Technical Data 2032
Effective December, 2015
Supersedes May, 2002
BUSSMANN
SERIES
GLR and HLR
Non-rejecting, fast-acting fuse and inline fuse holders
Catalog symbols:
•
•
•
GLR (Fuse)
HLR (Fuse holder)
HLR-2A and HLR-2L fuse holders
•
UL Recognized, 15A, 300Vac, Guide IZLT2,
File E14853
•
Description:
Fast-acting, non-rejection style inline fuse and
fuse holder system
CSA Certified, 15A, 300Vac, Class 6225-01,
File 47235
Specifications:
Ratings
•
•
A fuseholder
•
CSA Certified, 10A, 300Vac, Class 6225-01,
File 47235
Volts
•
300Vac or less
3/16-15A
10kA
GLR fuse catalog numbers
Fuse (amps)
GLR-3/16
GLR-1-6/10
GLR-1/2
GLR-2
GLR-1
GLR-3
GLR-1-1/2 GLR-4
GLR-5
GLR-6
GLR-7
GLR-8
GLR-9
GLR-10
GLR-12
GLR-15*
•
Amps
•
•
Interrupting rating
•
Agency information
•
* Must be used with the HLR-2A holder rated to 15A.
GLR fuse
•
UL
®
Listed, Std. 248-14, 3/16-15A/300Vac, Guide
JDYX, File E19180
•
HLR fuse holder catalog numbers
Catalog No. Description
Holder with installed linseide
HLR
terminal wire for 3/16 to 12 amp
GLR fuses
Holder with installed lineside and
HLR-2A
loadside terminal wires for 3/16 to
15 amp GLR fuses
Holder with uninstalled lineside
HLR-2L
and loadside terminal wires for
3/16 to 15 amp GLR fuses
Holder without lineside or loadside
A
termianl wires for for 3/16 to 15
amp GLR fuses
CSA
®
Certified, C22.2 No. 248.14, 0-10A/300Vac,
Class 1422-01, File 53787
•
HLR fuse holder
•
UL Recognized, 12A, 300Vac, Guide IZLT2,
File E14853
•
CSA Certified, 12A, 300Vac, Class 6225-01,
File 47235
Technical Data
2032
Effective December 2015
Non-rejecting, fast-acting GLR fuse and HLR in-line fuse holders
Features:
•
Dimensions - in (mm):
GLR fuse
GLR fuse and knob are an integral one-piece unit. There are
no replacement knobs (caps)
Units can be panel mounted with a separate steel clip. For
knockout hole mounting (see dimensions), order catalog
number BK/A-104. For the keyhole punch type hole mounting,
order catalog number 6374 for panels 0.043” to 0.062” thick,
or catalog number 4909 for panels 0.030” to 0.042” thick.
The HLR holder comes with 6 inches of red #18 insulated solid
copper wire attached to the lineside terminal, customer inserts
a #18 insulated solid copper wire into loadside terminal
Order holder catalog number HLR-2A to obtain 6 inches of
black #18 insulated solid copper wire pre-installed in the
loadside terminal
Order catalog number HLR-2L to obtain 6 inches of black #18
insulated solid copper wire packaged loose (uninstalled)
An alternative to the HLR fuse holder is the “A” fuse holder.
The “A” fuse holder comes WITHOUT leads. The customer
inserts #18 insulated solid copper wire into the lineside and
the loadside terminals. The “A” fuse holder has the same body
dimensions, utilizes the same mounting hole, and takes the
same mounting clips as the HLR, HLR-2A and HLR-2L
Do not put tension on the fuse holder’s lineside terminal
•
0.63" (15.9)
HLR fuse holder
0.720” (18.3)
2.250” (57.1)
0.850” (21.6)
Lineside terminal lead
•
•
0.850” 21.6)
C
L
•
Mounting holes
0.870” (22.1)
0.255” (6.5)
Loadside terminal lead
•
0.740” 18.8)
0.410” (10.4)
Knockout hole
0.635” (16.1)
•
Keyhole punch
2
Eaton.com/bussmannseries
Non-rejecting, fast-acting GLR fuse and HLR in-line fuse holders
Technical Data 2032
Effective December 2015
Time-current characteristic curves — average melt
1
1.5
7
10
100
10
Time in seconds
Time in Seconds
1
0.1
0.1
1
10
100
Current in amps
200
0.01
15
2
5
Amp
Amp
Rating
rating
Eaton.com/bussmannseries
3
Technical Data
2032
Effective December 2015
Non-rejecting, fast-acting GLR fuse and HLR in-line fuse holders
The only controlled copy of this data sheet is the electronic read-only version located on the Eaton network drive. All other copies of this
document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical
information that will help the end user with design applications. Eaton reserves the right, without notice, to change design or construction
of any products and to discontinue or limit distribution of any products. Eaton also reserves the right to change or update, without notice,
any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible
applications.
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
Bussmann Division
114 Old State Road
Ellisville, MO 63021
United States
Eaton.com/bussmannseries
© 2015 Eaton
All Rights Reserved
Printed in USA
Publication No. 2032 – BU-MC15051
December 2015
For Eaton’s Bussmann series
product information,
call
1-855-287-7626
or visit:
Eaton.com/bussmannseries
Eaton and Bussmann are valuable
trademarks of Eaton in the US and other
countries. You are not permitted to use the
Eaton trademarks without prior written
consent of Eaton.
CSA is a registered trademark of the
Canadian Standards Group.
UL is a registered trademark of the
Underwriters Laboratories, Inc.
Follow us on social media to get the
latest product and support information.