SPECIFICATION CONTROL DRAWING
TITLE
Date
FLHT+0312
Revision
HIGH TEMPERATURE HOOKUP WIRE, RADIATION-CROSSLINKED, MODIFIED ETFE-INSULATED, 600 VOLT
The complete requirements for procuring the wire described herein shall consist of this document and the issue in effect of
Raychem Specification WCD 3106, UL Subject 758, Style 3557, File E303150 and carries UL labels to this effect.
8-18-10
G
CONDUCTOR - SILVER-COATED COPPER
INSULATION - RADIATION-CROSSLINKED,
MODIFIED ETFE
TABLE I. CONSTRUCTION DETAILS
FINISHED WIRE
PART NUMBER
1/
WIRE
SIZE
(AWG)
CONDUCTOR
STRANDING
(number x AWG)
NOMINAL
CONDUCTOR
DIAMETER
(in.) (mm)
.015
(.381)
.019
(.483)
.024
(.610)
.030
(.762)
.038
(.965)
.047
(1.19)
.053
(1.35)
.066
(1.68)
.067
(1.71)
.085
(2.16)
MAXIMUM
RESISTANCE
AT 20°C
(ohms/1000 ft.)
(ohms/km)
68.2
42.7
26.7
16.9
10.6
(224.)
(140.)
(87.6)
(55.4)
(34.8)
DIAMETER
(in.) (mm)
MINIMUM
.0271
(.688)
.0301
(.765)
.0351
(.892)
.0411
(1.04)
.0491
(1.25)
.0583
(1.48)
.0656
(1.67)
.0799
(2.03)
.0812
(2.06)
.0984
(2.50)
NOMINAL
.0285
(.724)
.0315
(.800)
.0365
(.927)
.0425
(1.08)
.0505
(1.28)
.0600
(1.52)
.0675
(1.71)
.0820
(2.08)
.0833
(2.12)
.1010
(2.57)
MAXIMUM
.0299
(.759)
.0329
(.836)
.0379
(.963)
.0439
(1.12)
.0519
(1.32)
.0617
(1.57)
.0694
(1.76)
.0841
(2.14)
.0854
(2.17)
.1036
(2.63)
NOMINAL
WEIGHT
(lbs/1000 ft.)
(kg/km)
.89
(1.32)
1.29
(1.92)
1.88
(2.80)
2.75 (4.09)
4.25
(6.32)
6.44
(9.58)
8.21
(12.2)
12.7
(18.8)
12.0
(17.9)
19.3
(28.7)
FLHTB0312-28-*
FLHTC0312-26-*
FLHTC0312-24-*
FLHTC0312-22-*
FLHTC0312-20-*
FLHTC0312-18-*
FLHTC0312-16-*
FLHTC0312-14-*
FLHTD0312-14-*
FLHTD0312-12-*
28
26
24
22
20
18
16
14
14
12
7 x 36
19 x 38
19 x 36
19 x 34
19 x 32
19 x 30
19 x 29
19 x 27
37 x 30
37 x 28
6.66
(21.9)
4.82
(15.8)
3.05
(10.0)
3.22
(10.6)
2.01
(6.59)
Users should evaluate the suitability of this product for their application. Specifications are subject to change without notice.
Tyco Electronics also reserves the right to make changes in materials or processing, which do not affect compliance with any specification, without notification to Buyer.
1/
COLORS AND COLOR CODE DESIGNATORS SHALL BE IN ACCORDANCE WITH MIL-STD-681. OTHER CODES AND SUFFIXES MAY BE
ADDED TO THE PART NUMBER. AS NECESSARY, TO CAPTURE ANY ADDITIONAL REQUIREMENTS IMPOSED BY THE PURCHASE ORDER.
The TE logo, Tyco Electronics and Raychem are trademarks.
Raychem Wire & Cable
501 Oakside Avenue
Redwood City, CA 94063-3800
Phone: 1-800-227-8816
Fax: 1-650-361-6297
© 2005-2010 Tyco Electronics Corporation. All rights reserved.
Page 1 of 2
DIMENSIONS ARE IN INCHES, AND UNLESS OTHERWISE DESIGNATED ARE NOMINAL
THIS SPECIFICATION SHEET TAKES PRECEDENCE OVER DOCUMENTS REFERENCED HEREIN.
REFERENCED DOCUMENTS SHALL BE OF THE ISSUE IN EFFECT ON DATE OF INVITATION FOR BID.
SPECIFICATION CONTROL DRAWING
Page
2 of 2
Revision
SCD
G
FLHT+0312
TABLE II. PERFORMANCE DETAILS
BEND TESTING
PART NUMBER
1/
FLHTB0312-28-*
FLHTC0312-26-*
FLHTC0312-24-*
FLHTC0312-22-*
FLHTC0312-20-*
FLHTC0312-18-*
FLHTC0312-16-*
FLHTC0312-14-*
FLHTD0312-14-*
FLHTD0312-12-*
MANDREL DIAMETER
(inch)
(mm)
(± 3%)
CROSSLINK VERIFICATION
.375
(9.53)
.375
(9.53)
.375
(9.53)
.500
(12.7)
.500
(12.7)
.500
(12.7)
.750
(19.1)
1.00
1.00
1.50
(25.4)
(25.4)
(38.1)
WEIGHT
(lb)
(kg)
(± 3%)
CROSSLINK VERIFICATION
.125
(.057)
.125
(.057)
.500
(.227)
.750
(.340)
1.00
1.00
1.50
2.00
2.00
3.00
(.454)
(.454)
(.680)
(.907)
(.907)
(1.36)
WIRE RATINGS AND ADDITIONAL REQUIREMENTS
TEMPERATURE RATING: 200°C
VOLTAGE RATING: 600 volts (rms) at sea level
CROSSLINK VERIFICATION: 300 ± 3°C for 1 hour
FLAME RATING: VW-1
INSULATION ELONGATION AND TENSILE STRENGTH:
Elongation, 100% (minimum)
Tensile Strength, 5470 lbf/in
2
(minimum)
INSULATION FLAWS:
Spark Test, 6.0 kV (rms)
Impulse Dielectric Test, 8.0 kV (peak)
INSULATION THICKNESS:
AWG 28 - 16: .0055 inch (minimum), .006 inch (minimum average)
AWG 14: .006 inch (minimum), .0065 inch (minimum average)
AWG 12: .0065 inch (minimum), .007 inch (minimum average)
1/
See footer section on page 1
SHRINKAGE: 200°C for 1 hour, 0.125 in. (maximum) per end
THERMAL STABILITY: 232°C for 168 hours,
Elongation, 60% (minimum)
Tensile Strength, 5000 lbf/in
2
(minimum)
VOLTAGE WITHSTAND (Post Environmental): 2500 volts (rms), 60 Hz, 5 minutes
PART NUMBER:
The “+” in the part number in the upper right hand corner of pages 1 and 2 shall be replaced with
a letter designator to define conductor stranding (see part numbers in table).
B = 7 Strands C = 19 Strands D = 37 Strands
The “*” in the part numbers in tables I and II shall be replaced by a color code designator.
1/
Example: AWG 18, 19 strands, white: FLHTC0312-18-9
AWG 18, 19 strands, white with black stripe: FLHTC0312-18-90