EMC filters
3-phase line reactors for converters
4 A ... 390 A, 40
°C,
50/60 Hz
Series/Type:
Date:
B86305L
May 2014
© EPCOS AG 2015. Reproduction, publication and dissemination of this publication, enclosures hereto and the
information contained therein without EPCOS' prior express consent is prohibited.
EPCOS AG is a TDK Group Company.
Line reactors, output chokes and output filters
3-phase line reactors for converters
B86305L
3-phase line reactors for converters
Rated voltage V
R
: 520 V AC
Rated current I
R
: 4 A to 390 A
Construction
3-phase line reactor
Natural cooling
Features
Easy to install
Low weight
Compact design
Design complies with IEC 60076-6
Degree of protection
1)
:
IP20 (4 A ... 16 A)
IP10 (30 A ... 60 A)
IP00 (100 A ... 390 A)
Inductance constant up to 1.5
×
I
R
Inductance higher than 60% rated value at 3
×
I
R
UL approved insulation system
T-EIS-CF1
Typical applications
Frequency converters for motor drives, e.g.
elevators
pumps
traction systems
conveyor systems
HVAC systems (heating, ventilation and air
conditioning)
Power supplies
Terminals
Finger-safe terminal blocks (< 100 A)
Busbars from 100 A, cross section 20
×
3 mm
Marking
Marking on component:
Manufacturer's logo, ordering code, rated current, rated
frequency, inductance, approximate weight, date code
Minimum data on packaging:
Manufacturer's logo, ordering code, quantity, date code
1) According to IEC 60529
Please read
Cautions and warnings
and
Important notes
at the end of this document.
Page 2 of 11
Line reactors, output chokes and output filters
3-phase line reactors for converters
B86305L
Technical data and measuring conditions
Rated voltage V
R
Rated current I
R
Test voltage V
test
Relative voltage drop u
k
in %
Insulation class
Overload capability (thermal)
Climatic category (IEC 60068-1)
Approvals
Characteristics and ordering codes
I
R
*
A
u
k
%
R
typ1)
mΩ
335.0
78.0
42.2
12.4
6.2
3.2
0.9
0.6
L
R2)
mH
10.0
4.0
2.0
1.0
0.5
0.3
0.15
0.075
P
L3)
W
25
43
65
50
100
160
340
480
Approx. weight
kg
1.3
2.7
3.1
5.5
8.5
15.0
32.0
44.0
Ordering code
520 V AC (50/60 Hz)
Referred to 40
°C
rated temperature
1100 V AC, 2 s (line/line)
2500 V AC, 2 s (lines/case)
At I
R
; 50 Hz and 400 V AC
F (155
°C)
3 I
R
, t < 3 s in 300 s
25/100/21 ( 25
°C/+100 °C/21
days damp heat test)
Insulation system class 155 (F); T-EIS-CF1 UL 1446
V
R
= 520 V AC
4
5.4
10
5.4
16
4.4
30
4.1
60
4.1
100
4.1
230
4.7
390
4.0
B86305L0004R000
B86305L0010R000
B86305L0016R000
B86305L0030R000
B86305L0060R000
B86305L0100S000
B86305L0230S000
B86305L0390S000
* Higher current values upon request
1) Typical value at 20
°C,
tolerance
±10%
2) Tolerance 0%/+20%,
3) At I
R
, 50 Hz, 20
°C
Please read
Cautions and warnings
and
Important notes
at the end of this document.
Page 3 of 11
Line reactors, output chokes and output filters
3-phase line reactors for converters
B86305L
Dimensional drawings
B86305L0004R000 ... B86305L0016R000 (4 A ... 16 A)
Ordering code
A
B
135
150
150
C
60
90
90
D1
×
D2
6
×
9
6
×
12
6
×
12
E
80
100
100
G
40
60
60
G1
60
80.5
80.5
H
42
62
62
X
40
50
50
B86305L0004R000 100
B86305L0010R000 130
B86305L0016R000 130
General tolerances according to ISO 2768 cL
Dimensions in mm
Please read
Cautions and warnings
and
Important notes
at the end of this document.
Page 4 of 11
Line reactors, output chokes and output filters
3-phase line reactors for converters
B86305L
B86305L0030R000, B86305L0060R000 (30 A, 60 A)
Ordering code
A
B
C
E
F
G
G1
H
Q
MK
2
(mm ) (Nm)
16
PE D PE MP
(Nm)
1.2±0.1
3.0±0.15
B86305L0030R000 155 170 135 125 120 75
B86305L0060R000 180 205 150 150 135 85
107 90
2.0-2.3 M4
3.2-3.7 M6
122 105 35
General tolerances according to ISO 2768 cL
Dimensions in mm
Please read
Cautions and warnings
and
Important notes
at the end of this document.
Page 5 of 11