• Mechanical interlock auxiliary contact for hydraulic
elevators with automatic recall (5 amp 120 Vac rated)
• NEMA 3R, 4, and 12 enclosures available
3
• Phase failure and undervoltage relay available, consult
factory
• For added safety, use the Bussmann SAMI fuse covers to
improve maintenance personnel protection
4
(OSHA 1910.333, paragraph C)
Agency Approvals:
U.L. 98 Enclosed and Dead Front Switch
Guide 96NK3917, File E182262
NEMA 1, U.L. 50, listed enclosure
U.L.c per Canadian Standards C22.2, No. 0-M91-CAN/CSA
C22.2, No. 4-M89 Enclosed Switch
Option 2
Fire Safety Interface
Relay (3PDT, 10 amp, 120V)
Option 3
Key to Test Switch
Option 4
Pilot Light – “ON”
Option 5
Isolated Neutral Lug
(Full Capacity)
2
Option 6
Mechanical interlock auxiliary contact
for hydraulic elevators with automatic
recall (5 amp 120 Vac rated)
Option 7
Optional Enclosure
NEMA 3R
NEMA 4
NEMA 12
U
Y
Z
1
Class
J fuses not included.
200% rated neutral option available where required by excessive
non-linear loads.
3
Through 200A.
4
Through 100A.
5
Will handle up to 447VA inrush.
2
Oversized
Catalog No. Construction:
Catalog number of PS Switch
Options as required in option order as listed above
(i.e. option 1, 2, 3, etc.)
Example: •
•
•
•
•
100A S.T. Switch 480V-3P – PS1
480–120V CPT – T48
120 Vac Coil Fire Safety Interface Relay – R1
Pilot Light - “ON” (Green) – G
Mech. Interlock (1 NO & 1 NC) – A
Catalog Number PS1T48R1GA
Typical construction includes control power transformer and
fire safety interface relay as minimum options required.
12-28-98
SB98107
Rev. A
Form No. PS
Page 1 of 4
BIF Doc# 1145
Bussmann
®
Bussmann Power Module Switch
All-In-One Module
Bussmann Power Module Switch – Dimensions and Lug Data
Catalog
NEMA 1
NEMA
Number
Amp
Dimensions
1
3R, 12
2
PS3
30
20∑H ≈ 16∑W
20∑H ≈ 16∑W
PS6
60
20∑H ≈ 16∑W
20∑H ≈ 16∑W
PS1
100
20∑H ≈ 16∑W
20∑H ≈ 16∑W
PS2
200
30∑H ≈ 20∑W
30∑H ≈ 20∑W
PS4
400
55∑H ≈ 40∑W
—
1
Standard over size enclosure to mount control power transformer, interface relay and control terminal blocks.
2
Contact factory for dimensions for NEMA 4 enclosure.
3
Optional neutral lug size same as line and load.
Depth
8fiΩ•∑
8fiΩ•∑
8fiΩ•∑
8fiΩ•∑
13∑
PS
Lug Size
3
#14 - #8 Al or Cu
#14 - #2 Al or Cu
#8 - 1/0 Al or Cu
#6 - 250 kcmil Al or Cu
(2) 3/0 - 500 kcmil Al or Cu
Maximum Horsepower Rating of Switch – Sizing Based on Motor Type
30A
PS3
B
5
5
10
15
60A
PS6
B
10
10
25
30
Amp Rating of Switch
100A
PS1
B
C
A
15
15
40
20
15
50
40
30
100
50
40
125
200A
PS2
B
40
40
75
100
400A
PS4
B
75
75
150
200
Voltage
208AC-3P
240AC-3P
480AC-3P
600AC-3P
A
5
5
10
15
C
3
5
10
10
A
10
10
30
30
C
10
10
20
25
A
20
20
50
60
C
30
30
75
100
A
75
125
250
250
C
60
75
150
200
Column Sizing Guidelines:
A
Maximum horsepower rating of switch with Class J fuses, light-duty inrush
B
Maximum horsepower rating of switch with Class J fuses, medium-duty inrush
C
Maximum horsepower rating of switch with Class J fuses, heavy-duty or typical elevator cross line start
The above table can be used for estimating switch size for motor loads based upon the motor horsepower. Size the switch so that
the Class J, time-delay fuses are used at a minimum of 150% of motor full load amps or next size up (for light starting duty
applications, Column A). For general applications, excluding wound rotor and DC motors, NEC
®
430-52 allows sizing at 175%
of motor full load amps or the next standard size per NEC 240-6 (Column B). If sizing at 175% will not allow the motor to start,
NEC 430-52 will allow the fuses to be sized up to 225% of motor full load amps or the next size down (Column C).
