B-Series – General Specifications
™
Designed specifically for world market applications, the B-series
utilizes the hydraulic magnetic principle which provides precise
operation and performance even when exposed to extremely
hot and/or cold application environments. Typical applications
include power supplies, medical equipment, office equipment,
control panels and marine equipment.
1-6 poles, 0.02 - 50 amps, up to 277 VAC or 80 VDC, with
choice of time delays, terminals and actuator colors.
Agency Certifications
UL Recognized
UL Standard 1077
UL Listed
UL Standard 489A
Component Recognition Program as
Protectors, Supplementary (Guide
CCN/QVNU2, File E75596)
Switches, Industrial Control (Guide
CCN/NRNT2, File E148683)
Protectors, Supplementary for Marine
Electrical & Fuel Systems (Guide
PEQZ2, File E75596) Ignition Protection
Communications Equipment (Guide
CCN/DITT, File E189195)
Component Supplementary Protector
under Class 3215 30,
FIle 047848 0 000
CSA Standard C22.2 No. 235
EN60934, VDE 0642 under File No.
10537
CSA Certified
UL Standard 508
UL Standard 1500
VDE Certified
Electrical
Table A:
Lists UL Recognized & CSA Certified configurations and performance capabilities as a Component Supplementary
Protector.
B-SERIES TABLE A: COMPONENT SUPPLEMENTARY PROTECTOR
VOLTAGE
CURRENT RATING
FULL
CIRCUIT
CONFIGURATION
INTERRUPTING CAPACITY(AMPS)
UL / CSA
WITH
BACKUP FUSE
WITHOUT
BACKUP FUSE
GENERAL
PURPOSE
AMPS
MAX
RATING
FREQUENCY
PHASE
LOAD
AMPS
65
80
80
125/250
125/250
SERIES
DC
DC
DC
50/60
50/60
50/60
50/60
50/60
50/60
50/60
DC
50/60
50/60
50/60
DC
50/60
50/60
50/60
DC
50/60
50/60
50/60
DC
DC
50/60
50/60
50/60
50/60
---
---
---
1
3
1
3
1
1
3
3
1
---
1&3
1&3
1
---
1&3
1&3
1
---
1&3
1&3
1
---
---
1
1
3
1
31 - 50
0.02 - 30
---
0.02 - 30
31 - 50
0.02 - 30
---
0.02 - 20
21 - 30
0.02 - 30
0.02 - 30
0.02 - 20
21 - 30
0.02 - 30
0.02 - 30
0.02 - 20
21 - 30
0.02 - 30
0.02 - 30
0.02 - 20
21 - 30
0.02 - 30
0.02 - 50
0.02 - 30
31 - 50
---
0.02 - 50
0.02 - 30
---
---
31 - 50
---
---
---
31 - 50
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
31 - 50
---
31 - 50
---
---
---
---
---
2000
2000
5000
2000
1
3000
3000
1500
3000
2000
---
---
---
---
---
3000
---
---
---
3000
---
---
---
3000
---
---
---
250
250
250
250
277
80
250
1
1
1
5000
2
5000
1
---
5000
1
2000
1
5000
2
277
80
250
SHUNT
DUAL COIL
250
5000
1
---
5000
1
2000
1
5000
2
5000
1
---
5000
1
2000
1
5000
2
250
277
80
250
RELAY
250
277
65
80
250
5000
1
SWITCH ONLY
250
250
277
Notes for Table A:
1
Requires branch circuit backup with a UL LISTED Type K5
or RK5 fuse (15A minimum) at no more than 4 times the rat-
ing of the protector.
2
Same as note 1, except that backup fuse is limited to 80 A
maximum.
3
2 pole protector required (with one pole per power line) for:
250/125 VAC, 125/250 VAC and 208Y/120 VAC Power
Systems. 1 pole protector required for : 125 VAC, 1Ø Power
System.
www.carlingtech.com
49
Carling
Technologies
B-Series – General Specifications
™
Electrical
Table B:
Lists UL Recognized, CSA, VDE & TUV Certified configurations & performance capabilities as a Component Supplementary
Protector.
