• Optional Remote I/O via Flex modules. Communication can be
via the DeviceNet communication platform or the Remote I/O
communication platform.
Available from 23-1200 Amperes.
Specifications
Approvals
C
UL
US
Standards
The ElectroGuard Safety Isolation System is used in place of a
disconnect switch for Lockout and Tagout (LOTO). It uses power
contactors and Remote Lockout Stations to accomplish LOTO.
Isolating the electrical energy usually involves calling an electrician to
turn “Off ” the main disconnecting means. The electrician would
then perform LOTO of the disconnecting means operating handle.
This same procedure is required to perform cleaning, maintenance,
setup, lubrication or adjustment. Machines or processes with
multiple access points may require operator/maintenance
intervention several times a shift (perhaps as often as 60 times per
shift).
To perform these activities, the operator/maintenance person may
be required to place part of his or her body into an area not accessed
during normal operation. This may cause serious or fatal injury if
LOTO procedures are not followed.
The ElectroGuard Safety Isolation System allows the machine
operator to safely and quickly accomplish LOTO with dramatically
reduced downtime.
Provides Energy Isolation
• Power isolation accomplished by means of contactors rather than
disconnect switches.
• Uses redundant, independent and self-monitoring circuits to
detect a system fault.
• Prevents accumulation of faults in order to maintain the integrity
of the safety system.
• Tamper-resistant design.
Convenient Remote Lockout Station
• Allows remote isolation of the electrical power to the machine or
process—machine operator simply turns “Off ” a Remote
Lockout Station.
• A light on the Remote Lockout Station indicates that the three-
phase power source to the machine or process has been isolated.
No Light Means No Entry.
• If a fault occurs in the Safety Isolation System, the “System
Isolated” light on the Remote Lockout Stations will not
illuminate.
• Easy Lockout/Tagout.
Certified by TUV to meet requirements of Category 4
• Certified by TUV to meet Category 4, the most stringent safety
category defined within International Standard EN 954-1/ISO
13849-1.
• Subjected by TUV to rigorous third party testing and verification
of the Failure Mode & Effect Analysis (FMEA).
Estimated Component Life
Remote Lockout Station
Power Contactors
(Isolation & Grounding)
Environmental
Storage Temperature
Operating Temperature
Relative Humidity,
Non condensing
Power Panel Construction
Listed Industrial Control Panel;
TUV Rheinland certified; CE marked
for all applicable directives
IEC/EN 60204-1; IEC/EN 60439-1;
Category 4 to International Standard
EN 954-1/ISO 13849-1; 98/37/EC
Machinery Directive; 89/336/EC EMC
Directive; 73/23/EC Low Voltage
Directive; Fulfils the function of an
energy isolating device in accordance
with the conditions set forth in the
FedOSHA letter of interpretation
pertaining to Section 1910.147(b);
Cal/OSHA 3314.
250,000 operations
23A - 85A: 2,000,000 operations
110A-1200A: 1,000,000 operations
-10°C...+60°C (14°F...140°F)
0°C...+40°C (32°F...104°F) (Ambient)
90% Relative Humidity
Tamper-resistant Control Module
23A-85A systems support up to 4
Remote Lockout Stations without an
Expansion Module
110A-1200A systems support up to 6
Remote Lockout Stations without an
Expansion Module
Control Module with viewing window
for visual check of status indicator lights
Top and bottom 25.4mm (1.0in)
conduit entry (removable plug in
bottom conduit hole)
Sealing provision for tamper-resistance
Operating handle accepts up to 3
padlocks
4 port—supports up to 4 lockout
stations
• allows the systems to
accommodate up to 24 Remote
Lockout Stations
10 port—supports up to 10 lockout
stations
• allows the systems to
accommodate up to 60 Remote
Lockout Stations
Window for viewing status indicator
lights; Sealed for tamper-resistance
Remote Lockout Stations
Safety Mats,
➊
Light Curtains,
➊
E-Stop Stations,
➊
Proximity Switches,
➊
Photo Switches
➊
+10%, -15% of the line voltage
Remote Lockout Station
Construction
Expansion Module
Construction
Safety Isolation Sys. Inputs
Standard Inputs from
Optional Inputs from
Rockwell Automation
Safety Products
System Operational Limits
➊
Use of any of these input devices will not meet Lockout/Tagout (LOTO)
requirements.