Note: In sizing the fuses, the motor FLA, is per Table 430-150, not per nameplate information.
Inrush currents of motors may vary, consult motor manufacturer data for correct sizing.
On elevator applications, motor load plus auxiliary loads need to be considered. Follow elevator manufacturer’s
recommendation for correct fuse sizing. For estimation purposes only, Column C can be used as a conservative
approximation.
12-28-98
SB98107
Rev. A
Form No. PS
Page 2 of 4
BIF Doc# 1145
Bussmann
®
Bussmann Power Module Switch
All-In-One Module
Typical Control with Wiring Options
for Fire Safety Interface (Option R1)
Typical Control with Wiring Options for
Fire Safety Interface (Option R2)
Line
PS
Line
Mech. Interlock
Aux. Contact
Shunt Trip
FU1A
FU1A
Line Voltage
Load
Mech. Interlock
Aux. Contact
Shunt Trip
FU1A
Line Voltage
FU1A
Load
100VA CPT
100VA CPT
120V
N
120V
FU1.25A
G
NO F
.A.
1
Key
Test
8
CR 5
CR
4 7
SW. Aux.
Shunt
Trip
CR 2
4
5
6
Remote
Alarm
3
N
FU1.25A
G
A
CR
B
CR 2
4
8
CR 5
4
CR
7
SW. Aux.
Shunt
Trip
5
6
Remote
Alarm
Aux. 1
3
Option “A”
NO
Common
NC
Option “B”
NO
NO
Common
Common
NC
NC
1
Aux. 1
3
9
Aux. 2
6
Option “A”
NO
Common
NC
Option “B”
NO
NO
Common
Common
NC
NC
9
Aux. 2
6
24 Vdc Source
Provided by
Fire Alarm System
N.O.F.A.
3
Key
Test
A
CR
B
7
Legend:
F.A.
– Fire alarm contact 5A remote temperature sensor (maybe multiple F.A. contact locations).
Shunt Trip
– Solenoid for remote trip of switch activated by closing of fire alarm sensor or key test switch.
SW Aux.
– Normally closed contact when switch is closed. Opens as power switch opens.
Relay
– Normally closed (1 NC) and (1 NO) normally opened for remote signal.
G
– Pilot light if required.
Key Test
– Key operated test button.
CPT–
Control power transformer with 2 primary and 1 secondary Class CC fuses.
Option A or B
– Mechanical interlock auxiliary contact 1 NO & 1 NC or 2 NO & 2 NC (5 amp 120 Vac rated).
q
Connection Point (fire safety interface relay).
s
Terminal Block
The only controlled copy of this BIF document is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This
bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice,
to change design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical
information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
12-28-98
SB98107
Rev. A
Form No. PS
Page 3 of 4
BIF Doc# 1145
Bussmann
®
Bussmann Power Module Switch
All-In-One Module
Section 16XXX – Power Module Switch
Elevator – Computer Room – Emergency Systems
Part 1 – General
1.01 Description
A. Work of this section shall conform to the requirements
of the contract documents.
1.02 Section Includes
A. Provide elevator Power Module Switch(es), fuses and
accessories as required and specified on contract
drawings to distribute electrical power to all elevators.
