3-1393250-4

CategoryCircuit protection    The circuit breaker   
File Size402KB,2 Pages
ManufacturerTE Connectivity
Websitehttp://www.te.com
Download Datasheet Compare View All
Catalog 1308242
Issued 3-03 (PDF Rev. 11-15)
Potter & Brumfield
W28
series
Push to Reset
Fuseholder-Type
Thermal P
&
B Circuit Breaker
Note: VDE not available on 16A and 20A W28 only.
Features
• Push to reset.
• Approved to many international standards.
• Replaces slow blow glass cartridge fuse.
• Labor-saving snap-in mounting.
• Button extends for visual trip indication.
Resettable Overload Capacity: Six times rated current for 0.25 through
2 amp models. Ten times rated current
for 3 through 20 amp models.
Reset Time: 180 seconds max. for 0.25 through 2 amp models. 5 to 30
seconds for 3 through 20 amp models.
Agency Approvals
W28 series is UL 1077 Recognized as Supplementary Protectors, File E69543,
and CSA Accepted as Supplementary Protectors (Appliance Component
Protectors), File LR15734. W28 breakers are VDE approved for use in office
equipment (AC loads only) and provides 8mm isolation. 16 amp and 20 amp
models do not have VDE approvals at present. CCC mark compliant, certificate
2004010307135992.
Users should thoroughly review the technical data before selecting a product part
number. It is recommended that users also seek out the pertinent approvals files
of the agencies/laboratories and review them to confirm the product meets the
requirements for a given application.
Typical Resistance vs. Current Rating @ +25°C
Current
Rating
in Amps
0.25
0.50
0.75
1.0
2.0
3.0
4.0
5.0
6.0
7.0
Typical
Resistance
in Ohms
14.0
3.55
2.0
0.89
0.17
0.069
0.043
0.030
0.026
0.017
Current
Rating
in Amps
8.0
9.0
10.0
11.0
12.0
13.0
14.0
15.0
16.0
20.0
Typical
Resistance
in Ohms
0.016
0.014
0.011
0.01
0.009
0.009
0.007
0.007
0.007
0.006
Electrical Data @ 25°C
Calibration: Will continuously carry 100% of rating.
3-20 amp models – may trip between 101% and 134%, but
must trip at 135% of rating within one hour at +25°C.
0.25-2 amp models – may trip between 101% and 174%, but
must trip at 175% of rating within one hour at +25°C.
Dielectric Strength: Over 1,500 volts RMS.
Maximum Operating Voltages: 32VDC; 250VAC, 50/60 Hz.
Interrupt Capacity: 1,000 amps at 250VAC, 50/60 Hz. and 32VDC in
accordance with UL standard 1077.
Mechanical/Environmental Data
Termination: .250” (6.35mm) quick connects. Soldering to terminals is
not recommended.
Mounting: Snaps into panel from front. See Recommended
Panel Cutouts.
Approximate Weight: 0.35 oz. (10g).
Time vs. Current Trip Curve @ +25°C
1000
900
Load Current As A Percent
Of Breaker Rating
800
700
600
500
400
300
200
100
0
.1
1
10
Time In Seconds
100
1000
(B)
(A)
(A) All 3-20 Amp Models
Overload
Trip Times
Ambient Compensation Chart
(B) All 0.25-2 Amp Models
Overload
Trip Times
1.
40
1.
30
Cor ect on Fact
r i
or
1.
20
1.
10
1.
00
0.
90
0.
80
0.
70
0.
60
–20 –10 0 10 20 30 40 50 60
A m bi
ent Tem per ur I D egr
at e n
ees Cent gr
i ade (
°C)
100%
135%
200%
400%
600%
800%
1000%
No Trip
Trip in 1 hour
2.2-15.0 Sec.
0.55-1.8 Sec.
0.27-0.7 Sec.
0.17-0.45 Sec.
0.12-0.3 Sec.
100%
175%
200%
400%
600%
No Trip
Trip in 1 hour
4.5-28.0 Sec.
1.0-6.5 Sec.
0.4-4.0 Sec.
175
135
To use this chart: Read up from the ambient tem-
perature to the curve, and across to find a correction
factor. Multiply the breaker rating by the correc-
tion factor to determine the compensated rating.
Calculate the overloads in terms of the compensated
rating to use the published trip curve.
Do not use these devices outside their specified
operating temperature ranges.
USA: 1-800-522-6752
Canada: 1-905-470-4425
Mexico: 01-800-733-8926
C. America: 52-55-1106-0803
South America: 55-11-2103-6000
Hong Kong: 852-2735-1628
Japan: 81-44-844-8013
UK: 44-8706-080208
110
Revised 11-15
www.te.com
Dimensions are in inches over
(millimeters) unless otherwise
specified.
Dimensions are shown for reference
purposes only. Specifications and avail-
ability subject to change.

3-1393250-4 Related Products

Which one is more efficient, VFPv3, VFPv3-D16 or NEONv1?
Which one is more efficient, VFPv3, VFPv3-D16 or NEONv1, for Cortex-A8?...
cl17726 Embedded System
SG power supply selection
High current...
安_然 Test/Measurement
Let's see what's wrong with this electronic thermometer. There is a code inside.
#include#include#include #define uchar unsigned char #define uint unsigned int #define CPU_F ((double)1000000) //MCLK main frequency #define delay_us(x) __delay_cycles((long)(CPU_F*(double)x/1000000.0...
切换中英文 Microcontroller MCU
[Me and Yatli] + From nothing to something, from something to big, I hope to develop better!
[i=s]This post was last edited by eew_bsIqeC on 2020-8-27 08:47[/i][Me and Yatli] + From nothing to something, from something to big, I hope to develop better!The first microcontroller I came into con...
eew_bsIqeC Domestic Chip Exchange
10 tips to help you improve your workplace popularity
1. Withhold opinions: Excessive arguments are not beneficial to oneself and are also uncultured. Generally, one should not rush to express one's attitude or opinions, leaving people unpredictable. Cau...
ESD技术咨询 Talking about work
Please recommend an op amp that can measure a voltage of about 1mV with relatively low distortion~~
Please recommend an op amp that can measure a voltage of about 1mV with relatively low distortion. Can I use OP07?...
陈铁牛 Analog electronics

EEWorld
subscription
account

EEWorld
service
account

Automotive
development
circle

Robot
development
community

Index Files: 1868  1307  193  1825  1274  38  27  4  37  26 
Datasheet   0 1 2 3 4 5 6 7 8 9 A B C D E F G H I J K L M N O P Q R S T U V W X Y Z
Room 1530, 15th Floor, Building B, No. 18 Zhongguancun Street, Haidian District, Beijing Telephone: (010) 82350740 Postal Code: 100190
Copyright © 2005-2026 EEWORLD.com.cn, Inc. All rights reserved 京ICP证060456号 京ICP备10001474号-1 电信业务审批[2006]字第258号函 京公网安备 11010802033920号