HWS30-1500/ME Series
Single Output Industrial Power Supplies
Features
Limited Lifetime Warranty
Medical Approvals
2
Universal Input (85 - 265VAC)
High Efficiency
Broad 30W to 1500W product range
Wide range AC Input
Key Market Segments & Applications
Specifications
Model
Input Voltage range (47-63Hz) (2)
Input Current (Typ)
(1)
Inrush Current
(1)
Power Factor / Flicker
Temperature Coefficient
Overcurrent Protection
Overvoltage Protection
Hold Up Time (Typ)
Leakage Current (60Hz)
Remote Sense
Indicator
Remote On/Off
Parallel operation
DC Good
Voltage Programming
Operating Temperature & Derating
Storage Temperature
Humidity (non condensing)
Cooling
Withstand Voltage
Isolation Resistance
Vibration (non operating)
Shock
Safety Agency Approvals
Line Dip
Conducted & Radiated EMI
Immunity
Weight (Typ)
Size (WxHxD)
Warranty
HWS30
HWS100
HWS300
HWS600
HWS1500
HWS50
HWS150
-
85 - 265VAC or 120 - 370VDC
85 - 265VAC or 120 - 330VDC
85 - 265VAC
A
0.8 / 0.4
1.3 / 0.65
4.1 / 2.1
8.1 / 3.9
19 / 10
0.7 / 0.35
1.9 / 0.95
A
14 / 28
20 / 40
-
Meets EN61000-3-2, EN61000-3-3
-
<0.02%/°C
-
>104%
V
Yes (See table on page 2)
ms
20
mA
<0.5mA
-
No
Yes
-
Green LED = ON
-
No
Yes (Isolated from output)
-
No
Single wire connection (5 units max)
-
No
Yes
-
No
Yes
°C
HWS30-150: -10°C to +70°C, (-10 - +50°C: 100%, +60°C: 60%, +70°C: 20%)
HWS300-1500: -10°C to +70°C, (-10 - +50°C: 100%, derate linearly to 50% load from +50 to +70°C)
°C
-30 to +85°C
-
Operating: 30 - 90%RH (10 -90% on HWS300-1500), Non operating 10 - 95%RH
-
Convection
Internal fan
-
I/P to Grnd 2kVAC, I/P to O/P 3kVAC, O/P to Grnd 500VAC, O/P to Remote On/Off 100VAC for 1 min.
-
>100M at 25C & 70%RH, Output to Ground 500VDC, >10M Output to remote on/off 100VDC
-
10 - 55Hz (1 min sweep), 19.6m/s
2
constant, X, Y, Z axis, one hour each
-
< 196.1m/s
2
-
UL60601-1, EN60601, CSA-C22.2 No601.1-M90 (C-UL) (basic insulation), CE Mark
-
Complies with SEMI F47 (200VAC line only)
-
EN55011 / EN55022-B, FCC-B, VCCI-B (HWS600 & 1500 Class A)
-
IEC61000-4-2 (Level 2,3), -3, -4, -6, (Level 3), -5 (Level 3,4), -8 (Level 4), -11
g
220
450
1000
1600
3800
280
500
in 1.04x3.23x3.74
1.1x3.23x6.3
2.4x3.23x6.5
3.94x3.23x6.5 4.98x3.23x11.02
1.04x3.23x4.72
1.46x3.23x6.3
yrs
Limited lifetime warranty (See TDK-Lambda’s terms & conditions)
(3) HWS300-600 2.5kVAC Input to ground
(3)
(2)
(1) 100/200VAC input
(2) See conditions of accep[tability and clause 19.5DV.2 of UL60601 for
equipment in proximity of patient
The HWS50 to HWS150 is now obsolete,
please see HWS-A series
1-800-526-2324 • www.us.tdk-lambda.com/lp/
82
Disclaimer: us.tdk-lambda.com/lp/legal.htm
HWS30-1500/ME Series
