WKN 16 DS
Feed through terminal block
Double screw connection
Feed through terminal block
with double screw connection,
for mounting on TS 32 and 35,
nominal cross section 16 mm²;
width 10 mm, color gray
selos
selos
Max Voltage
Amperage
Width
Approvals
Type
Wire Size
WKN 16 DS
16 - 4 AWG
600 V
65 A
10 mm
IVB WKN 16
600 V
65 A
Part Number
Part Number
Part Number
Part Number
Feed-through block
57.016.5055.0
07.313.2255.0
Z7.283.2227.0
Z7.283.2327.0
Z7.283.2427.0
Z7.283.2527.0
Z7.283.2627.0
Z7.283.2727.0
Z7.283.2827.0
Z7.283.2927.0
Z7.283.3027.0
Z7.2833127.0
Z7.283.3227.0
Z7.283.6027.0
Z4.242.5053.0
34.210.0236.0
End plate
Cross connector
Cross connector
Cross connector
Cross connector
Cross connector
Cross connector
Cross connector
Cross connector
Cross connector
Cross connector
Cross connector
Cross connector
40 pole, uninsulated
2 pole, insulated
3 pole, insulated
4 pole, insulated
5 pole, insulated
6 pole, insulated
7 pole, insulated
8 pole, insulated
9 pole, insulated
10 pole, insulated
11 pole, insulated
12 pole, insulated
Blank, 110 tags, 5 mm wide
Custom Marked,5 tags
5 mm width, every other tag
Marking tags
Marking tags
Subject to change without notice
www.wieland-electric.ca
selos
selos
WKN 16 DS
Technical Data
Electrical Data
CSA
Rated Voltage
Rated Current
Solid / stranded wire
Fine stranded wire
Stripping Length
EN 60947-7-1
Rated Voltage
Rated Current
Nominal cross section
Solid / stranded wire
Fine stranded wire
Stripping Length
Cross connector
600 V
65 A
16 AWG - 4 AWG
16 AWG - 6 AWG
18 mm
800V / 8kV / 3
76 A
16 mm²
1.5 - 25 mm²
1.5 - 16 mm²
18 mm
Alternating jumper position is required
for adjacent blocks with different
potentials. End plates must be used
for cross connectors so that the rated
voltage is maintained
Mechanical Data
Type of Connection
Width
Flammability Rating
Color
Protection class
Insulating housing
Screw type connection
10 mm
UL 94 - V0
grey
IP 20
PA
Dimensions
Subject to change without notice