Description:
22 AWG solid tinned copper conductors, polypropylene insulation, twisted pairs, overall Beldfoil® shield
(100% coverage), 22 AWG solid TC drain wire, PVC jacket.
Physical Characteristics (Overall)
Conductor
AWG:
# Pairs AWG Stranding Conductor Material
38
22
Solid
TC - Tinned Copper
Insulation
Insulation Material:
Insulation Material Wall Thickness (mm)
PP - Polypropylene 0.2032
Insulation Resistance:
1250 megohms/1000 ft. at 500 VDC
Outer Shield
Outer Shield Material:
Outer Shield Trade Name Type Outer Shield Material
Beldfoil®
Coverage (%)
Tape Aluminum Foil-Polyester Tape 100
Outer Shield Drain Wire AWG:
AWG Stranding Drain Wire Conductor Material
22
7x30
TC - Tinned Copper
Outer Jacket
Outer Jacket Material:
Outer Jacket Material
Nom. Wall Thickness (mm)
PVC - Polyvinyl Chloride 1.143
Overall Cable
Overall Nominal Diameter:
15.494 mm
Pair
Pair Color Code Chart:
Number Color
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Blue & White
Orange & White
Green & White
Brown & White
Gray & White
Blue/White & White
Blue/Orange & White
Blue/Green & White
Blue/Brown & White
Blue/Gray & White
Orange/White & White
Orange/Green & White
Orange/Brown & White
Orange/Gray & White
Green/White & White
Page 1 of 3
02-01-2012
Detailed Specifications & Technical Data
METRIC MEASUREMENT VERSION
8752 Multi-Conductor - Audio, Control and Instrumentation Cable
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
Green/Brown & White
Green/Gray & White
Brown/White & White
Brown/Gray & White
Gray/White & White
Blue & Red
Orange & Red
Green & Red
Brown & Red
Gray & Red
Blue/White & Red
Blue/Orange & Red
Blue/Green & Red
Blue/Brown & Red
Blue/Gray & Red
Orange/White & Red
Orange/Green & Red
Orange/Brown & Red
Orange/Gray & Red
Green/White & Red
Green/Brown & Red
Green/Gray & Red
Brown/White & Red
Mechanical Characteristics (Overall)
Operating Temperature Range:
Non-UL Temperature Rating:
Bulk Cable Weight:
Max. Recommended Pulling Tension:
Min. Bend Radius (Install)/Minor Axis:
-20°C To +80°C
80°C
359.251 Kg/Km
2624.440 N
304.800 mm
Applicable Specifications and Agency Compliance (Overall)
Applicable Standards & Environmental Programs
EU CE Mark:
EU Directive 2000/53/EC (ELV):
EU Directive 2002/95/EC (RoHS):
EU RoHS Compliance Date (mm/dd/yyyy):
EU Directive 2002/96/EC (WEEE):
EU Directive 2003/11/EC (BFR):
CA Prop 65 (CJ for Wire & Cable):
MII Order #39 (China RoHS):
Yes
Yes
Yes
01/01/2004
Yes
Yes
Yes
Yes
Flame Test
UL Flame Test:
VW-1
Plenum/Non-Plenum
Plenum (Y/N):
No
Electrical Characteristics (Overall)
Nom. Capacitance Conductor to Shield:
Capacitance (pF/m)
79.7283
Nom. Capacitance Conductor to Conductor:
Capacitance (pF/m)
55.777
Page 2 of 3
02-01-2012
Detailed Specifications & Technical Data
METRIC MEASUREMENT VERSION
8752 Multi-Conductor - Audio, Control and Instrumentation Cable
Nom. Conductor DC Resistance:
DCR @ 20°C (Ohm/km)
52.496
Max. Operating Voltage - UL:
Voltage
200 V RMS
Max. Recommended Current:
Current
1 Amp per conductor @ 25°C
Related Documents:
No related documents are available for this product
Put Ups and Colors:
Item #
8752 0601000
8752 060250
Putup
305 MT
76 MT
Ship Weight
116.120 KG
29.484 KG
Color
CHROME
CHROME
Notes
CD
CD
Item Desc
38 PR #22 PP SHLD PVC
38 PR #22 PP SH PVC
Notes:
C = CRATE REEL PUT-UP.
D = FINAL PUT-UP LENGTH MAY VARY -0% TO +20% FROM LENGTH SHOWN.
Revision Number: 1
© 2012 Belden, Inc
All Rights Reserved.
Revision Date: 05-14-2007
Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications
described herein are subject to error or omission and to change without notice, and the listing of such information and specifications does not
ensure product availability.
Belden provides the information and specifications herein on an "AS IS" basis, with no representations or warranties, whether express,
statutory or implied. In no event will Belden be liable for any damages (including consequential, indirect, incidental, special, punitive, or
exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether in an action under contract,
negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein.
All sales of Belden products are subject to Belden's standard terms and conditions of sale.
Belden believes this product to be in compliance with EU RoHS (Directive 2002/95/EC, 27-Jan-2003). Material manufactured prior to the
compliance date may be in stock at Belden facilities and in our Distributor’s inventory. The information provided in this Product Disclosure, and
the identification of materials listed as reportable or restricted within the Product Disclosure, is correct to the best of Belden’s knowledge,
information, and belief at the date of its publication. The information provided in this Product Disclosure is designed only as a general guide
for the safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. This Product Disclosure is not
to be considered a warranty or quality specification. Regulatory information is for guidance purposes only. Product users are responsible for
determining the applicability of legislation and regulations based on their individual usage of the product.
Belden declares this product to be in compliance with EU LVD (Low Voltage Directive 73/23/EEC), as amended by directive 93/68/EEC.
Page 3 of 3
02-01-2012