480W Single Output Switching Power Supply
HEP-480
series
5
IP65 IP68
(optional)
■
Features
Universal AC input / Full range(up to 305VAC)
Built-in active PFC function
High efficiency up to 95%
Fanless design, cooling by free air convection
-55~+65
℃
wide operating range
Aluminum case and filling with heat-conducted silicone
IP65 design, optional IP68 rated model available
Meet 6KV surge immunity level
Withstand 10G vibration test
Operating altitude up to 5000 meters (Note.7)
Protections: Short circuit / Overload / Over voltage
/ Over temperature
6 years warranty
■
Applications
Outdoor telecommunication equipment
Outdoor electronic signage and billboard
Petroleum plant or mine shaft facility
■
Description
HEP-480 is a 480W industrial AC/DC power supply featuring the outstanding capability to operate under
highly humid, dusty, oily, and high-vibration harsh environment. The entire series is housed with the
aluminum case and fully potted with heat-conducted silicone. Thanks to state-of-the-art design, the working
efficiency is up to 95%, enabling HEP-480 perfectly work between -55
℃
and +65
℃
under free air convection.
■
Model Encoding
HEP - 480 - 24 A
Function mode option
Output voltage
Output wattage
Series name
{
A : Standard model, IP65, Vo and
I
o level can be adjusted
through internal potentiometer.
Blank : Optional model, IP68, with fixed Vo and
I
o level.
File Name:HEP-480-SPEC 2018-03-30
480W Single Output Switching Power Supply
SPECIFICATION
MODEL
DC VOLTAGE
RATED CURRENT
RATED POWER
HEP-480-24
24V
20A
480W
HEP-480
HEP-480-48
48V
10A
480W
series
HEP-480-36
36V
13.3A
478.8W
HEP-480-54
54V
8.9A
480.6W
RIPPLE & NOISE (max.)
Note.2
200mVp-p
VOLTAGE ADJ. RANGE
Note.5
OUTPUT
CURRENT ADJ. RANGE
20.4 ~ 25.2V
10 ~ 20A
250mVp-p
30.6 ~ 37.8V
6.6 ~ 13.3A
250mVp-p
40.8 ~ 50.4V
5 ~ 10A
350mVp-p
45.9 ~ 56.7V
4.4 ~ 8.9A
Adjusted
for A-type only (via built-in potentiometer)
Adjusted
for A-type only (via built-in potentiometer)
VOLTAGE TOLERANCE
Note.3
±
1.0%
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
FREQUENCY RANGE
POWER FACTOR (Typ.)
INPUT
EFFICIENCY (Typ.)
AC CURRENT (Typ.)
INRUSH CURRENT(Typ.)
±
1.0%
±
0.5%
±
1.0%
±
0.5%
±
0.5%
±
1.0%
±
0.5%
±
0.5%
±
0.5%
±
0.5%
±
0.5%
Note.4
500ms, 80ms 115VAC/230VAC
16ms
115VAC/230VAC
127 ~ 431VDC
Note.5
90 ~ 305VAC
47 ~ 63Hz
PF
≧
0.98/115VAC, PF
≧
0.97/230VAC, PF
≧
0.95/277VAC at full load
94%
95%
2A/277VAC
94.5%
95%
5A / 115VAC
2.45A / 230VAC
COLD START 35A at 230VAC
LEAKAGE CURRENT
OVER CURRENT
PROTECTION
SHORT CIRCUIT
OVER VOLTAGE
OVER TEMPERATURE
WORKING TEMP.
WORKING HUMIDITY
ENVIRONMENT STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
<0.75mA / 277VAC
105 ~ 125%
Constant current limiting, recovers automatically after fault condition is removed
Constant current limiting, recovers automatically after fault condition is removed
27 ~ 33V
40 ~ 50V
53 ~ 63V
Shut down output voltage, re-power on to recover
60 ~ 70V
Shut down
output
voltage,
re-power on to recover
-55 ~ +65
℃
(Refer to "Derating Curve")
20 ~ 95% RH non-condensing
-60 ~ +80
℃
, 10 ~ 95% RH non-condensing
±
0.02%/
℃
(0 ~ 60
℃
)
20 ~ 500Hz, 10G 12min./1cycle, period for 72min. each along X, Y, Z axes
I/P-O/P:3.75KVAC
I/P-FG:2KVAC
O/P-FG:1.5KVAC
SAFETY STANDARDS
Note.7
UL60950-1, IP65 (or IP68 for HEP-480 Blank-Type),
EAC TP TC 004 approved ; design refer to TUV EN60950-1
SAFETY &
EMC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25
℃
/ 70% RH
Compliance to
EN55032 (CISPR32) Class B, EN61000-3-2,-3
,
EAC TP TC 020
EMC EMISSION
EMC IMMUNITY
MTBF
OTHERS
NOTE
DIMENSION
PACKING
Compliance to
EN61000-4-2,3,4,5,6,8,11, EN55024
,
light
industry level (surge 6KV), criteria A,
EAC TP TC 020
89.8K hrs min. MIL-HDBK-217F (25
℃
)
262*125*43.8mm (L*W*H)
2.8Kg;4pcs/11.5Kg/0.55CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25
℃
of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. Length of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the setup time.
5. Derating may be needed under low input voltages. Please refer to the STATIC CHARACTERISTICS for more details.
6. The power supply shall be regarded as one component of the final system. The EMC performance will be affected by the complete system installation
and/or configuration, the final system manufacturers must re-verify overall EMC directive with the complete installation and/or configuration.
7. The water protection level test for the IP68 rating is performed 1000mm below the surface of the water for 1 month.
8. Please refer to the warranty statement on MEAN WELL's website at http://www.meanwell.com
9. The ambient temperature derating of 3.5
℃
/1000m with fanless models and of 5
℃
/1000m with fan models for operating altitude higher than 2000m(6500ft).
File Name:HEP-480-SPEC 2018-03-30