Detailed Specifications & Technical Data
ENGLISH MEASUREMENT VERSION
3029A Multi-Conductor - 300V Power-Limited Tray Cable
For more Information
please call
1-800-Belden1
General Description:
18 AWG pairs stranded (19x30) tinned copper conductors, twisted pairs, PVC insulation, individually
shielded (100% coverage), PVC jacket.
Physical Characteristics (Overall)
Conductor
AWG:
# Pairs AWG Stranding Conductor Material
4
18
19x30
TC - Tinned Copper
Total Number of Conductors:
8
Insulation
Insulation Material:
Insulation Material
PVC - Polyvinyl Chloride
Inner Shield
Inner Shield Material:
Inner Shield Trade Name Type Inner Shield Material
Beldfoil®
Coverage (%)
Tape Aluminum Foil-Polyester Tape 100
Inner Shield Drain Wire AWG:
AWG
20
Inner Shield Drain Wire Stranding:
Inner Shield Drain Wire Conductor Material:
7x30
TC - Tinned Copper
Outer Shield
Outer Shield Material:
Outer Shield Material
Unshielded
Outer Jacket
Outer Jacket Material:
Outer Jacket Material
Nom. Wall Thickness (in.)
PVC - Polyvinyl Chloride .053
Outer Jacket Ripcord:
Yes
Overall Cable
Overall Cabling Lay Length & Direction:
Direction
Left-hand Lay
Overall Nominal Diameter:
0.461 in.
Pair
Pair Color Code Chart:
Number Color
1
2
3
Black & White #1
Black & White #2
Black & White #3
Page 1 of 3
10-30-2013
Detailed Specifications & Technical Data
ENGLISH MEASUREMENT VERSION
3029A Multi-Conductor - 300V Power-Limited Tray Cable
4
Black & White #4
Mechanical Characteristics (Overall)
Operating Temperature Range:
UL Temperature Rating:
Bulk Cable Weight:
Max. Recommended Pulling Tension:
Min. Bend Radius/Minor Axis:
-30°C To +105°C
105°C
124 lbs/1000 ft.
296 lbs.
4.500 in.
Applicable Specifications and Agency Compliance (Overall)
Applicable Standards & Environmental Programs
NEC/(UL) Specification:
CEC/C(UL) Specification:
EU Directive 2011/65/EU (ROHS II):
EU CE Mark:
EU Directive 2000/53/EC (ELV):
EU Directive 2002/95/EC (RoHS):
EU RoHS Compliance Date (mm/dd/yyyy):
EU Directive 2002/96/EC (WEEE):
EU Directive 2003/11/EC (BFR):
CA Prop 65 (CJ for Wire & Cable):
MII Order #39 (China RoHS):
PLTC, ITC, CMG
CMG
Yes
Yes
Yes
Yes
04/01/2005
Yes
Yes
Yes
Yes
Flame Test
UL Flame Test:
C(UL) Flame Test:
IEEE Flame Test:
ICEA Flame Test:
UL1685 FT4 Loading
FT4
1202
T-29-520
Suitability
Suitability - Indoor:
Suitability - Outdoor:
Suitability - Burial:
Sunlight Resistance:
Yes
Yes
Yes
Yes
Plenum/Non-Plenum
Plenum (Y/N):
No
Electrical Characteristics (Overall)
Nom. Inductance:
Inductance (µH/ft)
.18
Nom. Capacitance Conductor to Shield:
Capacitance (pF/ft)
102
Nom. Capacitance Conductor to Conductor:
Capacitance (pF/ft)
57
Nom. Conductor DC Resistance:
DCR @ 20°C (Ohm/1000 ft)
Page 2 of 3
10-30-2013
Detailed Specifications & Technical Data
ENGLISH MEASUREMENT VERSION
3029A Multi-Conductor - 300V Power-Limited Tray Cable
5.96
Ind. Pair Nominal Shield DC Resistance @ 20
Deg. C:
Max. Operating Voltage - UL:
Voltage
300 V RMS (PLTC
CMG)
150 V RMS (ITC)
8.300 Ohm/1000 ft
Max. Recommended Current:
Current
5.7 Amps per conductor @ 25°C
Put Ups and Colors:
Item #
Putup
Ship Weight
Color
Notes
Item Desc
Revision Number: 1
© 2013 Belden, Inc
All Rights Reserved.
Revision Date: 05-14-2007
Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications
described herein are subject to error or omission and to change without notice, and the listing of such information and specifications does not
ensure product availability.
Belden provides the information and specifications herein on an "AS IS" basis, with no representations or warranties, whether express,
statutory or implied. In no event will Belden be liable for any damages (including consequential, indirect, incidental, special, punitive, or
exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether in an action under contract,
negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein.
All sales of Belden products are subject to Belden's standard terms and conditions of sale.
Belden believes this product to be in compliance with EU RoHS (Directive 2002/95/EC, 27-Jan-2003). Material manufactured prior to the
compliance date may be in stock at Belden facilities and in our Distributor’s inventory. The information provided in this Product Disclosure, and
the identification of materials listed as reportable or restricted within the Product Disclosure, is correct to the best of Belden’s knowledge,
information, and belief at the date of its publication. The information provided in this Product Disclosure is designed only as a general guide
for the safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. This Product Disclosure is not
to be considered a warranty or quality specification. Regulatory information is for guidance purposes only. Product users are responsible for
determining the applicability of legislation and regulations based on their individual usage of the product.
Belden declares this product to be in compliance with EU LVD (Low Voltage Directive 73/23/EEC), as amended by directive 93/68/EEC.
Page 3 of 3
10-30-2013