VRLA Rechargeable Battery
BPL7-12
FEATURES
Measures
Technology
Values
Innovation
(BPL7-12FR)
APPLICATION
UPS
Laboratory Equipment
Toy-Cars
Power Packs
Fishing Lights
Maintenance free(no water topping-up required).
No free acid(Non-spillable battery).
Low self-discharge rate, lower than 3% capacity
loss per month.
Can be used in any orientation(excluding used inverted).
SPECIFICATIONS
Nominal Voltage
Nominal Capacity
Approx. Weight
Terminals
Internal Resistance
Max. Discharge Current
Max. Charge Current
Operating Temperature Range
12 V
7.0Ah @ 20 hour rate F.V.(1.75V/cell)
2600g(5.73lbs.)
T2 (Faston Tab 250) T1 is optional
25m
(Fully Charged )
UL
CE
IEC61056
JIS C 8702
GB/T 19639
105 A (5 sec.)
2.1 A
Charge 0
o
C~40
o
C(32
o
F~104
o
F)
Discharge -20
o
C~50
o
C(-4
o
F~122
o
F)
Storage. -20
o
C~40
o
C(-4
o
F~104
o
F)
ABS(UL94-HB, UL94-V0 is optional)
ISO14001
ISO 9001
Container Material
DIMENSION(mm/inch)
Length
151±1.5 (5.94±0.06)
Width
65±1.5
(2.56±0.06)
93 1.5(3.66 0.06)
98 2(3.86 0.08)
151
OUTER DIMENSIONS
TERMINAL TYPE
Terminal T1
3.2(0.13)
4.75(0.19)
Terminal T2
3.4(0.13)
6.35(0.25)
1.5(5.94
0.06)
65
1.5(2.56
0.06)
0.8(0.03)
Total Height
98±2.0 (3.86±0.08)
Discharge
Time
Constant power discharge characteristics at 25 C/77 F
F.V.
(V/cell)
o
o
Unit: W
3 Hr
20.40
20.80
21.00
21.20
21.30
5 Min
228.0
264.0
280.0
293.0
302.0
10 Min
171.4
185.7
192.4
197.0
200.9
15 Min
138.8
145.3
149.7
153.2
156.2
30 Min
83.50
86.70
88.60
89.90
90.80
o
1 Hr
48.40
49.80
50.70
51.40
51.90
o
5 Hr
14.10
14.30
14.40
14.50
14.50
10 Hr
7.86
7.98
8.02
8.04
8.04
1.80V
1.75V
1.70V
1.65V
1.60V
Constant current discharge characteristics at 25 C/77 F
F.V.
(V/cell)
Discharge
Time
Unit: A
3 Hr
1.700
1.733
1.750
1.767
1.775
5 Min
20.54
24.22
25.69
26.88
27.71
10 Min
15.09
16.35
16.94
17.34
17.68
15 Min
12.07
12.63
13.02
13.32
13.58
30 Min
7.076
7.347
7.508
7.619
7.695
1 Hr
4.067
4.185
4.261
4.319
4.361
5 Hr
1.175
1.192
1.200
1.208
1.208
10 Hr
0.655
0.665
0.668
0.670
0.670
1.80V
1.75V
1.70V
1.65V
1.60V
All data shall be changed without prior notice, BB reserves the right to explain and update the information contained hereinto.
A/0
REV. Jul. 2009
Powered by
B.B. Battery Co., Ltd.
0.8(0.03)
Container Height
93±1.5 (3.66±0.06)
6.35(0.25)
7.85(0.31)
20 Hr
4.11
4.20
4.22
4.23
4.23
20 Hr
0.343
0.350
0.352
0.353
0.353