EEWORLDEEWORLDEEWORLD

Part Number

Search

BK/MDA-12B

Description
TIME DELAY BLOW ELECTRIC FUSE, 12A, 250VAC, 750A (IR), INLINE/HOLDER
CategoryCircuit protection    Circuit protection   
File Size137KB,2 Pages
ManufacturerEaton
Download Datasheet Parametric View All

BK/MDA-12B Overview

TIME DELAY BLOW ELECTRIC FUSE, 12A, 250VAC, 750A (IR), INLINE/HOLDER

BK/MDA-12B Parametric

Parameter NameAttribute value
MakerEaton
Reach Compliance Codeunknown
Fusing characteristicsTIME DELAY
body height31.75 mm
Body length or diameter6.35 mm
Circuit protection typeELECTRIC FUSE
Joule integral nominal113 J
Manufacturer's serial numberMDA
Installation featuresINLINE/HOLDER
method of packingBOX
physical size6.35mm x 31.75mm
Rated breaking capacity750 A
Rated current12 A
Rated voltage (AC)250 V
GuidelineCSA; UL
surface mountNO
Terminal surfaceNICKEL
Terminal shapeEND CAP
1/4" x 1-1/4" Fuses
MDA Series, Time Delay, Ceramic Tube
Description
• Time Delay, ceramic tube
• Optional axial leads available
• 1/4 x 1-1/4 (6.3mm x 32mm) physical size
• Ceramic tube, nickel-plated brass endcap construction
• UL Listed product meets standard 248-14
ELECTRICAL CHARACTERISTICS
Amp Rating
Opening Time
Rated Current
None
100%
1/4 - 30A
135%
60 Minutes Max.
200%
120 Seconds Max.
RoHS
2002/95/EC
Agency Information
• UL Listed Card: MDA 2/10 - 20A (Guide JDYX,
File E19180)
• UL Recognized Card: MDA 25 - 30A (Guide JDYX2,
File E19180)
• CSA Certification Card: MDA 2/10 - 15
(Class No. 1422-01)
• CSA Component Acceptance: MDA 20-30A
(Class No. 1422-30)
Environmental Data
• Shock: 1/100A and 8/10A – MIL-STD-202,
Method 213, Test Condition I;
1A thru 30A – MIL-STD-202, Method 207,
(HI Shock)
• Vibration: 1/100A and 8/10A – MIL-STD-202,
Method 201; 1/4A thru 30A – MIL-STD-202,
Method 204, Test Condition C (Except 5g, 500HZ)
Ordering
• Specify packaging, product, and option code
Dimensions
(
mm
in
)
Drawing Not to Scale
SPECIFICATIONS
Product
Code
MDA-1/4
MDA-1/2
MDA-3/4
MDA-1
MDA-1-1/2
MDA-2
MDA-2-1/2
MDA-3
MDA-4
MDA-5
MDA-6
MDA-7
MDA-8
MDA-10
MDA-12
MDA-15
MDA-20
MDA-25A
MDA-30A
*
**
Traditional Ferrule Fuses - Ferrule Type
Voltage
Rating
AC
DC
250V
-
250V
-
250V
-
-
250V
250V
-
250V
-
250V
-
250V
-
250V
-
250V
-
250V
-
250V
-
-
250V
250V
-
250V
-
-
250V
250V
125V
250V
125V
250V
125V
AC Interrupting
Rating*
250V
125V
35A
10000A
35A
10000A
35A
10000A
35A
10000A
100A
10000A
100A
10000A
200A
10000A
200A
10000A
200A
10000A
200A
10000A
200A
10000A
200A
10000A
200A
10000A
200A
10000A
750A
10000A
10000A
750A
1500A
10000A
1500A
10000A
1500A
10000A
DC Interrupting
Rating
125V
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
10000A
10000A
10000A
Typical DC Cold
Resistance**
(ohms)
9.325
1.925
0.8555
0.560
0.2585
0.1645
0.06685
0.0507
0.0346
0.02355
0.01850
0.01475
0.01230
0.00858
0.00725
0.00543
0.00358
0.00309
0.00243
Typical
Melting I
2
t†
AC
0.68
2.3
7.8
11.1
25.0
64.0
28.9
40.9
134.0
345.9
534.3
580.3
944.0
1491.3
113.8
206.2
439.5
667.9
997.0
Typical
Voltage
Drop‡
4.00
1.42
1.31
1.03
0.691
0.623
0.213
0.182
0.162
0.145
0.141
0.137
0.134
N/A
0.114
0.107
0.095
0.105
0.110
Interrupting Ratings (Measured at 70% - 80% power factor on AC. The interrupting ratings for 25Amp, 30Amp were measured at 90% - 100% power factor on AC)
DC Cold Resistance (Measured at
≤10%
of rated current)
Typical Melting I
2
t (A
2
Sec) (I
2
t was measured at listed interrupting rating and rated voltage)
Typical Voltage Drop (Voltage drop was measured at 25°C ambient temperature at rated current)
OC-92
40 High-Speed Photography Photos That Will Shock You
Does pure entertainment make life better?...
clark Creative Market
How to filter out the peak voltage generated when the switch is turned on?
Everyone, how can I filter out the peak voltage generated when the switch is turned on? My situation is this: 380VAC three-phase electricity comes out through a 3P (trip switch), and is filtered by in...
lockwe Embedded System
J-link debugging enters HardFault_Handler, please help
When doing a project for stm32f030, I first wrote an initialization configuration function for usart1. The main function calls the configuration function, and then single-steps into the function debug...
无帝老三 stm32/stm8
TCPMP 0.72RC1 for CE6.0 Errors
I used VS2005 to compile TCPMP, installed the SDK of CE6.0, compiled successfully, but there is always an error when running: a dialog box pops up, crash.txt. When debugging, I found that the error se...
momn12 Embedded System
1114 points linger!!!
Today I finally got 1114 points. It was hard-earned. I am very lucky to have the NXP LPC1114!...
zhaojun_xf NXP MCU
2016 Anhui Electric Competition
Dear seniors, please give me some advice on which direction the power supply should go this year....
吴圣中 LED Zone

EEWorld
subscription
account

EEWorld
service
account

Automotive
development
circle

Robot
development
community

Index Files: 2650  769  432  1431  848  54  16  9  29  18 
Datasheet   0 1 2 3 4 5 6 7 8 9 A B C D E F G H I J K L M N O P Q R S T U V W X Y Z
Room 1530, 15th Floor, Building B, No. 18 Zhongguancun Street, Haidian District, Beijing Telephone: (010) 82350740 Postal Code: 100190
Copyright © 2005-2026 EEWORLD.com.cn, Inc. All rights reserved 京ICP证060456号 京ICP备10001474号-1 电信业务审批[2006]字第258号函 京公网安备 11010802033920号