12-2
Safety Isolation System
ElectroGuard
Overview
Principle of Operation
Power Circuit
1IC
Incoming
3 Phase
Power
H1
X1
Disconnecting
Means/Branch
Circuit Protection
➊
H2
Trans.
X2
GC
Voltage
Decay
Relays
(VDR)
2IC
To Motor
Controllers
To Loads
After using the normal stopping
method of the machine or process,
the machine operator turns a
Remote Lockout Station handle
from the “On” to “Off ” position.
The station signals the isolation
contactors (1IC and 2IC) to drop
out and isolate the supply voltage
from the loads (see Control
Circuit).
When system residual voltage
decays to pre-determined levels,
the grounding contactor (GC) is
energized, connecting the load to
ground (see Power Circuit). The
grounding contactor (GC) is
electrically and mechanically
interlocked with the isolation
contactors (1IC and 2IC).
The “System Isolated” Light will
now illuminate on the Remote
Lockout Station to indicate the
system is isolated. The machine
operator then Locks-Out and
Tags-Out the station in the “Off ”
position.
Control Power
Grd
Control Circuit
Remote Lockout Station
Off
On
GC
1IC
GC
2IC
VDR
1IC
2IC
GC
Mechanically
Interlocked
1IC, 2IC,
&
GC are
mechanically
and electrically
interlocked
GC
1IC
2IC
System Isolated (*)
(*) = “On” when the Remote
Lockout Station switch is “Off”
➊
Available factory installed within the ElectroGuard as an option.
Optional Features
• Four (4) or ten (10) port Expansion Modules to permit additional Remote
Lockout Stations to be used (see page 12-16 for details).
• Pneumatic Isolation Module to isolate pneumatic energy (see page 12-15 for
details).
• Status communication to a remote PLC (see page 12-17 for details).
• Fusible disconnect switch (Bulletin 2032) or thermal-magnetic circuit breaker
(Bulletin 2033) to provide branch circuit protection.
Optional Pneumatic Isolation Module
12-3
Safety Isolation System
ElectroGuard
Non Combination Systems
+
Power Panel
3-Phase Max. Hp Rating (60Hz)
Ampere
Rating
(AC-3)
23
43
85
110
180
210
300
420
630
860
1200
Type 1 General
Purpose
Enclosure
2031-A0023A⊗
2031-A0043A⊗
2031-A0085A⊗
2031-A0110A⊗
2031-A0180A⊗
2031-A0210A⊗
2031-A0300A⊗
2031-A0420A⊗
2031*-A0630A⊗
2031*-A0860A⊗
2031*-A1200A⊗
One or More Remote Lockout Stations
(conduit hub not included)
Product Selection: For North America (see page 12-19 for Ordering Instructions)
Catalogue Number
➊
Type 12
Dust tight
Enclosure
2031-A0023J⊗
2031-A0043J⊗
2031-A0085J⊗
2031-A0110J⊗
2031-A0180J⊗
2031-A0210J⊗
2031-A0300J⊗
2031-A0420J⊗
2031*-A0630J⊗
2031*-A0860J⊗
2031*-A1200J⊗
200V
5
10
25
40
50
60
100
150
200
250
450
230V
7.5
15
30
40
60
75
125
175
250
300
450
460V
15
30
60
75
150
-
250
350
500
600
900
575V
