Detailed Specifications & Technical Data
METRIC MEASUREMENT VERSION
5400F1 Multi-Conductor - Water-Blocked for Use in Underground Ducts - 2 Cond Cabled
For more Information
please call
1-800-Belden1
General Description:
Security & Alarm Cable, Rated-CM, 2-20 AWG stranded tinned copper conductors with PVC insulation,
waterblocking tape, Beldfoil® shield and PVC jacket with ripcord
Physical Characteristics (Overall)
Conductor
AWG:
# Conductors AWG Stranding Conductor Material
2
20
7x28
TC - Tinned Copper
2
Total Number of Conductors:
Insulation
Insulation Material:
Insulation Material
Wall Thickness (mm)
PVC - Polyvinyl Chloride 0.254
Outer Shield
Outer Shield Material:
Outer Shield Trade Name Outer Shield Material
Beldfoil®
Aluminum Foil-Polyester Tape
Outer Shield Drain Wire AWG:
AWG Stranding Drain Wire Conductor Material
24
solid
TC - Tinned Copper
Non-woven waterblocking tape
Outer Shield Waterblocking Tape:
Outer Jacket
Outer Jacket Material:
Outer Jacket Material
Nom. Wall Thickness (mm)
PVC - Polyvinyl Chloride 0.635
Outer Jacket Ripcord:
Yes
Overall Cable
Overall Cabling Lay Length & Direction:
Length (mm)
50.7998
Overall Nominal Diameter:
5.232 mm
Mechanical Characteristics (Overall)
Operating Temperature Range:
Bulk Cable Weight:
Max. Recommended Pulling Tension:
Min. Bend Radius/Minor Axis:
-20°C To +105°C
28.276 Kg/Km
165.028 N
50.800 mm
Applicable Specifications and Agency Compliance (Overall)
Applicable Standards & Environmental Programs
NEC/(UL) Specification:
CEC/C(UL) Specification:
EU Directive 2011/65/EU (ROHS II):
EU CE Mark:
EU Directive 2000/53/EC (ELV):
EU Directive 2002/95/EC (RoHS):
EU RoHS Compliance Date (mm/dd/yyyy):
EU Directive 2002/96/EC (WEEE):
CM
CM
Yes
Yes
Yes
Yes
10/01/2005
Yes
Page 1 of 2
09-11-2017
Detailed Specifications & Technical Data
METRIC MEASUREMENT VERSION
5400F1 Multi-Conductor - Water-Blocked for Use in Underground Ducts - 2 Cond Cabled
EU Directive 2003/11/EC (BFR):
CA Prop 65 (CJ for Wire & Cable):
MII Order #39 (China RoHS):
Yes
Yes
Yes
Flame Test
UL Flame Test:
CSA Flame Test:
UL1685 UL Loading
FT1
Plenum/Non-Plenum
Plenum (Y/N):
No
Electrical Characteristics (Overall)
Nom. Inductance:
Inductance (µH/m)
0.55777
Nom. Capacitance Conductor to Conductor:
Capacitance (pF/m)
183.736
Nom. Capacitance Cond. to Other Conductor & Shield:
Capacitance (pF/m)
331.381
Nom. Conductor DC Resistance:
DCR @ 20°C (Ohm/km)
33.7943
Nominal Outer Shield DC Resistance:
DCR @ 20°C (Ohm/km)
58.730
Max. Operating Voltage - UL:
Voltage
300 V RMS
Max. Recommended Current:
Current
3.75 Amps per conductor @ 25°C (10°C rise in temp)
Put Ups and Colors:
Item #
5400F1 0081000
Notes:
C = CRATE REEL PUT-UP.
Putup
1,000 FT
Ship Weight
22.000 LB
Color
GRAY
Notes
C
Item Desc
2 #20 S-R PVC FS PVC
Revision Number: 2
© 2017 Belden, Inc
All Rights Reserved.
Revision Date: 09-12-2013
Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications described herein are subject to error or omission and to
change without notice, and the listing of such information and specifications does not ensure product availability.
Belden provides the information and specifications herein on an "AS IS" basis, with no representations or warranties, whether express, statutory or implied. In no event will Belden be liable for
any damages (including consequential, indirect, incidental, special, punitive, or exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether
in an action under contract, negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein.
All sales of Belden products are subject to Belden's standard terms and conditions of sale.
Belden believes this product to be in compliance with EU RoHS (Directive 2002/95/EC, 27-Jan-2003). Material manufactured prior to the compliance date may be in stock at Belden facilities
and in our Distributor’s inventory. The information provided in this Product Disclosure, and the identification of materials listed as reportable or restricted within the Product Disclosure, is
correct to the best of Belden’s knowledge, information, and belief at the date of its publication. The information provided in this Product Disclosure is designed only as a general guide for the
safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. This Product Disclosure is not to be considered a warranty or quality specification.
Regulatory information is for guidance purposes only. Product users are responsible for determining the applicability of legislation and regulations based on their individual usage of the
product.
Belden declares this product to be in compliance with EU LVD (Low Voltage Directive 2014/35/EU).
Page 2 of 2
09-11-2017