NEMA Contactors & Starters
Freedom
September 2008
33-105
Relays — Thermal Overload
Factory Modifications
C306 Thermal Overload Relays with Mounting Adapter
Consists of a thermal overload relay mounted to a terminal
base adapter — permits fast and easy installation.
Table 33-159. Product Selection
Description
C306DN3B + C306TB1
C306GN3B + C306TB2B
Catalog
Number
C306DT3B
C306GT3B
Price
U.S. $
Replacement Parts
Heater Pack Replacement
The heater pack series is determined by the 6th character of
the Catalog Number. Series A or prior heater packs (identi-
fied by either “A” or “-” as the 6th character) have built-in
load lugs. Series B or later heater packs do not (load lugs are
on overload relay). Replacement of Series A or earlier heater
packs with Series B or later heater packs, requires the one
time addition of Lug Adapter Kit C3606KAL1-3B to the Series
A1 overload relay.
33
Accessories
DIN Rail and Panel Mounting Adapter
These adapters are required when
component overload relays are to be
separately mounted. The terminal base
adapter includes line terminals and
connects with the overload relays on
Page 33-107.
Cat. No. C306TB1
Superseded
Series A
Heater Pack
Series B
Heater Pack
Table 33-162. Heater Pack Replacement Requirements
Existing Heater Pack
Catalog Numbers
Replacement Product Required
Lug Adapter Kit C306KAL1-3B and Series B
Heater Pack
Series B Heater Pack
When inventory is exhausted, replace with
Lug Adapter Kit C3606KAL1-3B and Series B
Heater Pack
Series B Heater Pack
When inventory is exhausted, replace with
heater pack chosen from
Table 33-163
When inventory is exhausted, replace with
Lug Adapter Kit C3606KAL1-3B and Series B
Heater Pack
Series B Heater Pack
Table 33-160. Product Selection
Description
For 32A Overload Relay
For 75A Overload Relay
Catalog
Number
C306TB1
C306TB2B
Price
U.S. $
H2001-3 – H2013-3
H2001A-3 – H2013A-3
H2001B-3 – H2013B-3
H2014-3
H2014A-3
H2014B-3
This Series B adapter will accept Series A or B overload relays
(C306GN3 or C306GN3B), C306TB2 can only be used with C306GN3.
Locking Cover for Overload Relay — C306 Only
Snap-on transparent or opaque plastic
panel for covering access port to the
overload relay trip setting dial — helps
prevent accidental or unauthorized
changes to trip and reset setting.
H2015-3 – H2017-3
H2015A-3 – H2017A-3
H2015B-3 – H2017B-3
Table 33-163. Heater Pack Ratings
Motor Full Load Ampere Rating
Dial Position
A
B
32.5
44.3
60.4
C
36.0
49.1
66.8
D
39.5
53.8
74.9
Order
Price
Heater Pack
U.S. $
Catalog Number
H2015B-3
H2016B-3
H2017B-3
Overload Relay
Cover
Table 33-161. Product Selection
Description
Min.
Order Qty.
(Std. Pkg.)
50
50
50
50
Catalog
Number
C320PC3
C320PC4
C320PC5
C320PC6
Price
U.S. $
29.0
39.6
53.9
Clear cover, no accessibility
Gray cover, no accessibility
w/Auto only nib
Gray cover, no accessibility,
w/Manual only nib
Gray cover with FLA dial
accessibility, A, B, C, D positions
and Auto only nib
Gray cover with FLA dial
accessibility, A, B, C, D positions
and Manual only nib
50
C320PC7
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . .
