Extract from the online
catalog
MINI-PS-100-240AC/24DC/1.3
Order No.: 2866446
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2866446
DIN rail power supply unit 24 V DC/1.3 A, primary switched-mode
Product notes
Commercial data
EAN
Pack
Customs tariff
Weight/Piece
Catalog page information
4046356073905
1 pcs.
85044081
0.255 KG
Page 576 (IF-2009)
http://
www.download.phoenixcontact.com
Please note that the data given
here has been taken from the
online catalog. For comprehensive
information and data, please refer
to the user documentation. The
General Terms and Conditions of
Use apply to Internet downloads.
WEEE/RoHS-compliant since:
08/12/2008
Product description
MINI POWER is the extremely slim power supply unit with constructional widths of 22.5 mm, 45 mm and 67.5 mm.
In addition to a 24 V version with output currents of 1.3 A, 2 A and 4 A, special voltages with 5 V/3 A and ±15 V/1 A and
10 V...15 V/2 A and 8 A are also available.
A reliable starting of complex loads is ensured by a power reserve of up to 100% – the POWER BOOST.
The high operational reliability is thus dependably guaranteed in complex global networks as well. MINI POWER also
functions in applications where static voltage dips, transient failures of the supply voltage or phase failure are to be
expected.
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Page 1 / 7
Mar 15, 2010
MINI-PS-100-240AC/24DC/1.3
Order No.: 2866446
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2866446
Generously dimensioned capacitors guarantee a mains buffering of more than 20 ms under full load.
Worldwide use is realized by the consistent implementation of a wide-range input.
In this way, your whole system can be tested at any manufacturing location in the world and be delivered to global
destinations without switching over the input voltage, often a source of faults. This saves storage costs and reduces the
logistical work.
An international approval package including UL 60950 for information technology equipment and UL 508 for industrial
regulating devices pave the way for worldwide applications.
Technical data
Input data
Nominal input voltage
AC input voltage range
DC input voltage range
AC frequency range
DC frequency range
Current consumption
Inrush surge current
Power failure bypass
Input fuse
Recommended backup fuse
100 V AC ... 240 V AC
85 V AC ... 264 V AC
90 V DC ... 350 V DC
45 Hz ... 65 Hz
0 Hz
Approx. 0.65 A (120 V AC)
0.25 A (230 V AC)
< 15 A (< 0.6 A s)
> 20 ms (120 V AC)
> 110 ms (230 V AC)
1.25 A (slow-blow, internal)
6 A (characteristic B)
10 A (characteristic B)
16 A (characteristic B)
Name of protection
Protective circuit/component
Output data
Nominal output voltage
Setting range of the output voltage
Output current
Derating
Connection in parallel
Connection in series
Starting delay with capacitive load
24 V DC ±1%
22.5 V DC ... 28.5 V DC (> 24 V constant capacity)
1.3 A (-25 °C ... 60 °C)
1.6 A (with POWER BOOST, -25°C ... 40°C permanent)
From +60°C to 70°C: 2.5% per Kelvin
Yes, for redundancy and increased capacity
No
(Unrestricted)
Transient surge protection
Varistor
2
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Page 2 / 7
Mar 15, 2010
MINI-PS-100-240AC/24DC/1.3
Order No.: 2866446
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2866446
Max. capacitive load
Current limitation
Control deviation
Unlimited
Approx. 5 A (for short circuit)
< 1 % (change in load, static 10% ... 90%)
< 3 % (change in load, dynamic 10% ... 90%)
< 0.1 % (change in input voltage ±10%)
Residual ripple
Peak switching voltages nominal load
Maximum power dissipation idling
Power loss nominal load max.