B-SERIES TABLE B: COMPONENT SUPPLEMENTARY PROTECTOR
VOLTAGE
CURRENT RATING
FULL
CIRCUIT
CONFIGURATION
INTERRUPTING CAPACITY (AMPS)
UL / CSA
WITH
WITHOUT
(Inc) WITH
BACKUP FUSE
VDE
(Icn) WITHOUT
BACKUP FUSE
(Inc) WITH
BACKUP FUSE
TUV
(Icn) WITHOUT
BACKUP FUSE
GENERAL
PURPOSE
AMPS
1
MAX
RATING
FREQUENCY
PHASE
LOAD
AMPS
BACKUP FUSE BACKUP FUSE
80
80
80
250
SERIES
DC
DC
DC
50/60
50/60
50/60
50/60
50/60
DC
50/60
50/60
50/60
DC
50/60
50/60
50/60
---
---
---
1&3
1&3
1
1
1
---
1&3
1&3
1
---
1&3
1&3
1
0.10 - 30
31 - 50
31 - 32
0.10 - 20
21 - 30
0.10 - 30
31 - 50
31 - 32
0.10 - 30
0.10 - 20
21 - 30
31 - 50
0.10 - 30
0.10 - 20
21 - 30
31 - 50
---
31 - 50
31 - 32
---
---
---
---
---
---
---
---
31 - 50
---
---
---
31 - 50
---
---
---
5000
2
3000
1500
1500
3000
---
2000
2000
---
3000
---
---
2000
3000
---
---
2000
3000
3000
3000
3000
3000
3000
---
3000
3000
3000
3000
---
3000
3000
3000
---
1500
1500
1500
1500
1500
1500
---
1500
1500
1500
1500
---
1500
1500
1500
---
3000
3000
3000
3000
3000
5000
5000
5000
3000
3000
3000
5000
3000
3000
3000
5000
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
250
250
250
250
80
250
DUAL COIL
2000
2
5000
3
---
---
2000
2
---
5000
2
250
250
80
250
SHUNT
2000
2
5000
3
---
---
5000
2
2000
2
250
250
5000
3
---
Notes for Table B:
1
General Purpose Ratings for UL/CSA Only.
2
Requires branch circuit backup with a UL LISTED Type K5 or RK5 fuse (15A minimum) at no more than 4 times the rating of the protector.
3
Same as note 1, except that backup fuse is limited to 80 A maximum.
Table C:
Lists UL Recognized, CSA Certified configurations and performance capabilities as Protectors, Supplementary for Marine
Electrical and Fuel Systems (CCN/Guide PEQZ2, File E75596). Ignition Protected per UL 1500. UL Classified Small Craft Electrical
Devices, Marine in accordance with ISO 8846 (CCN/Guide UZMK, File MQ1515) as Marine Supplementary Protectors.
B-SERIES TABLE C: UL1500 (MARINE IGNITION PROTECTED)
INTERRUPTING
VOLTAGE
CURRENT
RATING
CIRCUIT
CONFIGURATION
CAPACITY
(AMPS)
WITHOUT
BACKUP FUSE
MAX
RATING
FREQUENCY
PHASE
FULL LOAD
AMPS
SERIES
14
1
65
125 / 250
250
DC
DC
50/60
50/60
---
---
1
2
1
0.02 - 50
0.02 - 50
0.02 - 50
0.02 - 30
5000
3000
1500
1000
Notes for Table C:
1
Available with special catalog number only (consult factory).
2
2 pole protector required (with one pole per power line) for: 250/125 VAC, 125/250 VAC and 208Y/120 VAC Power Systems. 1 pole protector required for : 125 VAC, 1Ø Power System.
