Embedded Power for
Business-Critical Continuity
NLP110 Medical
Single and
triple output
Rev.02.19.07
NLP110 Medical
1 of 4
Total Power:
80 - 110W
Input Voltage: 90 - 264VAC
# of Outputs: Single, triple
Special Features
• Provides low voltage outputs
• Compliance to EN61000-3-2
(Power Factor = 0.98)
• Smallest industry
standard package 6.5 x 3.0 x
1.26 inches
• 90 Vac to 264 Vac universal
input range
• UL, cUL, and VDE
safety approvals and
CE-Marked to MDD
• Overvoltage and
short circuit protection
• VDE0871-A, EN55022-A,
EN55011-A conducted noise
• VDE0871-A, EN55022-A,
EN55011-A radiated noise
• Meets all applicable and
relevant immunity standards
EN61000-4-2,4,5 and 6
• Available RoHS compliant
• 2 year warranty
Safety
VDE0750/IEC60601-1
and EN60601-1
UL2601-1 and C22.2
No. 601.1-M90.
The NLP110 is a series of 110 W ac-dc open frame power supplies
in a 3 x 6.5 x 1.26 inch package. The NLP110 is power factor
corrected to meet EN61000-3-2 and is available in single and
multiple output models. The multiple output models have a
capability that is unique to the power supply market - they can
deliver equal amounts of current on multiple low voltage outputs
to support designs that will span the industry transition from 5 V
logic to 3.3 V logic. The NLP110 is practically the same size as a 65
Watt 3 x 5 inch product, e.g. NLP65 - the one difference is that the
footprint is a mere 1.5 inches longer. The NLP110 is primarily
designed for networking applications in 1U shelves or boxes that
have a heavy logic content such as access concentrators,
midrange routers, LAN switches and shared media hubs. The
availability of single output models with high peak load capability
also means that the NLP110 can provide a power factor corrected
solution for applications currently using the NFS110.
Embedded Power for
Business-Critical Continuity
Specifications
All specifications are typical at nominal input, full load at 25
°
C unless otherwise stated
Rev.02.19.07
NLP110 Medical
2 of 4
OUTPUT SPECIFICATIONS
Total regulation
(Line and load)
Rise time
Transient response
Main output
Auxiliary outputs
At turn-on
Main output
75% to 100%
step at 0.1 A/μs
±2.0%
±5.0%
1.0 s, max.
5.0% or 250 mV
max. dev., 1 ms max.
recovery to 1%
±0.02%/
°
C
Main outputs
Cyclic operation
Single and multiple
125%, ±10%
Continuous
See table
EMC CHARACTERISTICS (continued)
Surge
Fast transients
Radiated immunity
Conducted immunity
GENERAL SPECIFICATIONS
Hold-up time
Efficiency
Isolation voltage
Approvals and
standards
Weight
Universal input
90-264 Vac
47-63 Hz
120 Vac
230 Vac
230 Vac, 50 Hz
120 Vac @ 80 W
120 Vac @ 110 W
230 Vac @ 80 W
230 Vac @ 110 W
UL/IEC127
18 A max.
35 A max.
<100 μA
0.9 A rms
1.3 A rms
0.48 A rms
0.7 A rms
F3.15A H, 250 Vac
Relative humidity
Altitude
Level A
Level A
Compliant
Level 3
Level 3
Vibration (See Note 8)
Shock
MTBF (@ 25
°
C)
MIL-HDBK-217F
120 Vac, 60 Hz
120 Vac, 80 W (-9905J)
Input/output
Input/chassis
16.7 ms @ 110 W
75% min.
4000 Vac
1500 Vac
EN61000-4-5
EN61000-4-4
EN61000-4-3
EN61000-4-6
Level 3
Level 3
Level 3
Level 3
Temperature coefficient
Overvoltage protection
Short circuit protection
Minimum output current
INPUT SPECIFICATIONS
Input voltage range
(See Note 6)
Input frequency range
Input surge current
(cold start)
Safety ground
leakage current
Input current
EN60601-1, IEC60601-1,VDE0750,
UL2601-1, C22.2 No. 601.1-M90
283 g (10 oz)
220,000 hours min.
