Detailed Specifications & Technical Data
METRIC MEASUREMENT VERSION
9464 Multi-Conductor - Single-Pair Cable
For more Information
please call
1-800-Belden1
Description:
20 AWG stranded (7x28) TC conductors, polyethylene insulation, twisted pair, overall Beldfoil® shield
(100% coverage), 20 AWG stranded TC drain wire, PVC jacket.
Physical Characteristics (Overall)
Conductor
AWG:
# Pairs AWG Stranding Conductor Material
1
20
7x28
TC - Tinned Copper
Insulation
Insulation Material:
Insulation Material Wall Thickness (mm)
PE - Polyethylene
0.4064
Outer Shield
Outer Shield Material:
Outer Shield Trade Name Type Outer Shield Material
Beldfoil®
Coverage (%)
Tape Aluminum Foil-Polyester Tape 100
Outer Shield Drain Wire AWG:
AWG Stranding Drain Wire Conductor Material
20
7x28
TC - Tinned Copper
Outer Jacket
Outer Jacket Material:
Outer Jacket Material
Nom. Wall Thickness (mm)
PVC - Polyvinyl Chloride 0.889
Overall Cabling
Overall Nominal Diameter:
5.436 mm
Pair
Pair Color Code Chart:
Number Color
1
Black & Clear
Pair Lay Length & Direction:
Lay Length (mm) Twists/ft. (twist/m)
38.09985
26.248
Mechanical Characteristics (Overall)
Operating Temperature Range:
UL Temperature Rating:
Bulk Cable Weight:
Max. Recommended Pulling Tension:
Min. Bend Radius (Install)/Minor Axis:
-20°C To +60°C
60°C (UL AWM Style 2092)
41.818 Kg/Km
204.617 N
50.800 mm
Page 1 of 3
05-10-2011
Detailed Specifications & Technical Data
METRIC MEASUREMENT VERSION
9464 Multi-Conductor - Single-Pair Cable
Applicable Specifications and Agency Compliance (Overall)
Applicable Standards & Environmental Programs
NEC/(UL) Specification:
CEC/C(UL) Specification:
AWM Specification:
EU CE Mark:
EU Directive 2000/53/EC (ELV):
EU Directive 2002/95/EC (RoHS):
EU RoHS Compliance Date (mm/dd/yyyy):
EU Directive 2002/96/EC (WEEE):
EU Directive 2003/11/EC (BFR):
CA Prop 65 (CJ for Wire & Cable):
MII Order #39 (China RoHS):
CM
CM
UL Style 2092 (300 V 60°C)
Yes
Yes
Yes
01/01/2004
Yes
Yes
Yes
Yes
Flame Test
UL Flame Test:
UL1685 UL Loading
Plenum/Non-Plenum
Plenum (Y/N):
No
Electrical Characteristics (Overall)
Nom. Characteristic Impedance:
Impedance (Ohm)
56
Nom. Inductance:
Inductance (µH/m)
0.59058
Nom. Capacitance Conductor to Conductor:
Capacitance (pF/m)
88.587
Nom. Capacitance Cond. to Other Conductor & Shield:
Capacitance (pF/m)
160.769
Nom. Conductor DC Resistance:
DCR @ 20°C (Ohm/km)
31.1695
Max. Operating Voltage - UL:
Voltage
300 V RMS
Max. Recommended Current:
Current
3.9 Amps per conductor @ 20°C
Notes (Overall)
Notes:
The jacket and shield are bonded so both can be removed on automatic stripping equipment. Drain wire is on the inside of foil
shield.
Related Documents:
No related documents are available for this product
Put Ups and Colors:
Page 2 of 3
05-10-2011
Detailed Specifications & Technical Data
METRIC MEASUREMENT VERSION
9464 Multi-Conductor - Single-Pair Cable
Item #
9464 060U1000
9464 060U500
Putup
305 MT
152 MT
Ship Weight
14.515 KG
7.711 KG
Color
CHROME
CHROME
Notes
Item Desc
2 #20 PE FS PVC
2 #20 PE FS PVC
Revision Number: 1
© 2011 Belden, Inc
All Rights Reserved.
Revision Date: 09-18-2008
Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications
described herein are subject to error or omission and to change without notice, and the listing of such information and specifications does not
ensure product availability.
Belden provides the information and specifications herein on an "AS IS" basis, with no representations or warranties, whether express,
statutory or implied. In no event will Belden be liable for any damages (including consequential, indirect, incidental, special, punitive, or
exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether in an action under contract,
negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein.
All sales of Belden products are subject to Belden's standard terms and conditions of sale.
Belden believes this product to be in compliance with EU RoHS (Directive 2002/95/EC, 27-Jan-2003). Material manufactured prior to the
compliance date may be in stock at Belden facilities and in our Distributor’s inventory. The information provided in this Product Disclosure, and
the identification of materials listed as reportable or restricted within the Product Disclosure, is correct to the best of Belden’s knowledge,
information, and belief at the date of its publication. The information provided in this Product Disclosure is designed only as a general guide
for the safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. This Product Disclosure is not
to be considered a warranty or quality specification. Regulatory information is for guidance purposes only. Product users are responsible for
determining the applicability of legislation and regulations based on their individual usage of the product.
Belden declares this product to be in compliance with EU LVD (Low Voltage Directive 73/23/EEC), as amended by directive 93/68/EEC.
Page 3 of 3
05-10-2011