overview

AC/DC Current transducer

AC/DC Current transducer DHR-C420
The transducer for the electronic measurement of DC & distorted AC
waveform currents, with galvanic isolation between the primary circuit
(power) and the secondary circuit (measurement). True RMS 4-20mA
current output.
I
PN
= 100..1000 A
Features
Electrical data
Primary Nominal
DC & AC Current
I
PN
(A.t.RMS)
100
200
300
400
500
600
1000
Primary AC Current
Max. Peak Value
(
*
)
I
P
(A)
600
600
1000
1000
1800
1800
1800
Output current
I
OUT
(mADC)
4-20
4-20
4-20
4-20
4-20
4-20
4-20
DHR 100 C420
DHR 200 C420
DHR 300 C420
DHR 400 C420
DHR 500 C420
DHR 600 C420
DHR 1000 C420
Type
VFD and SCR waveforms current
measurement
True RMS output
4-20mA current output
Panel mounting
Eliminates insertion loss
Insulated plastic case recognized
according to UL94-V0
R
L
V
C
I
C
I
SL
Î
P
Load resistance
Supply voltage
Current consumption
Output current limitation
Overload capability (Ampere Turns)
< 300
+ 20 .. 50 V DC
30 mA +
I
OUT
< 25
mA
30000
A.t
Advantages
Large aperture for cable up to
Ø32mm
High isolation between primary and
secondary circuits
Easy installation
Performance data
ε
X
L
I
OE
TCI
OE
TCI
OUT
t
r
BW
Accuracy @
I
PN
,
T
A
= 25°C (excluding offset)
Linearity error (1% of
I
PN
.. ±
I
PN
)
Electrical offset current,
T
A
= 25°C
Temperature coefficient of
I
OE
( 0..+60 °C)
(-40..+70 °C)
Temperature coefficient of
I
OUT
(% of reading)
Response time to 90% of
I
PN
step
Frequency bandwidth (±1dB)
< ± 1 % of
I
PN
< ± 1.0 % of
I
PN
4
mA
± 3.2
µA/K
± 6.4
µA/K
± 0.1
%/K
< 150
ms
DC 20..6000Hz
Applications
VFD Controlled Loads
VFD output indicates how the motor
and attached load are operating.
SCR Controlled Loads
Acurate measurement of phase
angle fired or burst fired (time
proportioned)
General data
T
A
T
S
m
IPxx
Ambient operating temperature
Ambient storage temperature
Mass
Protection degree
- 40 .. + 70
- 40 .. + 85
260
IP20
°C
°C
g
SCRs. Current measurement gives
faster response than temperature
measurement.
Switching Power Supplies and
Electronic Ballasts
True RMS sensing is the most
accurate way to measure power
supply or ballast input power.
Note :
* The Max. Peak AC Current is the highest peak level of the primary signal that is
taken into account for accurate True RMS calculation. Yet the device is designed for
maximum continuous True RMS value equal to I
PN
, whereas the output is limited by
the above specified output limitation.
( )
Application domain
Energy and Automation
Page 1/3
061128/14
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
www.lem.com

DHR400C420 Related Products

DHR400C420 DHR-C420 DHR100C420 DHR300C420 DHR600C420 DHR500C420 DHR1000C420
Description AC/DC Current transducer AC/DC Current transducer AC/DC Current transducer AC/DC Current transducer AC/DC Current transducer AC/DC Current transducer AC/DC Current transducer

Technical ResourceMore

EEWorld
subscription
account

EEWorld
service
account

Automotive
development
circle

Robot
development
community

Index Files: 1738  159  2646  1829  97  35  4  54  37  2 
Datasheet   0 1 2 3 4 5 6 7 8 9 A B C D E F G H I J K L M N O P Q R S T U V W X Y Z
Room 1530, 15th Floor, Building B, No. 18 Zhongguancun Street, Haidian District, Beijing Telephone: (010) 82350740 Postal Code: 100190
Copyright © 2005-2026 EEWORLD.com.cn, Inc. All rights reserved 京ICP证060456号 京ICP备10001474号-1 电信业务审批[2006]字第258号函 京公网安备 11010802033920号