SE-TA24A Overview

TEMP COMPENSATED TERMINATION 18V

Littelfuse Startco Protection Relays
Technical Note - Ground Check
GC-13 : SPLITTER-BOX DUAL-CABLE MONITORING WITH AN SE-135
An SE-135 Ground-Fault Ground-Check Monitor can protect the cables entering and leaving a dual-cable splitter box
(junction box), when one is terminated with an SE-TA24A and the other with an SE-TA24B Termination Assembly.
The SE-MUX was previously used to monitor two ground-check circuits by sampling each ground-check circuit
every half second. As a result, ground-check trip times were increased by up to a half second. The improved
method provides continuous monitoring of both ground-check circuits; therefore ground-check trip times are not
increased, and the complexity of splitter boxes is reduced. Littelfuse recommends replacing the SE-MUX in splitter-
box applications with an SE-TA24A and an SE-TA24B, as shown in Fig. 1.
LOAD 1
SE-CS10/40
ØA, B, C
SPLITTER BOX
GC
L
TRIP A
N
24
22
L1
1
25
UV
G
S E -TA 2 4 A
TE RMI NATION
AS SE M BLY
Use with
SE-135 and
SE-TA24B
24A
!
TRIP B
23
L2
2
CURRENT 16
SENSOR 17
GROUND
CHECK
5
6
LOAD 2
GC
CABLE
GROUND
7
8
G
S E-TA 2 4B
24B
TERM I NATI ON
A SSE M BLY
SE-135
!
Use with
SE-135 and
SE-TA24A
PORTABLE SUBSTATION
Figure 1: Simplified Connection Diagram
When an SE-TA24A and an SE-TA24B are used as a set, the parallel combination has the 12-V Zener characteristic
required by the SE-135 as a valid ground-check-loop termination. An open or short in the ground-check loop of
either cable will result in an SE-135 ground-check trip; no indication is provided of which cable is faulted.
To be able to energize either single cable independently, a live-end cover fitted with an SE-TA24A or an
SE-TA24B, as required, must be available at the splitter box.
WARNING:
Take proper care to prevent an SE-TA12A-series termination assembly from being used in a dual-termination
application with an SE-135. Because a single SE-TA12A will satisfy the SE-135, if an SE-TA12A terminates one (or
both) of the cables on a splitter-box application with an SE-135, the second cable will not be monitored. This can
result in a hazardous condition on the unmonitored cable, where an energized open cable/coupler, an open ground
connection, or a shorted ground-check loop would not be detected. See Fig. 2 for a sample warning label that could
be applied to each cable coupler or beside each SE-TA24A and SE-TA24B installation location.
© 2014 Littelfuse Startco
www.littelfuse.com/relayscontrols
1
Pub. TN-GC12, Revised December 17, 2014

SE-TA24A Related Products

SE-TA24A SE-MUX SE-TA24B
Description TEMP COMPENSATED TERMINATION 18V GF/GC TERM MULTIPLEXER TEMP MULTIPLEX TERMINATION 18V

EEWorld
subscription
account

EEWorld
service
account

Automotive
development
circle

Robot
development
community

Index Files: 2006  1669  2668  2673  243  41  34  54  5  57 
Datasheet   0 1 2 3 4 5 6 7 8 9 A B C D E F G H I J K L M N O P Q R S T U V W X Y Z
Room 1530, 15th Floor, Building B, No. 18 Zhongguancun Street, Haidian District, Beijing Telephone: (010) 82350740 Postal Code: 100190
Copyright © 2005-2026 EEWORLD.com.cn, Inc. All rights reserved 京ICP证060456号 京ICP备10001474号-1 电信业务审批[2006]字第258号函 京公网安备 11010802033920号