Multifunction Digital Timer
Quartz Timer Offers Eight Time
Ranges, Seven Output Operations
s
Field-selectable time ranges from 0.01
second to 9999 hours
s
Selectable elapsed time (UP) and
time remaining (DOWN) display
s
Contact and solid-state outputs available
simultaneously
s
ON-delay with sustained and adjustable
one-shot outputs, with and without
continued timing
s
Built-in DC power supply for input devices
s
Easy-to-read 8 mm-high LED display
s
10-year battery memory back-up available
s
Draw-out construction allows setting,
servicing without disconnecting wiring
s
Panel mounting hardware included
H5AN
Ordering Information
s
TIMERS
Add the supply voltage to the part number when you order. For example,
H5AN-4DM-AC100-240.
Timing functions
Contact type
Terminal form
DC power supply for
external components
Memory back-up
Part number
Supply
AC
voltage DC
ON-delay and ON-delay with one-shot
SPDT relay and open collector transistor outputs, both available simultaneously
14 terminal screws on rear of case
Provided
Not provided
H5AN-4D
24 V or 100 to 240 V; 50/60 Hz
12 to 24 V, 48 V or 100 V
Provided
Provided, 10-year built-in battery
H5AN-4DM
24 V or 100 to 240 V; 50/60 Hz
12 to 24 V
s
REPLACEMENT PARTS
Description
Plastic front cover
Mounting bracket (one pair supplied with each timer); order two
Part number
H5AN COVER 0377762-0
Y92H-5
1
H5AN
H5AN
Specifications
Part number
Supply
voltage
Operating voltage
DC
Internal power supply
for external components
Timing functions
Reset and Gate inputs
Time limit
Control Type
output
Instantaneous
Max. load
Min. load
Repeat accuracy
Setting error
Resetting system
Resetting time
Indicators
Materials
Mounting
Connections
Weight
Approvals
Operating ambient temperature
Humidity
Vibration Mechanical durability
Malfunction durability
Shock
Mechanical durability
Malfunction durability
Variation due to voltage change
Variation due to temperature change
Insulation resistance
Dielectric strength
Power
consumption
AC
AC
DC
H5AN-4D
24 V or 100 to 240 V; 50/60 Hz
12 to 24 V, 48 V or 100 V
(permissible ripple factor: 20% max.)
85 to 100% of rated voltage
10 VA at 240 VAC, 50 Hz
5 W at 24 VDC
12 VDC
±10%,
80 mA
(permissible ripple factor: 5% max.)
ON-delay and ON-delay with one-slot
No-voltage
SPDT relay and open collector solid-state output
–
3 A, 250 VAC (p.f. = 1) for relay; 100 mA max., 30 VDC for open collector output
10 mA, 5 VDC
±0.01% ±0.05
sec max. (power-OFF start);
±0.005% ±0.03
sec max. (reset start)
See "Repeat Accuracy"
Power-OFF, manual or external
Manual or external
Power-OFF: 0.5 sec min.; External: 0.02 sec signal minimum
Time Up (red LED), Reset Input (red LED); 8 mm LED numeric display
Plastic
Panel; two mounting brackets included
Back-mounted screw terminals
360 g (12.7 oz.)
UL/CSA/SEV
-10° to 55°C (14° to 131°F)
35 to 85% RH
10 to 55 Hz; 0.75 mm (0.03 in) double amplitude
10 to 55 Hz; 0.5 mm (0.02 in) double amplitude
30 G
10 G
See "Repeat Accuracy"
See "Repeat Accuracy"
100 MΩ min. at 500 VDC
2,000 VAC, 50/60 Hz for 1 minute between current-carrying terminals and non-current-
carrying metal parts
750 VAC, 50/60 Hz for 1 minute between non-continuous contacts
10 million operations minimum
100,000 operations minimum at maximum rating
H5AN-4DM
24 V or 100 to 240 V; 50/60 Hz
12 to 24 V
(permissible ripple factor: 20% max.)
Service life
Mechanical
Electrical
2
H5AN
H5AN
Engineering Data
s
ELECTRICAL SERVICE LIFE
Timing Charts
s
ELAPSED TIME (UP) DISPLAY
Power
Reset
input
Gate
input
Time setting
1-2
8-9
ON
OFF
ON
OFF
ON
OFF
Interruption
8 - 10
Digital display
(See note)
Control Relay 4 - 5, 4 - 6
output Solid-state 12-13-14
ON
OFF
(See note)
Time up indicator
ON
OFF
ON
OFF
NOTE:
After the set time has elapsed, operation continues according to the mode selected.