1.03 Related Systems
A. (Reference other sections of the specification which
cover elevator installation)
1.04 Codes
A. All work shall be performed in accordance with the
latest edition of applicable standards, codes and laws.
1. NFPA 70 620-51 A-B, 620-62, 645-10, 700-25
(FPN)
2. Canadian Electric Code Part 1 38-034(3)
3. ANSI/ASME A17.1 102.2(4)
4. BOCA 3006.2.3
1.05 Standards
A. Except as modified by governing codes, all equipment
shall be manufactured in accordance with the latest
[url][color=Red]I wrote the program according to the tutorial, and there is no error or reminder after running it, but every time I burn it, it pops up "Flash download failed-"Cortex-M3". There is no ...
I have no experience in this area. Can the ARM board be connected to a network video server? I want to input a video signal, plug the camera into the video server, and then connect it to the ARM board...
Author: Ma Junpu Wei Zhi Source: Foreign Electronic Components Abstract: Real-time clock (RTC) has been widely used in various electronic products as system synchronization or time mark. With the vari...
The power of EasyPower lies in that we only need a few components to build a reliable power supply system. Because most of them use discrete components, as long as the parameters of the few components...
I saw a tutorial online that said to use Ubuntu to access the Internet, and use network sharing through Windows, but once shared, BBB's IP changes, it seems unsuccessful, can anyone do it? Thank you...
Microchip's PIC18F46J50 is a low-power, high-performance 8-bit USB microcontroller (MCU) using nanoWatt XLP technology. The current in deep sleep mode can be as low as 13nA, the operating voltage i...[Details]
Google's driverless technology is not only an eye-catching technology, but also a subversion of the car usage model.
Those who have watched anti-terrorism films and TV dramas must have been im...[Details]
Analog engineers have traditionally struggled with complexity when designing power supplies that required multiple outputs, dynamic load sharing, hot-swap, or extensive fault-handling capabilities....[Details]
In this article, the high-performance DSP developed by TI can be used as an effective confidentiality method if it is applied to PC encryption cards.
As an effective network security solution,...[Details]
The reason for the light decay of white LEDs: the decline of phosphor performance
So far, the rapid decline of the luminous performance of white light LEDs, especially low-power white light LE...[Details]
Two simple circuits are implemented to drive two LEDs from a battery powered microprocessor.
This design is based on a circuit that uses three resistors and a microprocessor I/O pin as an input h...[Details]
Images in science fiction movies often break through the limits of reality, such as in the movie "Minority Report." Tom Cruise uses a multi-touch screen to browse information. Capacitive sensing te...[Details]
0 Introduction
With the development of society, people pay more and more attention to security work. Monitoring products have been used in various fields instead of being used only in importan...[Details]
Microcalorimetry
is used to determine energy relationships. Microcalorimetry techniques are often required when performing calorimetric experiments with small sample sizes or slow heating rat...[Details]
Aromatic gases are widely present in food, medicine, cosmetics and various daily chemical products, such as snacks, liquor, spices, Chinese herbal medicines, plasters, perfumes, soaps, shampoos, et...[Details]
Contact resistance
is the resistance to current flow through a closed pair of contacts. This type of measurement is performed on devices such as connectors,
relays
, and switches. The...[Details]
Overview
As a remote network communication control method with advanced technology, high reliability, complete functions and reasonable cost, CAN-bus has been widely used in various automa...[Details]
1 Introduction to HART Protocol
HART (Highway Addressable Remote Transducer), an open communication protocol for addressable remote sensor high-speed channels, was launched by Rosemen in the U...[Details]
Xiaomi, a well-known Internet phone in mainland China, won a million-unit order contract from China Unicom on November 20 last year, which made Xiaomi famous in mainland China. In April this year...[Details]
Abstract: Aiming at the needs of coal-rock acoustic emission signal monitoring system, a data acquisition circuit with 24-bit resolution and 16-channel synchronous data acquisition function is desi...[Details]