https://www.phoenixcontact.com/us/products/2800106
Lightning arrester type 1 - FLT 25-400 - 2800106
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Type 1 / Class I / B arrester (lightning current arrester) with arc chopping spark gap, 1-channel. Housing width:
17.5 mm (1 Div.)
Product Features
High discharge capacity
Single-channel
Key Commercial Data
Packing unit
Weight per Piece (excluding packing)
Custom tariff number
Country of origin
1 pc
180.0 g
85363010
Germany
Technical data
Dimensions
Height
Width
Depth
Horizontal pitch
90 mm
17.7 mm
65.5 mm
1 Div.
Ambient conditions
Degree of protection
Ambient temperature (operation)
Ambient temperature (storage/transport)
Altitude
Permissible humidity (operation)
IP20 (only when all terminal points are used)
-40 °C ... 85 °C
-40 °C ... 85 °C
≤ 2000 m (amsl (above mean sea level))
5 % ... 95 %
General
IEC power supply system
TN-S
12/02/2015 Page 1 / 4
https://www.phoenixcontact.com/us/products/2800106
Lightning arrester type 1 - FLT 25-400 - 2800106
Technical data
General
TN-C
TT
Housing material
Flammability rating according to UL 94
Color
Standards for cearances and creepage distances
Mounting type
Type
Number of positions
Surge protection fault message
Direction of action
PA 6.6
V-0
black
EN 60664-1
EN 61643-11
DIN rail: 35 mm
Rail-mountable module, one-piece
1
None
1L-N/PE
Protective circuit
IEC test classification
EN type
Nominal voltage U
N
Maximum continuous operating voltage U
C
(L-PEN)
U
T
(TOV-proof)
TOV behavior at U
T
Nominal frequency f
N
Rated load current I
L
Residual current I
PE
Standby power consumption P
C
Nominal discharge current I
n
(8/20) µs (L-PEN)
Front of wave sparkover voltage at 6 kV (1.2/50) µs
Voltage protection level U
p
(L-PEN)
Response time t
A
(L-PE)
Max. backup fuse with branch wiring
Max. backup fuse with V-type through wiring
Short-circuit resistance I
P
with max. backup fuse (effective)
Short-circuit current rating I
SCCR
Follow current quenching capacity I
fi
(L-PEN)
I
T1
T1
230/400 V AC (TN)
440 V AC
440 V (5 sec.)
<p></p>
50 Hz (60 Hz)
80 A
≤ 0.1 mA
≤ 44 mVA
25 kA
≤ 5 kV
≤ 5 kV
≤ 100 ns
250 A AC (gG)
80 A AC (gG)
25 kA
2.5 kA
2.5 kA
Connection, protective circuit
Connection method
Connection type IN
Screw connection
Biconnect screw terminal block
12/02/2015 Page 2 / 4
https://www.phoenixcontact.com/us/products/2800106
Lightning arrester type 1 - FLT 25-400 - 2800106
Technical data
Connection, protective circuit
Connection type OUT
Connection method
Screw thread
Tightening torque
Stripping length
Conductor cross section flexible min.
Conductor cross section flexible max.
Conductor cross section solid min.
Conductor cross section solid max.
AWG conductor cross section
Biconnect screw terminal block
Biconnect terminal block
M5
4.5 Nm
14.5 mm
2.5 mm²
25 mm²
2.5 mm²
35 mm²
6 ... 2
Standards and Regulations
Standards/regulations
IEC 61643-11 2011
EN 61643-11 2012
Classifications
eCl@ss
eCl@ss 4.0
eCl@ss 4.1
eCl@ss 5.0
eCl@ss 5.1
eCl@ss 6.0
eCl@ss 7.0
eCl@ss 8.0
27140201
27140201
27140201
27140201
27140201
27140201
27130802
ETIM
ETIM 2.0
ETIM 3.0
ETIM 4.0
ETIM 5.0
EC000381
EC000381
EC000381
EC000381
UNSPSC
UNSPSC 6.01
UNSPSC 7.0901
UNSPSC 11
UNSPSC 12.01
UNSPSC 13.2
30212010
39121610
39121610
39121610
39121620
12/02/2015 Page 3 / 4
https://www.phoenixcontact.com/us/products/2800106
Lightning arrester type 1 - FLT 25-400 - 2800106
Approvals
Approvals
Approvals
EAC / EAC
Ex Approvals
Approvals submitted
Approval details
EAC
EAC
Drawings
Dimensional drawing
90
17,7
Circuit diagram
L/N ( )
L/N ( )
Phoenix Contact 2015 © - all rights reserved
http://www.phoenixcontact.com
65,5
58
12/02/2015 Page 4 / 4