Power Protection and Conditioning
MCR Portable Series – Power Line Conditioning with Voltage Regulation
The MCR provides excellent noise filtering and surge
protection to protect connected equipment from damage,
degradation or misoperation. Combined with the excellent
voltage regulation inherent to SolaHD’s ferroresonant design,
they can increase the actual Mean Time Between
Failure (MTBF) of protected equipment. These units are a
perfect choice where dirty power caused by impulses, swell,
sags, brownouts and waveform distortion can lead to costly
downtime because of damaged equipment.
Applications
• Computers/ Printers
• Telephone/FAX systems
• POS terminals
• Security systems
• Laboratory equipment
• LAN networks
Features
• ±3% output voltage regulation
• Noise attenuation
- 120 dB common mode
- 60 dB transverse mode
• Surge protection tested to ANSI/IEEE C62.41
Class A & B waveform (<10 V let-through typical)
• Harmonic filtering
• Galvanic isolation provides exceptional
circuit protection.
• Point-of-use protection (cord & plug connected)
- Easy & Flexible Installation
• 25 year typical MTBF
• No maintenance required
E47379 LR044950
Certifications and Compliances
All Models
• RoHS Compliant
•
Listed
- UL 1012
Select Models
•
•
Listed (1500VA Units)
- UL 1012, CSA C22.2 No. 66
Certified (70VA-1kVA Units)
- CSA C22.2 No. 66
Related Products
• DIN Rail AC UPS (SDU)
• Off-Line UPS (S1K Mini-Tower)
• Line-Interactive UPS (S3K Mini-Tower)
Selection Tables: Single Phase
Group A – MCR Portable Series, 60 Hz
VA
70
150
250
500
750
1000
1500*
2000
3000*
*
*
Catalog
Number
63-13-070-6
63-13-115-6
63-13-125-6
63-13-150-6
63-13-175-6
63-13-210-6
63-13-215-6
63-13-220-6
63-13-230-6
Voltage
Input/Output
120
120
120
120
120
120
120
120
120
Height
in (mm)
Width
in (mm)
Depth
in (mm)
9.00 (228.6)
9.00 (228.6)
9.00 (228.6)
Ship Weight
lbs (kg)
18.0 (8.16)
21.0 (9.53)
26.0 (11.79)
32.0 (14.51)
64.0 (29.03)
69.0 (31.30)
95.0 (43.09)
115.0 (52.16)
143.0 (64.86)
Receptacle (No.)
Type (NEMA)
(4) 5-15R
(4) 5-15R
(4) 5-15R
(4) 5-15R
(4) 5-15R
(4) 5-15R
(6) 5-15R
(4) 5-15R, (1) L5-30R
(4) 5-15R, (1) L5-30R
Plug
(NEMA)
5-15P
5-15P
5-15P
5-15P
5-15P
5-15P
5-20P
L5-30P
5-50P
6.00 (152.4) 7.00 (177.8)
6.00 (152.4) 7.00 (177.8)
6.00 (152.4) 7.00 (177.8)
9.00 (228.6) 9.00 (228.6) 16.00 (406.4)
9.00 (228.6) 9.00 (228.6) 16.00 (406.4)
9.00 (228.6) 9.00 (228.6) 16.00 (406.4)
11.00 (279.4) 11.00 (279.4) 17.00 (431.8)
11.00 (279.4) 11.00 (279.4) 17.00 (431.8)
11.00 (279.4) 11.00 (279.4) 17.00 (431.8)
Only
48
Visit our website at www.emerson.com or contact Technical Services at (800) 377-4384 with any questions.
© January 2017
Power Protection and Conditioning
Specifications
Parameter
Condition
Input
Voltage
Current
1
Frequency
Line Regulation
Overload Protection
Output Harmonic Distortion
Noise Attenuation
Let-Through
Efficiency
Storage Temperature
Operating Temperature
Audible Noise
Warranty
Notes:
1 - It is recommended that the unit run at a minimum of 40-50% load.
Continuous at full load (lower input voltage possible at lighter load)
For temporary surge or sags
At Full Load & 80% of nominal input voltage
See Operating Characteristics section for details.
Output
1
V
in
>80% and <110% of nominal
At Nominal Input Voltage
At full load within input range
-Common Mode
-Transverse Mode
ANSI/IEEE C62.41 Class A & B Waveform
General
At Full Load
Humidity <95% non-condensing
Humidity <95% non-condensing
Full Resistive Noise
10 + 2 year limited warranty
Value
+10% to -20% of nominal
+20% to -35% of nominal
I
in
≅
(VA/.89)/(V
in
x 80%)
60 Hz depending on model
±
3% for 60 Hz units
Current limited at 1.65 times rated current
3% total RMS content
120 dB
60 dB
<10V typical
92% Typical
-20° to +85°C
-20° to 40°C
35 dBA to 65 dBA
Back Panels
Plug & Receptacle Reference Chart
5-15P
5-15R
L5-30P
60 Hz, 70 – 1000 VA,
(4) 5-15R Receptacles
60 Hz, 2000–3000 VA,
(4) 5-15R and (1)
L5-30R Receptacle
Visit our website at www.emerson.com or contact Technical Services at (800) 377-4384 with any questions.
© January 2017
49
Power Protection and Conditioning
Model Comparison
Description
VA Ratings
Input Voltage Range
Voltage Regulation
Overload
Output Harmonic
Distortion
Noise Isolation
Surge Protection
Efficiency
Operating
Temperature
Audible Noise
Warranty
Note: All values are typical and may vary based on VA ratings of actual units.
32 dB to 65 dB
40 dB common and normal code.
Up to 6000 Volt surges are suppressed to a
let through of less than 1% per ANSI/IEEE
C62.41 Class A & B waveforms.
Up to 92% at full load
-20
o
C to 50
o
C
35 dB to 65 dB
10 year limited warranty
±1% for an input line variation of +10/-20%.
No loss of output for line loss of 3 msec.
Hardwired CVS
30 to 7500 VA
Hardwired MCR
120 to 15000 VA
+10/-20% of nominal
±3% for an input line variation of +10/-20% (50 Hz hardwired units ±5%.)
No loss of output for complete line loss of 3 msec.
Portable MCR
70 to 3000 VA
Limits output current to 1.65 x rated current at nominal input.
3% total RMS content at full load.
120 dB common mode and 60 dB normal mode.
ANSI/IEEE C62.41 Class A & B 6000 waveforms are
suppressed to a let-through of less than 0.2%.
Up to 90% at full load
-20
o
C to 40
o
C
34 dB to 49 dB
BTU Output Chart for CVS and MCR Series
VA Ratings
Total BTUs
120
136
250
225
500
280
750
444
1000
519
1500
686
2000
1229
3000
1331
5000
2117
7500
2407
10000
3209
15000
4813
Note: Ratings are for a 40
o
C ambient temperature.
50
Visit our website at www.emerson.com or contact Technical Services at (800) 377-4384 with any questions.
© January 2017