Table D:
Lists UL Listed configurations and performance capabilities as Circuit Breakers for use in Communications Equipment
(CCN/Guide DITT, File E189195), under UL489A
B-SERIES TABLE D: UL489A LISTED (COMMUNICATIONS EQUIPMENT)
INTERRUPTING
VOLTAGE
CURRENT
RATING
CIRCUIT
CONFIGURATION
CAPACITY
(AMPS)
WITHOUT
BACKUP FUSE
MAX
RATING
FREQUENCY
PHASE
UL GENERAL
PURPOSE AMPS
SERIES
80
DC
---
.10 - 50
5000
50
www.carlingtech.com
Carling
Technologies
B-Series – General Specifications
™
Electrical
Maximum Voltage
Current Ratings
277VAC 50/60 Hz, 80VDC
Standard current coils: 0.100,
0.250, 0.500, 0.750, 1.00, 2.50,
5.00, 7.50, 10.0, 15.0, 20.0, 25.0,
30.0, 35.0, 40.0 and 50.0 amps.
Other ratings available, see ordering
scheme.
DC - 6V, 12V; AC - 120V, other rat-
ings available, see ordering scheme.
SPDT; 10.1 AMPS - 250VAC,1.0A 65
VDC or 0.5A 80 VDC, 0.1 Amps -
125VAC (with gold contacts).
VDE-1.0 Amp - 125VAC.
Minimum of 100 Megohms at 500
VDC.
UL, CSA - 1500 V 50/60 Hz for one
minute between all electrically isolat-
ed terminals. B-Series circuit break-
ers comply with the 8mm spacing
and 3750V 50/60 Hz dielectric
requirements from hazardous voltage
to operator accessible surfaces,
between adjacent poles and from
main circuits to auxiliary circuits per
Publications EN 60950 and VDE
0805.
Values from Line to Load Terminal -
based on Series Trip Circuit Breaker.
Mechanical
Endurance
10,000 ON-OFF operations @ 6 per
minute; with rated Current and
Voltage.
All B-Series Circuit Breakers will trip
on overload, even when Handle is
forcibly held in the ON position.
The operating Handle moves positive-
ly to the OFF position when an over-
load causes the breaker to trip.
Trip Free
Trip Indication
Standard Voltage Coils
Auxiliary Switch Rating
Physical
Number of Poles
1 - 6 poles at 30 Amps or less. 1
and 2 poles at 31 Amps thru 50
Amps.
Series, (with or without auxiliary
switch), Shunt and Relay with current
or voltage trip coils, Dual Coil, Switch
Only (with or without auxiliary switch).
Approximately 65 grams/pole.
(Approximately 2.32 ounces/pole.
Housing- Black; Actuator - See
Ordering Scheme.
Insulation Resistance
Dielectric Strength
Internal Circuit Config.
Weight
Standard Colors
Environmental
Designed and tested in accordance with requirements of specifi-
cation MIL-PRF- 55629 and MIL-STD-202 as follows:
Shock
Withstands 100 Gs, 6ms, sawtooth
while carrying rated current per
Method 213, Test Condition "I".
Instantaneous and ultra-short curves
tested @ 90% of rated current.
Vibration
Withstands 0.060" excursion from
10-55 Hz, and 10 Gs 55-500 Hz, at
rated current per Method 204C, Test
Condition A. Instantaneous and
ultrashort curves tested at 90% of
rated current.
Moisture Resistance
Method 106D, i.e., ten 24-hour
cycles @ + 25°C to +65°C, 80-98%
RH.
Salt Spray
Method 101, Condition A (90-95%
RH @ 5% NaCl Solution, 96 hrs).
Thermal Shock
Method 107D, Condition A (Five
cycles @ -55°C to +25°C to +85°C to
+25°C).
Resistance, Impedance
RESISTANCE, IMPEDANCE VALUES
from Line to Load Terminals
(Values Based on Series Trip Circuit Breaker)
1000
CURRENT
(AMPS)
100
TOLERANCE
(%)
±
15%
±
25%
±
35%
0.10 - 5.0
5.1 - 20.0
20.1 - 50.0
10
O
H
M
S
1
0.1
0.01
0.001
0.01
0.1
1
10
100
AMPERE RATING
Pulse Tolerance Curves
Ir
60 Hz 1/2 Cycle
Inrush Pulse Tolerance
Time Delay Curves
42, 44 & 46
(50 Amps Max.)
Ir
y
Inrush Pulse Tolerance
Time Delay Curves
42, 44 & 46
(50 Amps Max.)