ENVIRONMENTAL SPECIFICATIONS
(9)
Thermal performance
Operating ambient,
0
°
C to +50
°
C
(See derating curve)
Non-operating
-40
°
C to +85
°
C
50
°
C to 70
°
C, ambient,
Derate to
convection cooled
50% load
0
°
C to 50
°
C, ambient,
80 W
convection cooled
0
°
C to 50
°
C ambient,
110 W
150 LFM forced air
Peak (0
°
C to +50
°
C, 60 s)
(See Note 3)
Non-condensing
Operating
Non-operating
5-500 Hz
per MIL-STD-810E
5% to 95% RH
10,000 feet max.
30,000 feet max.
2.4 G rms peak
516.4 Part IV
Input fuse
EMC CHARACTERISTICS
(12)
Conducted emissions
Radiated emissions
Harmonic current
emission correction
ESD air
ESD contact
EN55022, FCC part 15
EN55022, FCC part 15
EN61000-3-2
EN61000-4-2
EN61000-4-2
Embedded Power for
Business-Critical Continuity
Specifications Contd.
OUTPUT
VOLTAGE
+5 V
+12 V
+48 V
+24 V
+5 V (A)
+3.3 V (B)
+12 V
+3.3 V (A)
+2.5 V (B)
+12 V
+12 V (A)
+3.3 V (B)
-12 V
+12 V (A)
+5 V (B)
-12 V
Notes
1
Rev.02.19.07
NLP110 Medical
3 of 4
OUTPUT CURRENT
MIN
(6)
0.5 A
0.3 A
0A
0.2 A
0.5 A
0.2 A
0A
0.5 A
0.1 A
0A
0.2 A
0.5 A
0A
0.2 A
0.2 A
0A
MAX
(1)
15 A
6.4 A
1.6 A
3.2 A
13 A
13 A
0.65 A
13 A
13 A
0.65 A
6.5 A
13 A
0.65 A
6.5 A
13 A
0.65 A
150 LFM
(2)
22 A
9.2 A
2.3 A
4.6 A
16 A
16 A
1.0 A
16 A
16 A
1A
8.5 A
16 A
1A
8.5 A
16 A
1A
300 LFM
(3)
22 A
9.2 A
2.3 A
4.6 A
18 A
20 A
1A
20 A
20 A
1A
8.5 A
20 A
1A
8.5 A
18 A
1A
PEAK
(4)
22 A
11.5 A
2.5 A
6.0 A
18 A
20 A
1A
22 A
22 A
1A
10 A
22 A
1A
10 A
22 A
1A
RIPPLE
(5)
50 mV
120 mV
240 mV
240 mV
50 mV
50 mV
120 mV
50 mV
50 mV
120 mV
1200 mV
50 mV
120 mV
120 mV
50 mV
120 mV
TOTAL
REGULATION
±2.0%
±2.0%
±2.0%
±2.0%
±2.0%
±2.0%
±5.0%
±2.0%
±2.0%
±5.0%
±2.0%
±2.0%
±5.0%
±2.0%
±2.0%
±5.0%
MODEL
NUMBERS
(7,14,15)
NLP110-9605J
NLP110-9612J
NLP110-9617J
NLP110-9624J
NLP110-9693J
NLP110-9694J
NLP110-9695J
NLP110-9608J
2
3
4
5
6
Free air convection.
Multiple output units: maximum continuous output power not to exceed 80 W.
For -9693J; I
3.3 V
= 13 A max.; I
5.0 V
= 13 A max.; I
3.3 V
+ I
5.0 V
² 16 A.
For -9694J; I
3.3 V
= 13 A max.; I
2.5 V
= 13 A max.; I
3.3 V
+ I
2.5 V
² 16 A
For -9695J; I
3.3 V
= 13 A max.; I
12 V
= 6.5 A max.; I
3.3 V
+ I
12 V
² 16 A.
For -9608J; I
5.0 V
= 13 A max.; I
12 V
= 6.5 A max.; I
5.0 V
+ I
12 V
² 16 A.