15
30
60
100
150
200
300
400
600
700
900
Type 12 Motor
Control Centre
Type Enclosure
(with bussing)
2031-!0023J⊗
2031-!0043J⊗
2031-!0085J⊗
2031-!0110J⊗
2031-!0180J⊗
2031-!0210J⊗
2031-!0300J⊗
2031-!0420J⊗
2031-!0630J⊗
2031-!0860J⊗
2031-!1200J⊗
Type 4
Watertight
Painted Steel
Enclosure
2031-A0023F⊗
2031-A0043F⊗
2031-A0085F⊗
2031-A0110F⊗
2031-A0180F⊗
2031-A0210F⊗
2031-A0300F⊗
2031-A0420F⊗
2031*-A0630F⊗
2031*-A0860F⊗
2031*-A1200F⊗
Type 4X
Watertight
Stainless Steel
Enclosure
2031-A0023C⊗
2031-A0043C⊗
2031-A0085C⊗
2031-A0110C⊗
2031-A0180C⊗
2031-A0210C⊗
2031-A0300C⊗
2031-A0420C⊗
2031*-A0630C⊗
2031*-A0860C⊗
2031*-A1200C⊗
To order the Time Delay feature, add the following Catalogue String to the end of the Catalogue Number shown in the
table:
Factory set 30 second time delay feature:
-1TD
Example:
Catalogue Number
2031-A0180A⊗
becomes Catalogue Number
2031-A0180A⊗-1TD
to include the time delay feature.
* Input Power Feed Catalogue Number Code
The Catalogue Number as listed is incomplete. Select an Input Power Feed Code from the table below.
Example:
Catalogue Number
2031*-A0630J⊗
becomes Catalogue Number
2031T-A0630J⊗
for a “Top Feed” input power requirement.
Input Power Feed
Top Feed
Bottom Feed
Catalogue Number Code
T
B
Example:
Catalogue Number
2031-
!
0085J⊗
becomes Catalogue Number
2031-M0085J⊗
for “600A Line Side Incoming Bus and Outgoing Power Cables”
bussing designation.
Type of Bussing
➋
600A Line Side Incoming Bus and Outgoing Power Cables
1200A Line Side Incoming Bus and Outgoing Power Cables
Line Side Incoming Power Cables and 600A Load Side Outgoing Bus
Line Side Incoming Power Cables and 1200A Load Side Outgoing Bus
⊗
Input Line Voltage Code
Catalogue Number Code
M
S
F
B
!
Bussing Designation
The Catalogue Number as listed is incomplete. Select a Bussing Designation Code from the table below.
The Catalogue Number as listed is incomplete. Select an Input Line Voltage Code from the table below.
Example:
Catalogue Number
2031-A0085J⊗
becomes Catalogue Number
2031-A0085JB
for a 480V 60Hz Input Line Voltage application.
Input Line Voltage
Voltage Code for Catalogue Number
208V 60Hz
H
240V 60Hz
A
480V 60Hz
B
600V 60Hz
C
➊
Optional Time Delay Feature. The Safety Isolation System may be ordered with a factory set time delay feature (30 seconds) in order to allow time for the machine
operator to shut-down drives or other equipment that requires a controlled stop, after the operating handle on a Remote Lockout Station has been moved to the “Off”
position. Consult your local Rockwell Automation sales office for other time settings.
➋
Bus Type: Copper with tin plating. Consult factory for other types of bussing.
