3−line filters
for converters and power electronics
520/300 V, 50/60 Hz, 10...100 A, 50
°C
Ordering code:
Date:
Version:
B84143A*R106
2009−09−10
06
©
EPCOS AG 2009. Reproduction, publication and dissemination of this publication, enclosures
hereto and the information contained therein without EPCOS’ prior express consent is prohibited.
Page 1 of 11
3−line filters
for converters and power electronics
B84143A*R106
Construction
S
3−line filter
S
Metal case
Features
S
High insertion loss
S
Optimized leakage current
S
Easy to install
S
Low weight
S
Compact design
S
Degree of protection IP 20
1)
S
Optimized for long motor cable
and operation under full load
S
ENEC10, UL und cUL approval
c
us
Applications
S
Frequency converters for motor drives, e.g.
− elevators
− pumps
− conveyor systems
− HVAC systems (heating, ventilation and air conditioning)
S
Power supplies
S
Textile machines, packaging machines, machine−tools
Terminals
S
Line side: finger−save terminal blocks
S
Load side: finger−save terminal blocks
Marking
S
Marking on component:
manufacturer’s logo, ordering code, rated voltage, rated current,
rated temperature, climatic category, date code
S
Minimum marking on packaging: maufacturer’s logo, ordering code,
date code, quantity
1
)
To IEC 60529:2001
Please read and
Cautions and warnings
and
Important notes
at the end of this document.
Page 2 of 11
B84143A*R106−06−7659
3−line filters
for converters and power electronics
B84143A*R106
Typical circuit diagram
LINE
L1
L2
L3
LOAD
L1’
L2’
L3’
PE
PE
Technical data and measuring conditions
Rated voltage
Rated frequency
Test voltage line to line for 2 s
Test voltage line to case for 2 s
Rated temperature
Overload capability (thermal)
for 3 min per hour or
for 30 s per hour
Climatic category (IEC 60068−1)
U
R
f
R
U
test
U
test
T
R
520/300
50/60
2236
2720
50
1.5 x I
R
2.5 x I
R
25/100/21
V AC
Hz
V DC
V DC
°C
Please read and
Cautions and warnings
and
Important notes
at the end of this document.
Page 3 of 11
B84143A*R106−06−7659
3−line filters
for converters and power electronics
B84143A*R106
Characteristics and ordering codes
I
R
Terminal
cross
section
I
leak 2)
R
typ
Approx.
weight
kg
0,4
0,6
0,9
1,4
1,9
2,4
2,9
Ordering code
Approvals
A
10
20
35
50
65
80
100
mm
2
4
4
10
25
25
50
50
mA
14,3
14,3
15,8
15,8
15,8
15,8
15,8
mΩ
5,5
3,3
1,7
1,1
0,94
0,60
0,48
B84143A0010R106
B84143A0020R106
B84143A0035R106
B84143A0050R106
B84143A0065R106
B84143A0080R106
B84143A0100R106
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
X = approval granted
2) 3 phase operation in TN network; maximum voltage = U
R
; frequency = 50 Hz without harmonics; tolerance of capacitors −20%/ 0%; worst
case positioning of the components; unbalance 2% according EN 50160:2000.
Please read and
Cautions and warnings
and
Important notes
at the end of this document.
Page 4 of 11
B84143A*R106−06−7659
3−line filters
for converters and power electronics
B84143A*R106
Dimensional drawings
B84143A0010R106, B84143A0020R106 (10A and 20A)
B84143A0035R106 (35A)
Please read and
Cautions and warnings
and
Important notes
at the end of this document.
Page 5 of 11
B84143A*R106−06−7659