3120-F323-H7T1-W02A-14A

Description
2 POLE(S), 14A, 250 V(AC), 50 V(DC), PANEL MOUNT, THERMAL CIRCUIT BREAKER,
CategoryCircuit protection    Circuit protection   
File Size441KB,5 Pages
ManufacturerE-T-A [E-T-A Circuit Breakers]
Download Datasheet Parametric View All

3120-F323-H7T1-W02A-14A Overview

2 POLE(S), 14A, 250 V(AC), 50 V(DC), PANEL MOUNT, THERMAL CIRCUIT BREAKER,

3120-F323-H7T1-W02A-14A Parametric

Parameter NameAttribute value
MakerE-T-A [E-T-A Circuit Breakers]
Reach Compliance Codecompliant
Actuator typeROCKER
body width21 mm
body height33 mm
Body length or diameter54 mm
circuit functionMANUAL ON/OFF
Circuit protection typeTHERMAL CIRCUIT BREAKER
Environmental characteristicsCORROSSION RESISTANT
Installation featuresPANEL MOUNT
Number of poles2
Maximum operating temperature60 °C
Minimum operating temperature-30 °C
physical size54mm x 21mm x 33mm
Rated breaking capacity140 A
Rated current14 A
Rated voltage (AC)250 V
Rated voltage (DC)50 V
GuidelineCCC; CSA; UL; VDE
surface mountNO
Terminal shapeQUICK CONNECT
Thermal Overcurrent Circuit Breaker 3120-F...
Description
An extremely versatile range of rocker switch/thermal circuit breakers
(S-type TO CBE to EN 60934 with trip free mechanism) offering the choice
of single pole, double pole with single pole protection, and double pole
with protection on both poles. Designed for snap-in panel mounting with
versions available for three different panel cut-out sizes. Illumination is
optional and there is a range of colours and markings for the rocker.
Add on modules:
Under voltage release coil (for double pole versions only).
Magnetic trip coil for short circuit protection.
Magnetic trip coil for remote relay trip.
Auxiliary contacts for status signalling.
Approved to CBE standard EN 60934 (IEC 60934).
Meets the requirements regarding fire resistance of EN 60335-1 : 2007-02
Safety of household and similar electrical appliances.
3120-F3...F5
Typical applications
Technical data
Motors, transformers, solenoids, extra low voltage wiring systems, office
machines, electro-medical equipment, power supplies, communications
systems, medical equipment to EN 60601.
Standard current ratings and typical internal resistance values
Current rating
(A)
0.1
0.2
0.3
0.4
0.5
0.6
0.8
1
1.2
1.5
2
2.5
3
3.5
Internal
resistance
per pole (Ω)
94
24
12
5.30
4.20
2.90
1.50
0.9
0.80
0.45
0.27
0.0785
0.0595
0.0565
Current rating
(A)
4
4.5
5
6
7
8
10
12
14
15
16
18
20
Internal
resistance
per pole (Ω)
0.0435
0.0435
0.0325
0.0215
0.0165
0.0165
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
Dielectric strength
(IEC 60664 and 60664A)
operating area
between poles (2-pole)
Insulation resistance
Interrupting capacity I
cn
3120-F7
2
For further details please see chapter: Technical Information
Voltage rating
AC 240 V; DC 50 V
(AC 415 V to special order)
(UL: AC 250 V; DC 50 V)
Current ratings
0.1...20 A
(up to 30 A to special order, single pole only)
Typical life
AC 240 V:
DC 50 V:
DC 28 V:
AC 415 V:
AC 240 V:
0.1...20 A
0.1...4 A
4.5...16 A
0.1...20 A
0.1...16 A
0.1...16 A
17...20 A
DC 50 V:
0.1...16 A
17...20 A
Ambient temperature
Insulation co-ordination
(IEC 60664 and 60664 A
1-pole
30,000 operations at 1 x I
N
, inductive
30,000 operations at 1 x I
N
, inductive
30,000 operations at 1 x I
N
, resistive
30,000 operations at 1 x I
N
, inductive
2-pole
10,000 operations at 1 x I
N
, inductive
50,000 operations at 1 x I
N
, inductive
30,000 operations at 1 x I
N
, inductive
50,000 operations at 1 x I
N
, inductive
10,000 operations at 1 x I
N