12-4
Safety Isolation System
ElectroGuard
Non Combination Systems
Product Selection: Remote Lockout Station
➊
“System Isolated”
Light Colour
White
Type 1 General
Purpose Enclosure
2030-RLSAW
Catalogue Number
Type 12 Dust tight
Type 4 Watertight Painted
Enclosure
Steel Enclosure
2030-RLSJW
2030-RLSFW
Type 4X Watertight Stainless
Steel Enclosure
2030-RLSCW
Product Selection: For Outside of North America (see page 12-19 for Ordering Instructions)
3-Phase Max. kW Rating (50Hz)
Ampere
Rating
(AC-3)
23
43
85
110
180
210
300
420
630
860
1200
230V
7.5
13
25
32
55
63
90
132
200
250
391
400V
11
22
45
55
90
110
160
220
355
500
710
500V
11
22
45
63
110
150
200
300
450
560
888
600V
11
22
45
100
160
200
300
425
500
600
1043
IP 30 Enclosure
2031-C0023P⊗
2031-C0043P⊗
2031-C0085P⊗
2031-C0110P⊗
2031-C0180P⊗
2031-C0210P⊗
2031-C0300P⊗
2031-C0420P⊗
2031*-C0630P⊗
2031*-C0860P⊗
2031*-C1200P⊗
Catalogue Number
➋
IP 54 Motor Control
Centre Type Enclosure
IP 54 Enclosure
(w/bussing)
2031-C0023H⊗
2031-C0043H⊗
2031-C0085H⊗
2031-C0110H⊗
2031-C0180H⊗
2031-C0210H⊗
2031-C0300H⊗
2031-C0420H⊗
2031*-C0630H⊗
2031*-C0860H⊗
2031*-C1200H⊗
2031-!0023H⊗
2031-!0043H⊗
2031-!0085H⊗
2031-!0110H⊗
2031-!0180H⊗
2031-!0210H⊗
2031-!0300H⊗
2031-!0420H⊗
2031-!0630H⊗
2031-!0860H⊗
2031-!1200H⊗
IP 65 Enclosure
2031-C0023W⊗
2031-C0043W⊗
2031-C0085W⊗
2031-C0110W⊗
2031-C0180W⊗
2031-C0210W⊗
2031-C0300W⊗
2031-C0420W⊗
2031*-C0630W⊗
2031*-C0860W⊗
2031*-C1200W⊗
To order the Time Delay feature, add the following Cat. String to the end of the Cat. No. shown in the table:
Factory set 30 second time delay feature:
-1TD
Example:
Catalogue Number
2031-C0180H⊗becomes
Catalogue Number
2031-C0180H⊗-1TD
to include the time delay feature.
* Input Power Feed Catalogue Number Code
The Catalogue Number as listed is incomplete. Select an Input Power Feed Code from the table below.
Example:
Catalogue Number
2031*-C0630H⊗
becomes Catalogue Number
2031T-C0630H⊗
for a “Top Feed” input power requirement.
Input Power Feed
Catalogue Number Code
Top Feed
T
Bottom Feed
B
Example:
Catalogue Number
2031-
!
0085H⊗
becomes Catalogue Number
2031-E0085H⊗
for “600A Line Side Incoming Bus and Outgoing Power Cables”
bussing designation.
Type of Bussing
➌
600A Line Side Incoming Bus and Outgoing Power Cables
1200A Line Side Incoming Bus and Outgoing Power Cables
Line Side Incoming Power Cables and 600A Load Side Outgoing Bus
Line Side Incoming Power Cables and 1200A Load Side Outgoing Bus
⊗
Input Line Voltage Code
Catalogue Number Code
E
D
H
R
!
Bussing Designation
The Catalogue Number as listed is incomplete. Select a Bussing Designation Code from the table.
The Catalogue Number as listed is incomplete. Select an Input Line Voltage Code from the table below.
Example:
Catalogue Number
2031-C0085P⊗
becomes Catalogue Number
2031-C0085PN
for a 380V 50Hz Input Line Voltage application.
Input Line Voltage
220V 50HZ
380-400V 50Hz
400-415V 50Hz
440V 50Hz 500V 50Hz
Voltage Code for Catalogue Number
A
N
G
B
M
550V 50Hz
C
Product Selection: Remote Lockout Station
➊
“System Isolated” Light Colour
Green
IP 30 Enclosure
2030-RLSPG
Catalogue Number
IP 54 Enclosure
2030-RLSHG
IP 65 Enclosure
2030-RLSWG
➊
Safety Isolation Systems rated up through 85A can support a maximum of four (4) Remote Lockout Stations (RLS).
