The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
1 phase
200...240 V - 15...10 %
170...264 V
50...60 Hz - 5...5 %
47.5...63 Hz
0.75 kW 200...240 V
1 hp 200...240 V
Complementary
Line current
Apparent power
Prospective line Isc
Nominal output current
Maximum transient current
Speed drive output frequency
Nominal switching frequency
Switching frequency
Speed range
Speed accuracy
Torque accuracy
Transient overtorque
Braking torque
Asynchronous motor control profile
8.5 A 240 V 1 phase 0.75 kW 1 hp
10.1 A 200 V 1 phase 0.75 kW 1 hp
2 kVA 240 V 1 phase 0.75 kW 1 hp
<= 1 kA 1 phase
4.8 A 4 kHz 240 V 0.75 kW 1 hp
7.2 A 60 s 0.75 kW 1 hp
0.5...599 Hz
4 kHz
2...16 kHz adjustable
1...100 asynchronous motor in open-loop mode
+/- 10 % of nominal slip 0.2 Tn to Tn
+/- 15 %
170...200 %
< 170 % with braking resistor
Voltage/Frequency ratio, 2 points
Voltage/Frequency ratio, 5 points
Flux vector control without sensor - Energy Saving, NoLoad law
Flux vector control without sensor, standard
Voltage/Frequency ratio - Energy Saving, quadratic U/f
Vector control without sensor
Adjustable PID regulator
Automatic whatever the load
Not available in voltage/frequency ratio (2 or 5 points)
Adjustable 0...300 %
1 LED red drive fault
1 LED red CANopen error
1 LED green CANopen run
1 LED red drive voltage
<= power supply voltage
Synchronous motor control profile
Regulation loop
Motor slip compensation
Local signalling
Output voltage
Jun 15, 2015
1
Noise level
Insulation
Electrical connection
43 dB 86/188/EEC
Electrical between power and control
Screw terminal 1.5...4 mm² AWG 14...AWG 10 power supply