Time Delay Curves
22, 24, 26, 32, 34, 36
(70 Amps Max.)
t
5.0
10.0
20.0
Multiple of
Rated Current
Multiple of
Rated Current
25x
22x
12x
Time Delay Curves
22, 24, 26, 32, 34, 36
(70 Amps Max.)
10x
t
4.165
8.33
16.67
Time in
Milliseconds
Time in
Milliseconds
www.carlingtech.com
51
Carling
Technologies
B-Series Handle UL Recognized – Ordering Scheme
™
B A 3 B 0 10 450 1 B 1 C
1
Series
2
Actuator
3
Poles
4
Circuit
5
Aux/Alarm
Switch
6
Frequency
& Delay
7
Current Rating
8
Terminal
9
Actuator
Color
10
Mounting/
Barriers
11
Agency
Approval
1 SERIES
B
2 ACTUATOR
1
A
Handle, one per pole
B
Handle, one per multipole unit
S
Mid-Trip Handle, one per pole
T
Mid-Trip Handle, one per pole & Alarm Switch
3 POLES
1
One
2
Two
4 CIRCUIT
Switch Only (No Coil)
A
2
B
Series Trip (Current)
C
Series Trip (Voltage)
Shunt Trip (Current)
D
3
Shunt Trip (Voltage)
E
3
Relay Trip (Current)
F
3
5 AUXILIARY/ALARM SWITCH
5
0
w/o Aux Switch
1
S.P.D.T., 0.093 Q.C. Term.
2
S.P.D.T., 0.110 Q.C. Term.
3
S.P.D.T., 0.139 Solder Lug
4
S.P.D.T., 0.110 Q.C. Term.
(Gold Contacts)
6 FREQUENCY & DELAY
03
2
DC 50/60Hz, Switch Only
10
6
DC Instantaneous
11
DC Ultra Short
12
DC Short
14
DC Medium
16
DC Long
20
6
50/60Hz Instantaneous
21
50/60Hz Ultra Short
22
50/60Hz Short
24
50/60Hz Medium
26
50/60Hz Long
3
4
Three
Four
G
3
H
3,4
J
3,4
K
3,4
5
6
Five
Six
Relay Trip (Voltage)
Dual Coil with Shunt Trip
Voltage Coil
Dual Coil with Shunt Trip
Voltage Coil (side terminal)
Dual Coil with Relay Trip
Voltage Coil
S.P.S.T., 0.093 Q.C.
Term.(Gold Contacts)
S.P.S.T., 0.139 Solder Lug
S.P.S.T., 0.110 Q.C.
Term.(Gold Contacts)
S.P.S.T., 0.187 Q.C. Term.
S.P.D.T., 0.187 Q.C. Term.
5
6
7
8
9
7 CURRENT RATING (AMPERES)
425
2.500
230
0.300
020
0.020
527
2.750
235
0.350
025
0.025
430
3.000
240
0.400
030
0.030
435
3.500
245
0.450
035
0.035
440
4.000
250
0.500
040
0.040
445
4.500
255
0.550
045
0.045
450
5.000
260
0.600
050
0.050
455
5.500
265
0.650
055
0.055
460
6.000
270
0.700
060
0.060
465
6.500
275
0.750
065
0.065
470
7.000
280
0.800
070
0.070
475
7.500
285
0.850
075
0.075
480
8.000
290
0.900
080
0.080
485
8.500
295
0.950
085
0.085
490
9.000
410
1.000
090
0.090
495
9.500
512
1.250
0.095
095
610
10.000
415
1.500
210
0.100
710
10.500
517
1.750
215
0.150
611
11.000
420
2.000
220
0.200
711
11.500
522
2.250
225
0.250
OR
VOLTAGE COIL (NOMINAL RATED VOLTAGE)
6
J12
12 AC
A32
32 DC
A06
6 DC
J18
18 AC
A48
48 DC
A12
12 DC
J24
24 AC
A65
65 DC
A18
18 DC
J48
48 AC
J06
6 AC
A24
24 DC
8 TERMINAL
9
1
10
Push-On 0.250 Tab (Q.C.)