Output Ratings
Model
HWS30-5/ME
HWS50-5/ME
HWS100-5/ME
HWS150-5/ME
HWS30-12/ME
HWS50-12/ME
HWS100-12/ME
HWS150-12/ME
HWS300-12/ME
HWS30-15/ME
HWS50-15/ME
HWS100-15/ME
HWS150-15/ME
HWS300-15/ME
(5)
HWS30-24/ME
HWS50-24/ME
HWS100-24/ME
HWS150-24/ME
HWS300-24/ME
HWS600-24/ME
HWS1500-24/ME
HWS1500-36/ME
HWS30-48/ME
HWS50-48/ME
HWS100-48/ME
HWS150-48/ME
HWS300-48/ME
(5)
HWS1500-48/ME
Adjust
Voltage
Range
5V
4.0 - 6.0
5V
4.0 - 6.0
5V
4.0 - 6.0
5V
4.0 - 6.0
12V
9.6 - 14.4
12V
9.6 - 14.4
12V
9.6 - 14.4
12V
9.6 - 14.4
12V
9.6 - 14.4
15V
12.0 - 18.0
15V
12.0 - 18.0
15V
12.0 - 18.0
15V
12.0 - 18.0
15V
12.0 - 18.0
24V
19.2 - 28.8
24V
19.2 - 28.8
24V
19.2 - 28.8
24V
19.2 - 28.8
24V
19.2 - 28.8
24V
19.2 - 28.8
24V
19.2 - 28.8, 4.8 - 28.8
(7)
36V
28.8 - 43.2, 7.2 - 43.2
(7)
48V
38.4 - 52.8
48V
38.4 - 52.8
48V
38.4 - 52.8
48V
38.4 - 52.8
48V
38.4 - 52.8
48V
38.4 - 52.8, 9.6 - 52.8
(7)
Max
Curr(A)4
6
10
20
30
2.5
4.3
8.5
13
27
2
3.5
7
10
22
1.3
2.2
4.5
6.5
14 (16.5 pk)
(6)
27 (31 pk)
(6)
65 (105 pk)
(6)
42 (70 pk)
(6)
0.65
1.1
2.1
3.3
7
32
Max
Load
Power(W) Reg(mV)
30
40
50
40
100
40
150
40
30
96
51.6
96
102
96
156
96
324
72
30
120
52.5
120
105
120
150
120
330
90
31.2
192
52.8
192
108
192
156
192
336
144
648
144
1560(2520 pk)
(6)
144
1512(2520 pk)
(6)
150
31.2
384
52.8
384
100.8
384
158.4
384
336
288
1536
288
Line
Reg(mV)
20
20
20
20
48
48
48
48
48
60
60
60
60
60
96
96
96
96
96
96
96
144
192
192
192
192
192
192
Ripple
Overvoltage
Noise(mV)
(V)
120
6.25-7.25
120
6.25-7.25
120
6.25-7.25
120
6.25-7.25
150
15-17.4
150
15-17.4
150
15-17.4
150
15-17.4
150
15-17.4
150
18.8-21.8
150
18.8-21.8
150
18.8-21.8
150
18.8-21.8
150
18.8-21.8
200
30-34.8
150
30-34.8
150
30-34.8
150
30-34.8
150
30-34.8
150
30-34.8
200
30-34.8
200
34-49.7
200
55.2-64.8
200
55.2-64.8
200
55.2-64.8
200
55.2-64.8
350
55.2-64.8
200
55.2-64.8
Efficiency
(typ)%1
77/80
82/84
83/86
83/86
81/83
81/83
83/86
83/86
80/83
81/83
81/83
83/86
83/86
82/85
83/86
82/84
84/87
85/88
82/85
82/85
84/88
84/88
82/83
83/85
84/87
85/88
82/85
86/90
(4) Peak load for 10s maximum on time, 35% duty cycle
(5) Safety agency in progress - contact factory for status.
(6) 200-265AC Input
(7) Using voltage programming input - see installation manual for details
Options
Suffix
Blank
/MEA
Description
No Cover (HWS30-150/ME Only)
HWS300-1500/ME the cover is always fitted
The cover option for the
HWS30-150/ME is special order only.
HWS300-1500/ME the cover is always fitted
For Additional Information, please visit
us.tdk-lambda.com/lp/products/hws-series.htm
The HWS50 to HWS150 is now obsolete,
please see HWS-A series
1-800-526-2324 • www.us.tdk-lambda.com/lp/
83
Revision B7: Jul 2019