1CD1C
CA08102001E
For more information visit:
www.eaton.com
33-108
NEMA Contactors & Starters
Freedom
March 2009
Relays — Thermal Overload
Table 33-169. Standard Trip — Class 20 Heater Selection
Overload
Relay
Size
Motor Full Load Ampere Rating
Dial Position
A
B
C
D
Catalog
Number
(Includes
3 Heater
Packs)
Price
U.S. $
Table 33-170. Fast Trip — Class 10 Heater Selection
Overload
Relay
Size
Motor Full Load Ampere Rating
Dial Position
A
B
C
D
Catalog
Number
(Includes
3 Heater
Packs)
Price
U.S. $
33
For Use with NEMA Sizes 00 – 0 Series C, NEMA Sizes 1 – 2 Series B;
IEC Sizes A – F Series C, IEC Sizes G – K Series B
32A or
75A
.254
.375
.560
.814
1.20
1.79
2.15
3.23
4.55
6.75
9.14
14.0
18.7
23.5
75A
29.0
39.6
53.9
8.0
11.4
14.3
18.0
24.6
33.5
45.7
62.2
84.7
106.0
32A
49
72
107
129
194
144
215
258
388
163
240
358
430
646
244
360
537
645
969
.306
.452
.676
.983
1.45
2.16
2.60
3.90
5.50
8.17
10.8
16.9
22.7
28.5
34.0
45.5
60.9
9.2
12.8
15.7
20.2
27.6
37.5
51.2
69.7
95.0
118.0
59
87
130
156
234
174
259
312
468
197
290
432
520
780
295
435
648
780
1170
.359
.530
.791
1.15
1.71
2.53
3.04
4.56
6.45
9.58
12.4
19.9
26.7
33.5
39.1
51.5
67.9
10.3
14.3
17.4
22.3
30.5
41.5
56.7
77.1
105.0
131.0
69
103
152
182
274
205
304
365
547
230
342
506
608
912
345
513
759
912
1368
.411
.607
.907
1.32
1.96
2.90
3.49
5.23
7.40
11.0
14.0
22.8
30.7
38.5
44.1
57.4
74.9
11.5
15.7
19.0
24.5
33.4
45.6
62.1
84.6
115.0
144.0
79
118
174
209
—
235
348
419
627
264
392
580
698
—
396
588
870
1047
—
H2001B-3
H2002B-3
H2003B-3
H2004B-3
H2005B-3
H2006B-3
H2007B-3
H2008B-3
H2009B-3
H2010B-3
H2011B-3
H2012B-3
H2013B-3
H2014B-3
H2015B-3
H2016B-3
H2017B-3
H2025-3
H2026-3
H2027-3
H2018-3
H2019-3
H2020-3
H2021-3
H2022-3
H2023-3
H2024-3
H2004B-3
H2005B-3
H2006B-3
H2007B-3
H2008B-3
H2005B-3
H2006B-3
H2007B-3
H2008B-3
H2004B-3
H2005B-3
H2006B-3
H2007B-3
H2008B-3
H2004B-3
H2005B-3
H2006B-3
H2007B-3
H2008B-3
For Use with NEMA Sizes 00 – 0 Series C, NEMA Sizes 1 – 2 Series B;
IEC Sizes A – F Series C, IEC Sizes G – K Series B
32A or
75A
.260
.384
.570
.846
1.28
1.92
2.30
3.38
4.96
7.07
9.60
14.4
18.7
23.5
75A
28.3
36.6
53.8
51
77
115
138
203
154
230
276
406
169
256
384
460
676
254
384
576
690
1014
.313
.464
.688
1.02
1.55
2.33
2.79
4.10
6.03
8.58
11.2
17.5
21.8
27.3
32.6
42.3
60.8
61
93
140
167
246
186
280
335
492
204
310
466
558
820
306
465
699
837
1230
.367
.543
.806
1.20
1.83
2.74
3.28
4.82
7.09
10.1
12.8
20.7
25.0
31.0
37.0
48.1
67.9
72
110
164
197
289
220
329
394
578
240
366
543
656
—
360
549
822
984
—
.420
.623
.924
1.37
2.10
3.15
3.77
5.54
8.16
11.6
14.4
23.8
28.1
34.8
41.3
53.8
74.9
82
126
189
226
—
252
378
452
—
274
420
630
754
—
411
630
945
1131
—
H2101B-3
H2102B-3
H2103B-3
H2104B-3
H2105B-3
H2106B-3
H2107B-3
H2108B-3
H2109B-3
H2110B-3
H2111B-3
H2112B-3
H2113B-3
H2114B-3
H2115B-3
H2116B-3
H2117B-3
H2104B-3
H2105B-3
H2106B-3
H2107B-3
H2108B-3
H2105B-3
H2106B-3
H2107B-3
H2108B-3
H2104B-3
H2105B-3
H2106B-3
H2107B-3
H2108B-3
H2104B-3
H2105B-3
H2106B-3
H2107B-3
H2108B-3
For Use with NEMA Size 2, IEC Sizes G – K Only — Series B
For Use with NEMA Size 2, IEC Sizes G – K Only — Series B
For Use with NEMA Sizes 3 – 4, IEC Sizes L – N Only — Series A
105A or
144A
For Use with Size 5 Starters Only — Series B and IEC P, R and S with 300/5 CT
32A
For Use with Size 6 Starters Only — Series B and IEC T – V with 600/5 CT
32A
For Use with Size 5 Starters — Series B and IEC P, R and S with 300/5 CT
For Use with Size 7 Starters Only — Series B and IEC W – X with 1000/5 CT
32A
For Use with Size 6 Starters Only — Series B and IEC T – V with 600/5 CT
32A
For Use with Size 8 Starters Only — Series B and IEC Z with 1500/5 CT
32A
For Use with Size 7 Starters Only — Series B and IEC W – X with 1000/5 CT
32A
Heater packs are shipped 3 to a carton. Catalog Numbers are for
3 heater packs.
Sizes 5 – 8 and IEC P – Z use the 32A overload relay with current
transformers.
For Use with Size 8 Starters Only — Series B and IEC Z with 1500/5 CT
32A
Heater packs are shipped 3 to a carton. Catalog Numbers are for
3 heater packs.
Sizes 5 – 8 and IEC P – Z use the 32A overload relay with current
transformers.
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . .
1CD1C
For more information visit:
www.eaton.com
CA08102001E