On-Delay Relay, 4PDT, Momentary, 0.104A (Coil), 24VDC (Coil), 2500mW (Coil), 10A (Contact), 28VDC (Contact), 1s Adj Min, 10s Adj Max, DC Input, AC/DC Output, Through Hole-Straight Mount
CategoryMechanical and electronic products    relay   
File Size447KB,2 Pages
ManufacturerStruthers-Dunn
Download Datasheet Parametric View All

246ABA33-01024VDC Overview

On-Delay Relay, 4PDT, Momentary, 0.104A (Coil), 24VDC (Coil), 2500mW (Coil), 10A (Contact), 28VDC (Contact), 1s Adj Min, 10s Adj Max, DC Input, AC/DC Output, Through Hole-Straight Mount

246ABA33-01024VDC Parametric

Parameter NameAttribute value
Reach Compliance Codeunknow
ECCN codeEAR99
Maximum adjustable time delay10 s
Minimum adjustable time delay1 s
body width37.2 mm
body height95.2 mm
Body length or diameter66.8 mm
Maximum coil current (DC)0.104 A
Coil operating voltage (DC)19.2 V
Coil power2500 mW
Coil resistance230.77 Ω
Maximum coil voltage (DC)24 V
Coil/Input Power TypeDC
Contact (AC) maximum rated R load10A@240VAC
Maximum contact current (AC)10 A
Maximum contact current (DC)10 A
Contact (DC) maximum rated R load10A@28VDC
Maximum contact voltage (AC)240 V
Maximum contact voltage (DC)28 V
Contact/Output Power TypeAC/DC
Electrical life100000 Cycle(s)
Manufacturer's serial number246
Installation featuresTHROUGH HOLE-STRAIGHT MOUNT
Maximum operating temperature70 °C
Minimum operating temperature-20 °C
physical size66.8mm X 37.2mm X 95.2mm
GuidelineCSA; UL
Relay actionMOMENTARY
Relay function4PDT
Relay typeON-DELAY RELAY
surface mountNO
Termination typeSOLDER
Base Number Matches1
246/247 Series - Timer Delay Relay
DPDT, 4PDT,6PST, 10 Amp
Rugged, industrial time delay versions of the popular 219 series. Contacts can be configured up
to four pole double throw or six pole single throw. Time ranges are adjustable over a 1:10 range.
Knob adjustment and integral hold down clip are standard. A large option list makes this product
easily customized for special applications.
E13224
GENERAL SPECIFICATIONS (@ 25° C)
Timing:
Functions Available
Time Range
Timing Adjustment
Timing Repeatability
(Constant voltage and temperature)
Reset Time maximum
Input Pulse Length minimum
Contacts:
Contact Configuration
Contact Material
Contact Rating
120 / 240VAC Resistive
28VDC Resistive
Motor 120VAC
Motor 240VAC
Minimum Contct Load
Contact Resistance, Initial
Coil:
Coils Available
Nominal Coil Power
Input Voltage Tolorance -AC
Input Voltage Tolorance -DC
Transient Protection
Reverse Polarity Protection
Duty
Dielectric Strength:
Across Open Contacts
Between Mutally Insulated Points
Insulation Resistance
Temperature:
Operating
Storage
Life Expectancy:
Electrical (full load operations)
Mechanical (no load operations)
Miscellaneous:
Mounting Position
Mating Socket
Accessories
Enclosure
Weight
On-delay, Off-delay
Up to 10 minutes
Knob
3%
150mS
50mS
DPDT, 4PDT, 6PST
Silver Alloy Gold Diffused
10 Amp / 5 Amp
10 Amp
-
-
500mW
100 milliohms max @ 6VDC, 1A
AC and DC
5VA 2.5W
85% to 110% of nominal
80% to 110% of nominal
Yes
Yes
Continuous
500Vrms
1500Vrms
1,000 Mohms min @ 500VDC
-20 to 70°C (-4 to 158°F)
-40 to 105°C (-40 to 221°F)
100,000
10,000,000
Any
12 pin =27390, 27390D
14 pin = 33377, 33377D
Hold down clip integral to relay
Clear Polycarbonate
8.6oz (244 grams)
with socket
Industrial Pin Out
Note: SM = Single make
DM = Double make
Voltage
Make
Carry
Resistive Inductive
120VAC
30 Amp 10 Amp 10 Amp
3 Amp
240VAC
30 Amp 10 Amp 5 Amp
1 Amp
24VDC
30 Amp 10 Amp 10 Amp
5 Amp
28VDC
30 Amp 10 Amp 10 Amp
3 Amp
125VDC
30 Amp 10 Amp 0.5 Amp
0.1 Amp
For versions with suffix “69” permant magnet blowouts
Voltage
Make
Carry
Resistive Inductive
125VDC (SM) 30 Amp 10 Amp 1.5 Amp
0.5 Amp
125VDC (DM) 30 Amp 10 Amp
4 Amp
1.5 Amp
250VDC (SM) 30 Amp 10 Amp
0.5 Amp 150 mAmp
250VDC (DM) 30 Amp 10 Amp 1.5 Amp
0.5 Amp
246/247 Contact Load Specifications
7/9
www.struthers-dunn.com
(843) 664-3303
Electrical knowledge encyclopedia
Electrical knowledge sharing...
缥缈轮回 Analog electronics
When a 1MHZ step signal is input, how does the output of the integrating circuit composed of operational amplifiers restore the input signal?
When a 1MHZ step signal is input, how does the output of the integration circuit composed of op amps restore the input signal? What kind of op amp is more suitable? How to calculate the resistance and...
yyzh Analogue and Mixed Signal
Should I choose combinational logic or sequential logic?
The output of combinational logic is only related to the current input; while the output of sequential logic is not only related to the input, but also to the previous state of the system. This is ver...
DSP16 FPGA/CPLD
PG-1000 Series Pulse Generator SCPI Remote Control
This article uses the PG 1000 series pulse generator from Active Technologies (AT) as an example to explain how to use NI MAX to configure the system before using SCPI to control the instrument. 1.[/c...
Stone_Mei Test/Measurement
How to test if the TVS diode is working
I don't have any tools like an electrostatic generator, only a linear power supply with a maximum of 60V 3.3A. A smaj36 transient tube is connected in parallel to the circuit, but I don't know if this...
abusama Industrial Control Electronics
AVR STUDIO4 compiles 485 sending program and there is a puzzling problem. Please help me find out what is going on.
Program: void USART1_Send(void) //RS485 sending function { uint i; // uchar tx_cBuffer1[100]; tx_cBuffer1[0]=0x01; tx_cBuffer1[1]=0x03; tx_cBuffer1[2]=0x00; tx_cBuffer1[3]=0x03; tx_cBuffer1[4]=0x00; t...
weipj528 Microchip MCU

EEWorld
subscription
account

EEWorld
service
account

Automotive
development
circle

Robot
development
community

Index Files: 888  1670  2391  2096  887  18  34  49  43  5 
Datasheet   0 1 2 3 4 5 6 7 8 9 A B C D E F G H I J K L M N O P Q R S T U V W X Y Z
Room 1530, 15th Floor, Building B, No. 18 Zhongguancun Street, Haidian District, Beijing Telephone: (010) 82350740 Postal Code: 100190
Copyright © 2005-2026 EEWORLD.com.cn, Inc. All rights reserved 京ICP证060456号 京ICP备10001474号-1 电信业务审批[2006]字第258号函 京公网安备 11010802033920号