2
Screw 8-32 w/upturned lugs
Screw 8-32 (Bus Type)
3
11
4
Screw 10-32 w/upturned lugs
Screw 10-32 (Bus Type)
5
11
6
Screw 8-32 w/upturned lugs
and 30° bend
7
Screw 8-32 (Bus Type) and
30° bend
8
Screw 10-32 w/upturned lugs
and 30° bend
9
Screw 10-32 (Bus Type) and
30° bend
B
Screw M5 w/upturned lugs
C
Screw M4 w/upturned lugs
9 ACTUATOR COLOR & LEGEND
I-O
ON-OFF Dual
White
A
B
1
Black
C
D
2
Red
F
G
3
Green
H
J
4
Blue
K
L
5
Yellow
M
N
6
Gray
P
Q
7
Orange
R
S
8
E
11
F
G
H
L
12
M
11
P
13
Q
R
S
15
T
612
712
613
614
615
616
617
618
620
622
624
625
630
635
8
640
8
645
8
650
8
12.000
12.500
13.000
14.000
15.000
16.000
17.000
18.000
20.000
22.000
24.000
25.000
30.000
35.000
40.000
45.000
50.000
J65
65 AC
K20
120 AC
L40
240 AC
30
31
32
34
36
42
7
44
7
46
7
52
7
54
7
56
7
DC, 50/60Hz Instantaneous
DC, 50/60Hz Ultra Short
DC, 50/60Hz Short
DC, 50/60Hz Medium
DC, 50/60Hz Long
50/60Hz Short, Hi-Inrush
50/60Hz Medium, Hi-Inrush
50/60Hz Long, Hi-Inrush
DC, Short,Hi-Inrush
DC,Medium, Hi-Inrush
DC, Long, Hi-Inrush
Screw M4 (Bus Type)
Screw M5 w/upturned lugs
and 30° bend
Screw M5 (Bus Type)
and 30° bend
Screw M5 (Bus Type)
0.250 Q.C./ Solder Lug
M6 Threaded Studs
Printed Circuit Board
Terminals
Push-In Stud
Screw M4 w/upturned lugs
and 30° bend
Push-On 0.110 Tab (Q.C.)
Screw M4 (Bus Type)
and 30° bend
Notes:
1
Actuator Code:
A: Handle tie pin spacer(s) and retainers provided unassembled with multi-pole units.
B: Handle location as viewed from front of breaker:
2 pole - left pole
3 pole - center pole
4 pole - two handles at center poles 5 pole - three handles at center poles
6 pole - four handles at center poles
S: Handle moves to mid-position only upon electrical trip of the breaker. Available with cir-
cuit codes B, C, D, E, F, G, H and K.
T: Handle moves to mid-position and alarm switch activates only upon electrical trip of the
breaker. Available with circuit codes B & C.
2
Switch Only circuits, rated up to 50 amps and 6 poles, and only available with VDE
Certification when tied to a protected pole (Circuit Code B, C, D or H.), For .02 to 30
amps, select Current Code 630. For 35 - 50 amps, select Current Code 650.
3
Available with Terminal Codes 1, 2 and 3. Current Rating limited to 30 amps maximum.
4
Consult factory for available Dual Coil options, as special catalog number is required.
With Shunt construction, Dual Coils will trip instantaneously on line voltage. Dual coils
require 30VA minimum power to trip and are rated for intermittent duty only.
5
Auxiliary Switch breakers with Series Trip and Switch Only circuits. On multi-pole break-
ers, one aux. switch is supplied, mounted in the extreme right pole.
6
Separate pole type voltage coils not rated for continuous duty. Available only with delay
codes 10 and 20.
7
Available with Circuit Codes B & D only. VDE Certified to 30 amps. UL Recognized and
CSA Certified to 50 amps.
8
VDE Certification available with single pole breakers with DC Delay only. UL Recognition
and CSA Certification available in one and two pole breakers.
9
Screw Terminals are recommended on ratings greater than 20 amps. Ratings over 30
amps are only available with Terminal Codes 5, 9, G, H, M and Q.
10
VDE Certification up to 25 amps and UL Recognition and CSA Certification up to 30 amps,
but not recommended over 20 amps.
