Detailed Specifications & Technical Data
METRIC MEASUREMENT VERSION
83554 Multi-Conductor - Audio, Control and Instrumentation Cable
For more Information
please call
1-800-Belden1
Description:
22 AWG stranded (7x30) TC conductors, conductors cabled, plenum, FEP insulation, overall Beldfoil®
(100% coverage) + TC braid shield (85% coverage), FEP jacket.
Physical Characteristics (Overall)
Conductor
AWG:
# Conductors AWG Stranding Conductor Material
4
22
7x30
TC - Tinned Copper
Insulation
Insulation Material:
Insulation Material
Wall Thickness (mm)
FEP - Fluorinated Ethylene Propylene 0.1524
Outer Shield
Outer Shield Material:
Layer # Outer Shield Trade Name Type Outer Shield Material
1
2
Beldfoil®
Braid TC - Tinned Copper
Coverage (%)
85
Tape Aluminum Foil-Polyester Tape 100
Outer Jacket
Outer Jacket Material:
Outer Jacket Material
Nom. Wall Thickness (mm)
FEP - Fluorinated Ethylene Propylene 0.3556
Overall Cabling
Overall Cabling Lay Length & Direction:
Length (mm)
50.7998
Overall Cabling Color Code Chart:
Number Color
1
2
3
4
Black
White
Red
Green
Overall Nominal Diameter:
4.039 mm
Mechanical Characteristics (Overall)
Operating Temperature Range:
Bulk Cable Weight:
Max. Recommended Pulling Tension:
Min. Bend Radius (Install)/Minor Axis:
-70°C To +200°C
38.247 Kg/Km
177.928 N
43.180 mm
Applicable Specifications and Agency Compliance (Overall)
Applicable Standards & Environmental Programs
NEC/(UL) Specification:
CMP
Page 1 of 3
05-10-2011
Detailed Specifications & Technical Data
METRIC MEASUREMENT VERSION
83554 Multi-Conductor - Audio, Control and Instrumentation Cable
CEC/C(UL) Specification:
EU CE Mark:
EU Directive 2000/53/EC (ELV):
EU Directive 2002/95/EC (RoHS):
EU RoHS Compliance Date (mm/dd/yyyy):
EU Directive 2002/96/EC (WEEE):
EU Directive 2003/11/EC (BFR):
CA Prop 65 (CJ for Wire & Cable):
MII Order #39 (China RoHS):
CMP
Yes
Yes
Yes
04/01/2005
Yes
Yes
Yes
Yes
Flame Test
UL Flame Test:
C(UL) Flame Test:
NFPA 262
FT6
Plenum/Non-Plenum
Plenum (Y/N):
Yes
Electrical Characteristics (Overall)
Nom. Capacitance Conductor to Conductor:
Capacitance (pF/m)
75.463
Nom. Capacitance Cond. to Other Conductor & Shield:
Capacitance (pF/m)
131.24
Nom. Conductor DC Resistance:
DCR @ 20°C (Ohm/km)
50.8555
Nominal Outer Shield DC Resistance:
DCR @ 20°C (Ohm/km)
16.0769
Max. Operating Voltage - UL:
Voltage
300 V RMS
Max. Recommended Current:
Current
2.2 Amps per conductor @ 25°C
Notes (Overall)
Notes:
Plenum Cables, except for Flamarrest® jacket, are suitable for Outdoor and Direct Burial application.
Related Documents:
No related documents are available for this product
Put Ups and Colors:
Item #
83554 002100
83554 0021000
83554 002500
Notes:
C = CRATE REEL PUT-UP.
Putup
30 MT
305 MT
152 MT
Ship Weight
1.814 KG
11.340 KG
5.670 KG
Color
RED
RED
RED
C
C
Notes
Item Desc
4#22 FEP SH FEP
4#22 FEP SH FEP
4#22 FEP SH FEP
Page 2 of 3
05-10-2011
Detailed Specifications & Technical Data
METRIC MEASUREMENT VERSION
83554 Multi-Conductor - Audio, Control and Instrumentation Cable
Revision Number: 1
© 2011 Belden, Inc
All Rights Reserved.
Revision Date: 09-18-2008
Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications
described herein are subject to error or omission and to change without notice, and the listing of such information and specifications does not
ensure product availability.
Belden provides the information and specifications herein on an "AS IS" basis, with no representations or warranties, whether express,
statutory or implied. In no event will Belden be liable for any damages (including consequential, indirect, incidental, special, punitive, or
exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether in an action under contract,
negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein.
All sales of Belden products are subject to Belden's standard terms and conditions of sale.
Belden believes this product to be in compliance with EU RoHS (Directive 2002/95/EC, 27-Jan-2003). Material manufactured prior to the
compliance date may be in stock at Belden facilities and in our Distributor’s inventory. The information provided in this Product Disclosure, and
the identification of materials listed as reportable or restricted within the Product Disclosure, is correct to the best of Belden’s knowledge,
information, and belief at the date of its publication. The information provided in this Product Disclosure is designed only as a general guide
for the safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. This Product Disclosure is not
to be considered a warranty or quality specification. Regulatory information is for guidance purposes only. Product users are responsible for
determining the applicability of legislation and regulations based on their individual usage of the product.
Belden declares this product to be in compliance with EU LVD (Low Voltage Directive 73/23/EEC), as amended by directive 93/68/EEC.
Page 3 of 3
05-10-2011