Single output units: maximum continuous output power not to exceed; 75 W
on -9605J; 76.8 W on -9612J,-9624J, and -9617J.
150 LFM forced air cooling from L4 side.
Multiple output units: maximum continuous output power not to exceed 105
W.
For -9693J; I
3.3 V
= 16 A max.; I
5.0 V
= 16 A max.; I
3.3 V
+ I
5.0 V
² 20 A.
For -9694J; I
3.3 V
= 16 A max.; I
2.5 V
= 16 A max.; I
3.3 V
+ I
2.5 V
² 20 A
For -9695J; I
3.3 V
= 16 A max.; I
12 V
= 8.5 A max.; I
3.3 V
+ I
12 V
² 20 A.
For -9608J; I
5.0 V
= 16 A max.; I
12 V
= 8.5 A max.; I
5.0 V
+ I
12 V
² 20 A.
Single output units: maximum continuous output power not to exceed 110 W
for all models.
300 LFM forced air cooling from L4 side.
Multiple output units: maximum continuous output power not to exceed 110
W.
For -9693J; I
3.3 V
= 20 A max.; I
5.0 V
= 18 A max.; I
3.3 V
+ I
5.0 V
² 22 A.
For -9694J; I
3.3 V
= 20 A max.; I
2.5 V
= 20 A max.; I
3.3 V
+ I
2.5 V
² 22 A
For -9695J; I
3.3 V
= 20 A max.; I
12 V
= 8.5 A max.; I
3.3 V
+ I
12 V
² 22 A.
For -9608J; I
5.0 V
= 20 A max.; I
12 V
= 8.5 A max.; I
5.0 V
+ I
12 V
² 22 A.
Single output units: maximum continuous output power not to exceed 110 W
for all models.
Peak output current lasting less than 30 seconds with duty cycle less than 5%.
During peak loading, output voltage may exceed total regulation limits.
Figure is peak-to-peak for convection power rating. Output noise
measurements are made across a 20 MHz bandwidth using a 6’ twisted pair,
terminated with a 10 μF electrolytic capacitor and a 0.1 μF ceramic capacitor.
Minimum load required for correct start-up and operation on single outputs
and on main output of multiple versions. Failure to observe minimum load
on main output will not allow the supply to start-up correctly. Some
electronic test loads have a large delay time before they start drawing current
7
8
9
10
11
12
13
14
15
even though the voltage from the supply is present. During this time delay,
there is no load on the output and as a result, the supply cannot start-up
properly and maintain its correct output voltage. In these instances, a
dummy resistive load across the output may be necessary to load the output
of the supply until the test load can function correctly and draw the intended
minimum load. Minimum load required on auxiliary outputs to maintain
regulation.
For models NLP110-9608J and NLP110-9695J, the 12 V output is floating. For
-12 V output, pin 11 on J2 has to be connected to Return making pin 12 the -
12 V output
Three orthogonal axes, random vibration 10 minutes for each axes, 2.4 G rms
5 Hz to 500 Hz.
For optimum reliability, no part of the heatsink should exceed 110 °C, and no
semiconductor case temperature should exceed 120 °C.
CAUTION: Allow a minimum of 1 second after disconnecting line power when
making thermal measurements.
This product is only for inclusion by professional installers within other
equipment and must not be operated as a stand alone product.
The EMI specifications reference measurements made with the power supply
mounted on a grounded metal sheet extending 1 inch beyond each edge,
using an unshielded cable. No external filtering required during conducted
emissions testing but some applications may require additional filtering to
achieve system compliance. A line choke, (ac input cords looped twice
through an EMI suppression toroid) was used during radiated emissions
testing. Considerable radiated testing in 1U six-sided boxes has shown that
units can meet level B in typical systems. Application support is available
from the factory to assist with EMI compliance.
All models require a minimum mounting stand-off of 6.35 mm (0.25 inches)
in the end use product.
The ‘J’ suffix indicates that these parts are Pb-free (RoHS 6/6) compliant. TSE
RoHS 5/6 (non Pb-free) compliant versions may be available on special request,
please contact your local sales representative for details.
NOTICE: Some models do not support all options. Please contact your local
Artesyn representative or use the on-line model number search tool at
http://www.artesyn.com/powergroup/products.htm to find a suitable
alternative.