Reset input indicator
s
TIME REMAINING (DOWN) DISPLAY
Power
Reset
input
Gate
input
Time setting
1-2
8-9
ON
OFF
ON
OFF
ON
OFF
Interruption
8 - 10
Digital display
Control Relay 4 - 5, 4 - 6
output Solid-state 12-13-14
ON
OFF
ON
OFF
ON
OFF
NOTE:
After the set time has elapsed, operation continues according to the mode selected.
(See note)
(See note)
Time up indicator
Reset input indicator
3
H5AN
s
OPERATION MODES
Mode
N
Sustained
output
Reset
Set value
Digital display
H5AN
Elapsed time (UP) display
Time remaining (DOWN) display
Reset
Set value
Digital display
Control output
Control output
The display increments from zero to the preset. When
the preset is reached, the output is energized. The
preset is display until the timer is reset.
F
Sustained
Output
Reset
Set value
Digital display
The display decrements from the preset to zero. When
zero is reached, the output is energized. Zeros are
displayed until the timer is reset.
Reset
Set value
Digital display
Control output
Control output
The display increments from zero to the preset. When
the preset is reached, the output is energized. The
display will continue to increment until the timer is reset.
The display decrements from the preset to zero. When
zero is reached, the output is energized. The display
will continue to decrement until the timer is reset.
C
One-shot
Output
Reset
Set value
Digital display
Reset
Set value
Digital display
Control output
Control output
The display increments from zero to the preset. When
the preset is reached, the timer restarts its timing from
zero and energizes a one-shot output. The cycle is
repeated until the timer is reset.
R
One-shot
Output
Reset
Set value
Digital display
The display decrements from the preset to zero. When
zero is reached, the timer restarts its timing from the
preset and energizes a one-shot output. The cycle is
repeated until the timer is reset.
Reset
Set value
Digital display
Control output
Control output
The display increments from zero to the preset. When
the preset is reached, the output is energized for the
one-shot time. Timing from zero is restarted at the
trailing edge of the output. The cycle is repeated until
the timer is reset.
K
One-shot
Output
Reset
Set value
Digital display
The display decrements from the preset to zero. When
zero is reached, the output is energized for the one-shot
time. Timing from the preset is restarted at the trailing
edge of the output. The cycle is repeated until the timer
is reset.
Reset
Set value
Digital display
Control output
Control output
The display increments from zero to the preset. When
the preset is reached, the output is energized for the
one-shot time. The display continues to increment until
the timer is reset.
The display decrements from the preset to zero. When
zero is reached, the output is energized for the one-shot
time. The display continues to decrement until the timer
is reset.
NOTE:
In modes F and K, when the 99 min 59 s or 99 h 59 min ranges are selected in DOWN display, the overflow values will be
shown as 9959, 9958, 9957, etc.
In C mode, the set time should be longer than the one-shot time.
4
H5AN
OPERATION MODES (continued)
Mode
P
One-shot
output
Reset
Set value
Digital display
H5AN
Elapsed time (UP) display
Time remaining (DOWN) display
Reset
Set value
Digital display
Control output
Control output
The display increments from zero to the preset. When
the preset is reached, the output is energized for the
one-shot time. The timer restarts its timing, but the
display is not updated until the one-shot time is up.
The cycle is repeated.
Q
One-shot
Output
Reset
Set value
Digital display
The display decrements from the preset to zero. When
zero is reached, the output is energized for the one-shot
time. The timer restarts its timing, but the display is not
updated until the one-shot time is up. The cycle is
repeated.
Reset
Set value
Digital display
Control output
Control output
The display increments from zero to the preset. When
the preset is reached, the output is energized for the
one-shot time. The display continues incrementing
during the one-shot, but restarts from zero when the
one-shot time is up. The cycle is repeated.
NOTE:
The display decrements from the preset to zero. When
zero is reached, the output is energized for the one-shot
time. The display continues decrementing during the
one-shot, but restarts from the preset when the one-shot
time is up. The cycle is repeated.
In mode Q, when the 99 min 59 s or 99 h 59 min ranges are selected in DOWN display, the overflow values will be shown as
9959, 9958, 9957, etc.
In P mode, the set time should be longer than the one-shot time.
Dimensions
Unit: mm (inch)
Two mounting
brackets
M3.5 terminal
screws
72
(2.83)
67.6
(2.66)
72
(2.83)
115 (4.53)
130 (5.12)
Panel cutout
Panel cutout for side-by-side
mounting for two units
NOTE:
Recommended panel thickness is 1 to 5 mm.
Panel cutout conforms to DIN 43700.
5