11
Terminal Codes 3, 5 E and H (Bus Type) with VDE, are supplied with Lock Washers, and
Terminal Code M (M6 Threaded Stud) with VDE is supplied with Lock and Flat Washers.
These breakers are only VDE Certified when the washers are used.
12
VDE Cert. available up to 12 amps. UL Rec. & CSA Cert. available up to 30 amps.
13
Single pole breakers with Terminal Code P (Printed Circuit Board) are available up to 30
amps with VDE Certification and 50 amps with UL Recognition and CSA Certification, with
Circuit Codes A, B and C. Two pole breakers with Terminal Code P (Printed Circuit Board)
are available up to 40 amps with UL Recognition and CSA Certification with Circuit Codes
A, B and C.
14
Available with Actuator Codes A, S and T.
15
Available with voltage coils only.
Legend Color
Black
White
White
White
White
Black
Black
Black
10 MOUNTING/BARRIERS
MOUNTING STYLE
BARRIERS
Threaded Insert, 2 per pole
1
6-32 x 0.195 inches
no
A
6-32 X 0.195 inches
yes
2
ISO M3 x 5mm
no
B
ISO M3 x 5mm
yes
Rectangular Adapter Plate with mounting centers of 2.062”
[52.37mm] and Threaded insert, 2 per pole
3
14
6-32 x 0.225 inches
no
C
14
6-32 X 0.225 inches
yes
4
14
ISO M3 x 6.5mm
no
D
14
ISO M3 x 6.5mm
yes
Front panel Snap-In, 0.75” [19.05mm] wide bezel
5
without Handleguard
no
6
without Handleguard
yes
Front panel Snap-In, 0.96” [24.48mm] wide bezel
7
without Handleguard on 1-pole units; .105“ [2.67mm] ] no
bezel overhang/ side on multipole units
8
without Handleguard on 1-pole units; .105“ [2.67mm] yes
bezel overhang/side on multipole units
11 AGENCY APPROVAL
C
UL Recognized & CSA Certified
D
VDE Certified, UL Recognized & CSA Certified
E
TUV Certified, UL Recognized & CSA Certified
I
UL Rec. STD 1077, UL Rec. 1500 (ignition protected), & CSA Certified
52
www.carlingtech.com
Carling
Technologies
B-Series Handle UL489A – Ordering Scheme
™
B A 1 B 0 14 450 1 B 1 M T
1
Series
2
Actuator
3
Poles
4
Circuit
5
Aux/Alarm
Switch
6
Frequency
& Delay
7
Current Rating
8
Terminal
9
Actuator
Color
10
Mounting/
Barriers
11
Max. Appl.
Rating
12
Agency
Approval
1 SERIES
B
2 ACTUATOR
1
A
Handle, one per pole
S
Mid-Trip Handle, one per pole
T
Mid-Trip Handle, one per pole & Alarm Switch
3 POLES
1
One
2
Two
3
Three
4
Four
4 CIRCUIT
B
Series Trip (Current)
5 AUXILIARY/ALARM SWITCH
2
0
w/o Aux Switch
1
S.P.D.T., 0.093 Q.C. Term.
2
S.P.D.T., 0.110 Q.C. Term.
3
S.P.D.T., 0.139 Solder Lug
6 FREQUENCY & DELAY
4
11
DC Ultra Short
12
DC Short
14
DC Medium
16
DC Long
7 CURRENT RATING (AMPERES)
210
215
220
225
230
235
240
245
250
255
260
265
270
275
280
285
290
295
410
512
0.100
0.150
0.200
0.250
0.300
0.350
0.400
0.450
0.500
0.550
0.600
0.650
0.700
0.750
0.800
0.850
0.900
0.950
1.000
1.250
415
517
420
522
527
430
435
440
445
450
455
460
465
470
475
480
485
490
495
610
1.500
1.750
2.000
2.250
2.750
3.000
3.500
4.000
4.500
5.000
5.500
6.000
6.500
7.000
7.500
8.000
8.500
9.000
9.500
10.000
710
611
711
612
712
613
614
615
616
617
618
620
622
624
625
630
635
4
640
4
645
4
650
4
10.500
11.000
11.500
12.000
12.500
13.000
14.000
15.000
16.000
17.000
18.000
20.000
22.000
24.000
25.000
30.000
35.000
40.000
45.000
50.000
8 TERMINAL
5
1
6
Push-On 0.250 Tab (Q.C.)