Embedded Power for
Business-Critical Continuity
Mechanical Notes
A
All dimensions are in inches (mm).
6.50
(165.10)
6.050
(153.670)
0.23
(5.842)
Rev.02.19.07
NLP110 Medical
4 of 4
2
Americas
5810 Van Allen Way
Carlsbad, CA 92008
USA
Telephone: +1 760 930 4600
Facsimile: +1 760 930 0698
J4
4
12
3
J2
!
2.550
(64.770)
3.00
(76.20)
1
Recommended direction
for forced air relative to
power supply orientation
shown below.
1
2
3
4
Optimum.
Very good.
Good.
Not recommended.
Europe (UK)
Waterfront Business Park
Merry Hill, Dudley
West Midlands, DY5 1LX
United Kingdom
Telephone: +44 (0) 1384 842 211
Facsimile: +44 (0) 1384 843 355
F1
1
3
T1 (REF.)
J1
J3
J5
ALL DIMENSIONS IN INCHES (mm)
MAXIMUM COMPONENT
HEIGHT IS 1.26 (32.00)
1
1
2
2
1
0.23
(5.842)
Asia (HK)
16th - 17th Floors, Lu Plaza
2 Wing Yip Street, Kwun Tong
Kowloon, Hong Kong
Telephone: +852 2176 3333
Facsimile: +852 2176 3888
INPUT
PIN CONNECTIONS
J1
Pin 1
AC Neutral
Pin 2
Pin 3
Pin 1
Pin 2
Pin 1
Pin 1
Pin 2
No Connection
AC Line
J3
V (A) Sense +
V (A) Sense -
J4
Safety Earth
J5
V (B) Sense +
V (B) Sense -
OUTPUT PIN CONNECTIONS
SINGLE
TRIPLE
No Connection
V (B)
No Connection
No Connection
Return
Return
Return
Return
V (A)
V (A)
V (A)
No Connection
No Connection
V (B)
V (B)
Return
Return
Return
Return
V (A)
V (A)
V (A)
V (C)
V (C) Return
(7)
I nput and output connectors
AC (J1) connector type
Molex 26-60-4030 or
equivalent.
Mating connectors
AC (J1) mating connector type
Molex 09-50-3031 or equivalent
with Molex 08-50-0105 or
equivalent crimp terminals.
DC (J2) mating connector type
Molex Spox type 26-03-3121
and contact 08-52-0113.
DERATING CURVE
Output Power (Watts)
110W
80W
150 LFM FORCED
AIR COOLING
For global contact, visit:
NATURAL
CONVECTION
COOLING
www.powerconversion.com
55W
40W
technicalsupport@powerconversion.com
While every precaution has been taken to ensure
accuracy and completeness in this literature, Emerson
Network Power assumes no responsibility, and disclaims
all liability for damages resulting from use of this
information or for any errors or omissions.
0°C
10°C 20°C 30°C 40°C 50°C 60°C 70°C
Emerson Network Power.
The global leader in enabling
business-critical continuity.
AC Power
Connectivity
DC Power
Embedded Power
Inbound Power
Integrated Cabinet Solutions
Outside Plant
Precision Cooling
Site Monitoring and Services
EmersonNetworkPower. com
Emerson Network Power and the Emerson
Network Power logo are trademarks and
service marks of Emerson Electric Co.
©2007 Emerson Electric Co.
J2
Pin 1
Pin 2
Pin 3
Pin 4
Pin 5
Pin 6
Pin 7
Pin 8
Pin 9
Pin 10
Pin 11
Pin 12
DC (J2) connector type
12 position Molex Spox type
26-48
1125 or equivalent.
Sense (J3) connector type
Molex 22-23-2021 or
equivalent.
Earth (J4) connector type
Male 0.250 quick disconnect.
Sense (J3) mating
connector type
Molex 22-01-3027 and contact
08-50-0113.
Earth (J4) mating
connector type
Molex 90028.
Sense (J5) mating
connector type
Leoco 2420S020000 and
contact 2453TPB00V1.
Sense (J5) connector type