EEWORLDEEWORLDEEWORLD

Part Number

Search

8340-F910-P1M2-BHH0-20A

Description
CIR BRKR MAG 20A 240VAC 80VDC
CategoryCircuit protection   
File Size455KB,6 Pages
ManufacturerE-Switch
Websitehttp://www.e-switch.com
Environmental Compliance
Download Datasheet Parametric View All

8340-F910-P1M2-BHH0-20A Online Shopping

Suppliers Part Number Price MOQ In stock  
8340-F910-P1M2-BHH0-20A - - View Buy Now

8340-F910-P1M2-BHH0-20A Overview

CIR BRKR MAG 20A 240VAC 80VDC

8340-F910-P1M2-BHH0-20A Parametric

Parameter NameAttribute value
Circuit breaker typeMagnetic
Rated current20A
Rated voltage - AC240V
Rated voltage - DC80V
Number of poles1
Actuator typepress slice
illumination-
Lighting voltage (nominal)-
Installation typePanel mounting
Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-F...
Description
Single and multipole magnetic circuit breakers with trip-free
mechanism and toggle actuation. A choice of fast magnetic only or
hydraulically delayed switching characteristics (S-type MO or HM
CBE to EN 60934) ensures suitability for a wide range of applications.
Industry standard dimensions and panel mounting. Options include
auxiliary changeover contacts. Low temperature sensitivity at rated
load.
Approved to CBE standard EN 60934 (IEC 60934).
Typical application
Control equipment, communications systems, transportation, power
supplies.
1-pole
8340-F...
1
2-pole
Standard current ratings and typical internal resistance values
Current
rating (A)
0,02
0,05
0,1
0,25
0,5
0,75
1
2
2,5
3
5
6
8
10
12
15
16
20
25
30
40
50
Internal resistance values (Ω) per pole
F1
1 493
276
58
8,2
2,3
0,98
0,58
0,145
0,096
0,065
0,025
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,01
< 0,01
953
152
37
6,0
1,47
0,63
0,35
0,096
0,061
0,048
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
-
-
F2
K1, M1, T1
2 669
452
100
15,5
3,9
1,65
0,95
0,26
0,15
0,10
0,042
0,029
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,01
< 0,01
K2, M2, T2
2 457
376
94
14,7
3,2
1,56
0,90
0,20
0,15
0,10
0,040
0,028
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
< 0,02
-
-
Technical data
For further details please see chapter: Technical Information
Voltage rating
3 AC 415 V; AC 240 V, 50/60 Hz; DC 80 V
(higher DC ratings to special order)
Current ratings
0.02...50 A DC
0.02...30 A AC
Auxiliary circuit
6 A, AC 240 V;
3 A, DC 28 V
1 A, DC 65 V;
0.5 A, DC 80 V
Typical life
3 AC 415 V, AC 240 V:
0.02...30 A
6,000 operations at 1 x I
N
, inductive
10,000 operations at 1 x I
N
, resistive
DC 80 V: 0.02...25 A
6,000 operations at 1 x I
N
, inductive
0.02...30 A
10,000 operations at 1 x I
N
, resistive
40 + 50 A
6,000 operations at 1 x I
N
, resistive
Ambient temperature
-40...+85 °C (-40...+185 °F)
Insulation co-ordination
rated impulse
pollution
(IEC 60664 and 60664A) withstand voltage
degree
2.5 kV
2
reinforced insulation in operating area
Dielectric strength
(IEC 60664 and 60664A)
operating area
test voltage AC 3,000 V
Line to Load
test voltage AC 1,500 V
pole to pole
(2- and 3-pole)
test voltage AC 1,500 V
main to auxiliary circuit
test voltage AC 3,000 V
switching to trip circuit
test voltage AC 1,500 V
(version -X)
Insulation resistance
> 100 MΩ (DC 500 V)
Interrupting capacity
6 x IN at AC;
IEC 60934 - test sequence E 4 x IN at DC
Interrupting capacity
(UL 1077)
AC:
1-pole
2-pole
3-pole
1-pole
2-pole
I
N
0.02...20 A
25...30 A
AC 250 V/3,500A AC 250 V/3,500A
AC 250 V/3,500A AC 250 V/5,000A
3AC 250V/3,500A 3AC250V/5,000A
0.02...50 A
0.02...30 A
DC 80 V/3,500 A
DC 80 V/3500 A
DC:
Degree of protection
(IEC 60529/DIN 40050)
Vibration
with toggle down:
directions 1, 2, 3, 4, 5:
Shock
Corrosion
Humidity
Mass
1747
www.e-t-a.de
operating area IP40
terminal area IP00
10 g (57-2000Hz) ± 0.76 mm (10-57 Hz)
at 0.9 x IN
10 g (57-2000 Hz) at 1 x IN.
100 g (11 ms) at 1 x IN, directions 1,2,3,4,5
100 g (11 ms) at 0.8 x IN, direction 6.
96 hours at 5 % salt mist,
to IEC 60068-2-11, test Ka
240 hours at 95 % RH
to IEC 60068-2-78, test Cab
approx. 65 g per pole
1
Which great friend has information about visual building doorbell?
I would like to ask the experts to give me some wiring diagrams and schematic diagrams of the community video intercom doorbell. Thank you very much...
佟维新 Industrial Control Electronics
Problems with using superheterodyne wireless modules
When transmitting PPM data on a superheterodyne wireless module, it is found that the first low level of each data is jittered severely, and the width of other low levels also increases. What is the c...
zhenshuibian RF/Wirelessly
Makers' wearable designs take care of the elderly and enable them to live independently
Reprinted from deyisupport [align=left][color=#000]When you think of wearables, what images come to mind? Perhaps a young woman tracking her miles on a long run. Perhaps a middle-aged person checking ...
maylove Microcontroller MCU
Can the microcontroller read data in the FPGA like reading RAM?
Can the MCU AT89C51 read the data in FPGA like reading RAM? Has anyone done it? How to read it, using parallel port or serial port? Thanks for your answer!...
qinyonglyz MCU
The problem of Chinese character array being too large!!! Someone has mentioned it before, but the solution is the problem of small array!
Each Chinese font structure is defined as typedef struct typFNT_GB16 { unsigned char index[2]; // Chinese character internal code index unsigned char dot_data[32]; // dot code data}FONT_GB16; The arra...
stonecyk Embedded System
Microcontroller Programming Experience
[align=center][url=http://crazybc.com/forum-196-1.html][size=4]Microcontroller Programming Experience[/size][/url][/align] 1. Processing of delay programs: 1. For microcontrollers that can set the sys...
疯狂编程 51mcu

EEWorld
subscription
account

EEWorld
service
account

Automotive
development
circle

Robot
development
community

Index Files: 172  574  557  344  972  4  12  7  20  27 
Datasheet   0 1 2 3 4 5 6 7 8 9 A B C D E F G H I J K L M N O P Q R S T U V W X Y Z
Room 1530, 15th Floor, Building B, No. 18 Zhongguancun Street, Haidian District, Beijing Telephone: (010) 82350740 Postal Code: 100190
Copyright © 2005-2026 EEWORLD.com.cn, Inc. All rights reserved 京ICP证060456号 京ICP备10001474号-1 电信业务审批[2006]字第258号函 京公网安备 11010802033920号