2
Screw 8-32 w/upturned lugs
3
7
Screw 8-32 (Bus Type)
4
Screw 10-32 w/upturned lugs
5
7
Screw 10-32 (Bus Type)
6
Screw 8-32 w/upturned lugs
and 30° bend
7
Screw 8-32 (Bus Type) and
30° bend
8
Screw 10-32 w/upturned lugs
and 30° bend
9 ACTUATOR COLOR
LEGEND
ON-OFF
White
B
Black
D
Red
G
Green
J
Blue
L
Yellow
N
Gray
Q
Orange
S
9
B
F
G
H
M
7
P
8
Q
Screw 10-32 (Bus Type) and
30° bend
Screw M5 w/upturned lugs
Screw M5 w/upturned lugs
and 30° bend
Screw M5 (Bus Type)
and 30° bend
Screw M5 (Bus Type)
M6 Threaded Stud
Printed Circuit Board
Terminals
Push-In Stud
7
8
9
S.P.S.T., 0.110 Q.C.
Term.(Gold Contacts)
S.P.S.T., 0.187 Q.C. Term.
S.P.D.T., 0.187 Q.C. Term.
52
3
54
3
56
3
DC, Short,Hi-Inrush
DC, Medium, Hi-Inrush
DC, Long, Hi-Inrush
Dual
1
2
3
4
5
6
7
8
Legend Color
Black
White
White
White
White
Black
Black
Black
10 MOUNTING/BARRIERS
MOUNTING STYLE
BARRIERS
Threaded Insert, 2 per pole
1
6-32 x 0.195 inches
no
A
6-32 X 0.195 inches
yes
2
ISO M3 x 5mm
no
B
ISO M3 x 5mm
yes
Rectangular Adapter Plate with mounting centers of 2.062 inches
and Threaded insert, 2 per pole
3
6-32 x 0.225 inches
no
C
6-32 X 0.225 inches
yes
4
ISO M3 x 6.5mm
no
D
ISO M3 x 6.5mm
yes
Front panel Snap-In, 0.75” wide bezel
5
without Handleguard
no
6
without Handleguard
yes
Front panel Snap-In, 0.96” wide bezel
7
without Handleguard on 1-pole
no
units; .105 “ bezel overhang/
side on multipole units
8
without Handleguard on 1-pole
yes
units; .105 “ bezel overhang/
side on multipole units
11 MAXIMUM APPLICATION RATING
M
80 DC
12 AGENCY APPROVAL
T
UL489A LISTED
K
UL489A LISTED, VDE CERTIFIED
Notes:
1
Actuator Code:
A: Handle tie pin spacer(s) and retainers provided unassembled with multi-pole units.
S: Handle moves to mid-position only upon electrical trip of the breaker.
T: Handle moves to mid-position and alarm switch activates only upon electrical trip of the
breaker.
2
On multi-pole breakers, one auxiliary switch is supplied, mounted in the extreme right
pole.
3
VDE Certified to 30 amps. UL489A Listed to 50 amps.
4
VDE Certification available with single pole breakers only. UL489A Listing available with
one and two pole breakers.
5
Screw Terminals are recommended on ratings greater than 20 amps. Ratings over 30
amps are only available with Terminal Codes 5, 9, G, H, M and Q.
6
Terminal Code 1 (Push-On) available up to 25 amps with VDE Certification and 30 amps
with UL489A Listing, but is not recommended over 20 amps.
7
Terminal Codes 3, 5 and H (Bus Type) with VDE, are supplied with Lock Washers, and
Terminal Code M (M6 Threaded Stud) with VDE is supplied with Lock and Flat Washers.
These breakers are only VDE Certified when the washers are used.
8
Single pole breakers with Terminal Code P (Printed Circuit Board) are available up to 30
amps with VDE Certification and 50 amps with UL489A Listing.