, inductive
-30...+60 °C (-22...+140 °F)
rated impulse
pollution
withstand voltage
degree
2.5 kV
2
reinforced insulation in operating area
Illumination voltage/power consumption
operating voltage
12 V DC
24 V DC
115 V AC
230 V AC
power consumption
Y+R
2 mA
2 mA
0.9 mA
0.9 mA
G
3.5 mA
3.5 mA
2.8 mA
2.8 mA
test voltage
AC 3,000 V
AC 1,500 V
> 100 MΩ (DC 500 V)
0.1...2 A 10 x I
N
2.5...20 A 250 A 2-pole, or 150 A 1-pole
Interrupting capacity (UL 1077)
I
N
1, 2-pole
1, 2-pole
Degree of protection
(IEC 60529/DIN 40050)
Vibration
0.1...20 A
0.1...20 A
U
N
AC 250 V
DC 50 V
I
nc
5000 A
1000 A
Approvals
Authority
VDE (EN 60934)
Voltage ratings
AC 240 V; DC 28 V
DC 50 V
DC 50 V
AC 250 V; DC 50 V
AC 250 V; DC 50 V
Current ratings
0.1...20 A
0.1...20 A
2-pole
0.1...10 A
1-pole
0.1...20 A
0.1...20 A
Shock
Corrosion
Humidity
Mass
UL, CSA
CCC
operating area IP40
(IP54 with water splash protection)
terminal area IP00
8 g (57-500 Hz), ± 0.61 mm (10-57 Hz)
to IEC 60068-2-6, test Fc
10 frequency cycles/axis
30 g (11 ms)
to IEC 60068-2-27, test Ea
96 hours at 5 % salt mist,
to IEC 60068-2-11, test Ka
240 hours at 95 % RH,
to IEC 60068-2-78, test Cab
approx. 33 g (double pole)
approx. 27 g (single pole)
Issue D
www.e-t-a.de
2
- 67
【Keysight Essay Call】Learn to Use Digital Oscilloscopes in the "Thanksgiving Month" Live Broadcast
[i=s]This post was last edited by xunke on 2017-4-2 07:48[/i] [align=left][align=left] Due to limited conditions, I have never used a Keysight oscilloscope. In order to see if I could win a prize, I w...
xunke Test/Measurement
Analysis of installation techniques of magnetic flap level gauge for high liquid level tank
Magnetic flap level gauge is also called magnetic level gauge, magnetic column level gauge, magnetic float level gauge. Its working principle is to use the principle of magnetic coupling. It is one of...
cfybhd Sensor
Good Samaritan, where are you, urgent help!!
First of all, the signal is a pulse signal. Secondly, the microcontroller used is MSP430F425.Design purpose: Display speed and mileage, overspeed warning alarm.Please help me solve this problem! Time ...
小明同学 Microcontroller MCU
The difference and connection between ucos_III semaphores and task semaphores
I would like to ask the experts: Question 1: What is the difference between semaphores and task semaphores? Question 2: Do the creation, sending and waiting of task semaphores have to be done within a...
liuchang--- Real-time operating system RTOS
PCB layout design review element layout DFM requirements
1 The preferred process route has been determined, and all components have been placed on the PCB. 2 The origin of the coordinate system is the intersection of the left and lower extension lines of th...
ESD技术咨询 PCB Design
【LAUNCHXL-CC1350-4】- 0: Unboxing Post
[i=s]This post was last edited by MianQi on 2021-6-7 17:27[/i]I was attracted by the 2.4G+433M dual-band combination of TI's product and applied to participate in the evaluation activity. Speaking of ...
MianQi RF/Wirelessly

EEWorld
subscription
account

EEWorld
service
account

Automotive
development
circle

Robot
development
community

Index Files: 1791  2298  1673  1487  580  37  47  34  30  12 
Datasheet   0 1 2 3 4 5 6 7 8 9 A B C D E F G H I J K L M N O P Q R S T U V W X Y Z
Room 1530, 15th Floor, Building B, No. 18 Zhongguancun Street, Haidian District, Beijing Telephone: (010) 82350740 Postal Code: 100190
Copyright © 2005-2026 EEWORLD.com.cn, Inc. All rights reserved 京ICP证060456号 京ICP备10001474号-1 电信业务审批[2006]字第258号函 京公网安备 11010802033920号