Systems rated from 110A - 1200A can support a maximum of six (6) RLS. If additional RLS are required, order the optional Expansion Module(s) (see page 12-16).
➋
Optional Time Delay Feature. The Safety Isolation System may be ordered with a factory set time delay feature (30 seconds) in order to allow time for the machine
operator to shut-down drives or other equipment that requires a controlled stop, after the operating handle on a Remote Lockout Station has been moved to the “Off”
position. Consult your local Rockwell Automation sales office for other time settings.
➌
Bus Type: Copper with tin plating. Consult factory for other types of bussing.
[i=s]This post was last edited by paulhyde on 2014-9-15 09:07[/i]Principles of MCU Hardware System Design The hardware circuit design of a MCU application system includes two parts: one is system expa...
On the WinCE platform, you can set the system sound by calling the waveOutSetVolume API. However, you cannot set the volume of Bluetooth in this way. The Bluetooth module in the project can control th...
Yesterday, I happened to see my dad watching TV. I glanced at it and was immediately attracted by the title: My husband is 61 and I am 19. I can’t imagine what kind of combination this relationship is...
1. Relatively speaking, the program framework of SensorTile is really too large. It covers the interfaces of the entire series of Nucleo boards and various BSD and middleware. However, for developers ...
In the previous stage, I was not familiar with the writing of Linux device drivers and could not find any information. So I temporarily put the experiment of SPI devices on hold. A few days ago, I was...
Microchip's PIC18F46J50 is a low-power, high-performance 8-bit USB microcontroller (MCU) using nanoWatt XLP technology. The current in deep sleep mode can be as low as 13nA, the operating voltage i...[Details]
Due to the significant increase in electronic devices in automotive and industrial applications, the automotive and industrial markets continue to play an important role in China's electronics in...[Details]
As cellular phones become more advanced, the power consumption of the system during operation and the power consumption during standby are also increasing. Therefore, the power management design of...[Details]
I. Introduction
In the field of power conversion, isolated converters (forward, flyback, and double-ended) with low output DC voltage all use MOSFET as the rectifier device. Since these devi...[Details]
Two simple circuits are implemented to drive two LEDs from a battery powered microprocessor.
This design is based on a circuit that uses three resistors and a microprocessor I/O pin as an input h...[Details]
In the previous series, we have listed some basic knowledge of C language in Tables 1 to 3. We hope that beginners can strengthen their memory of the above tables and gradually learn to use them wh...[Details]
Microcalorimetry
is used to determine energy relationships. Microcalorimetry techniques are often required when performing calorimetric experiments with small sample sizes or slow heating rat...[Details]
In today's body control module (BCM) designs, savvy engineers are moving away from electromechanical relays whenever possible. Their next step is to eliminate fuses. But is eliminating fuses a nece...[Details]
The rectified DC voltage is then converted back to AC using power electronics such as insulated gate bipolar transistors.
The output voltage is switched on and off at a high frequency, control...[Details]
Introduction
Nowadays, people pay more and more attention to the security alarm system, and people have higher and higher requirements for the functions and performance of the alarm. This paper prop...[Details]
The automotive power electronics market has grown rapidly as comfort and active safety features become more common. As traditional mechanical functions shift to electronic applications, the demand ...[Details]
Currently, high-frequency and high-efficiency DCDC converters are increasingly used in automotive electronic systems.
High switching frequency can use smaller power inductors and output filter...[Details]
Power supply is often the most easily overlooked link in the circuit design process. In fact, as an excellent design, power supply design should be very important, which greatly affects the perfor...[Details]
With the popularity of digital appliances, rechargeable batteries can be seen everywhere in people's daily lives and have become one of the indispensable daily necessities.
This article gives ...[Details]
1 Introduction
With the development of computer technology and information technology in the world, the global information age has arrived. All countries are formulating their own development p...[Details]