General data
Width
Height
Depth
Weight
Operating voltage display
Efficiency
Insulation voltage input/output
Degree of protection
Class of protection
MTBF
Ambient temperature (operation)
Ambient temperature (storage/transport)
Max. permissible relative humidity (operation)
Mounting position
Assembly instructions
Electromagnetic compatibility
Immunity to interference
Standard – Electrical equipment of machines
Standard - Safety of transformers
Standard - Electrical safety
Standard – Electronic equipment for use in
electrical power installations and their assembly
into electrical power installations
< 20 mV
PP
< 50 mV
PP
0.9 W
4.5 W
22.5 mm
99 mm
107 mm
0.2 kg
LED green
> 85 % (At 230 V AC and nominal values)
3 kV (routine test)
4 kV (type test)
IP20
II (in an enclosed control cabinet)
> 500 000 h in acc. with IEC 61709 (SN 29500)
-25 °C ... 70 °C (> 60 °C derating)
-40 °C ... 85 °C
95 % (at 25 °C, no condensation)
Horizontal DIN rail NS 35, EN 60715
Can be aligned: Horizontal 0 cm, vertical 5 cm
Conformance with EMC guideline 2004/108/EC and for low-
voltage guideline 2006/95/EC
EN 61000-6-2:2005
EN 60204
EN 61558-2-17
EN 60950/VDE 0805 (SELV)
EN 50178/VDE 0160 (PELV)
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Page 3 / 7
Mar 15, 2010
MINI-PS-100-240AC/24DC/1.3
Order No.: 2866446
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2866446
Standard – Safety extra-low voltage
Standard - Safe isolation
Standard – Protection against shock currents,
basic requirements for protective separation in
electrical equipment
Standard – Limitation of mains harmonic currents
UL approvals
EN 60950 (SELV)
EN 60204 (PELV)
DIN VDE 0100-410
DIN VDE 0106-1010
DIN VDE 0106-101
EN 61000-3-2
UL/C-UL listed UL 508
UL/C-UL Recognized UL 60950
UL/C-UL Listed UL 1604 Class I, Division 2, Groups A, B, C, D
NEC Class 2 as per UL 1310
Surge voltage category
Connection data, input
Type of connection
Conductor cross section solid min.
Conductor cross section solid max.
Conductor cross section stranded min.
Conductor cross section stranded max.
Conductor cross section AWG/kcmil min.
Conductor cross section AWG/kcmil max
Stripping length
Screw thread
Connection data, output
Type of connection
Conductor cross section solid min.
Conductor cross section solid max.
Conductor cross section stranded min.
Conductor cross section stranded max.
Conductor cross section AWG/kcmil min.
Conductor cross section AWG/kcmil max
Stripping length
Signaling
Output name
Output description
III
Pluggable screw connection
0.2 mm²
2.5 mm²
0.2 mm²
2.5 mm²
24
12
7 mm
M3
Pluggable screw connection
0.2 mm²
2.5 mm²
0.2 mm²
2.5 mm²
24
12
7 mm
DC OK active
U
OUT
> 21.5 V: High signal
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Page 4 / 7
Mar 15, 2010
MINI-PS-100-240AC/24DC/1.3
Order No.: 2866446
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2866446
Maximum switching voltage
Output voltage
Continuous load current
Status display
Note on status display
Conductor cross section solid min.
Conductor cross section solid max.
Conductor cross section stranded min.
Conductor cross section stranded max.
Conductor cross section AWG/kcmil min.
Conductor cross section AWG/kcmil max
Tightening torque, min
Tightening torque max
Screw thread
Certificates / Approvals
≤ 24 V
+ 24 V DC (signal)
≤ 20 mA
"DC OK" LED green
U
OUT
> 21.5 V: LED lights up
0.2 mm²
2.5 mm²
0.2 mm²
2.5 mm²
24
12
0.5 Nm
0.6 Nm
M3
Certification
Certification Ex:
Diagrams/Drawings
Block diagram
CUL, CUL Listed, GOST, UL, UL Listed
CUL-EX LIS, UL-EX LIS
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Page 5 / 7
Mar 15, 2010