EEWORLDEEWORLDEEWORLD

Part Number

Search

W28-XT1A-12

Description
THERMAL CIRCUIT BREAKER
CategoryCircuit protection   
File Size533KB,2 Pages
ManufacturerMACOM
Websitehttp://www.macom.com
Download Datasheet Parametric View All

W28-XT1A-12 Online Shopping

Suppliers Part Number Price MOQ In stock  
W28-XT1A-12 - - View Buy Now

W28-XT1A-12 Overview

THERMAL CIRCUIT BREAKER

W28-XT1A-12 Parametric

Parameter NameAttribute value
stateActive
circuit_protection_typeTHERMAL CIRCUIT BREAKER
Manufacturer SeriesW28
Catalog 1308242
Issued 3-03 (PDF Rev. 10-10)
W28
series
Push to Reset
Fuseholder-Type
Thermal P
&
B Circuit Breaker
Note:
VDE not available on 16A and 20A W28 only.
Features
Push to reset.
Approved to many international standards.
Replaces slow blow glass cartridge fuse.
Labor-saving snap-in mounting.
Button extends for visual trip indication.
Resettable Overload Capacity:
Six times rated current for 0.25 through
2 amp models. Ten times rated current
for 3 through 20 amp models.
Reset Time:
180 seconds max. for 0.25 through 2 amp models. 5 to 30
seconds for 3 through 20 amp models.
Agency Approvals
W28 series is UL 1077 Recognized as Supplementary Protectors, File
E69543, and CSA Accepted as Supplementary Protectors (Appliance
Component Protectors), File LR15734. W28 breakers are VDE
approved for use in office equipment (AC loads only) and provides
8mm isolation. 16 amp and 20 amp models do not have VDE
approvals at present.
Users should thoroughly review the technical data before selecting a product part
number. It is recommended that users also seek out the pertinent approvals files of
the agencies/laboratories and review them to confirm the product meets the
requirements for a given application.
Typical Resistance vs. Current Rating @ +25°C
Current
Rating
in Amps
0.25
0.50
0.75
1.0
2.0
3.0
4.0
5.0
6.0
7.0
Typical
Resistance
in Ohms
14.0
3.55
2.0
0.89
0.17
0.069
0.043
0.030
0.026
0.017
Current
Rating
in Amps
8.0
9.0
10.0
11.0
12.0
13.0
14.0
15.0
16.0
20.0
Typical
Resistance
in Ohms
0.016
0.014
0.011
0.01
0.009
0.009
0.007
0.007
0.007
0.006
Electrical Data @ 25°C
Calibration:
Will continuously carry 100% of rating.
3-20 amp models – may trip between 101% and 134%, but
must trip at 135% of rating within one hour at +25°C.
0.25-2 amp models – may trip between 101% and 174%, but
must trip at 175% of rating within one hour at +25°C.
Dielectric Strength:
Over 1,500 volts RMS.
Maximum Operating Voltages:
32VDC; 250VAC, 50/60 Hz.
Interrupt Capacity:
1,000 amps at 250VAC, 50/60 Hz. and 32VDC in
accordance with UL standard 1077.
Mechanical/Environmental Data
Termination:
.250” (6.35mm) quick connects. Soldering to terminals is
not recommended.
Mounting:
Snaps into panel from front. See Recommended
Panel Cutouts.
Approximate Weight:
0.35 oz. (10g).
Time vs. Current Trip Curve @ +25°C
1000
(A) All 3-20 Amp Models
(B) All 0.25-2 Amp Models
Overload
Trip Times
Ambient Compensation Chart
1.40
Overload
Trip Times
900
800
Load Current As A Percent
Of Breaker Rating
700
600
500
400
300
200
100
0
.1
1
(A)
1.30
Correction Factor
1.20
1.10
1.00
0.90
0.80
0.70
0.60
–20 –10 0 10 20 30 40 50 60
Ambient Temperature In Degrees Centigrade (°C)
100%
135%
200%
400%
600%
800%
1000%
No Trip
Trip in 1 hour
2.2-15.0 Sec.
0.55-1.8 Sec.
0.27-0.7 Sec.
0.17-0.45 Sec.
0.12-0.3 Sec.
100%
175%
200%
400%
600%
No Trip
Trip in 1 hour
4.5-28.0 Sec.
1.0-6.5 Sec.
0.4-4.0 Sec.
(B)
175
135
10
Time In Seconds
100
1000
To use this chart:
Read up from the ambient temper-
ature to the curve, and across to find a correction fac-
tor. Multiply the breaker rating by the correction fac-
tor to determine the compensated rating. Calculate
the overloads in terms of the compensated rating to
use the published trip curve.
Do not use these devices outside their specified
operating temperature ranges.
Dimensions are shown for
110
reference purposes only.
Dimensions are in inches over
(millimeters) unless otherwise
specified.
Specifications and availability
subject to change.
www.tycoelectronics.com
Technical support:
Refer to inside back cover.

Technical ResourceMore

EEWorld
subscription
account

EEWorld
service
account

Automotive
development
circle

Robot
development
community

Index Files: 1425  2720  1590  41  1861  29  55  32  1  38 
Datasheet   0 1 2 3 4 5 6 7 8 9 A B C D E F G H I J K L M N O P Q R S T U V W X Y Z
Room 1530, 15th Floor, Building B, No. 18 Zhongguancun Street, Haidian District, Beijing Telephone: (010) 82350740 Postal Code: 100190
Copyright © 2005-2026 EEWORLD.com.cn, Inc. All rights reserved 京ICP证060456号 京ICP备10001474号-1 电信业务审批[2006]字第258号函 京公网安备 11010802033920号