Detailed Specifications & Technical Data
ENGLISH MEASUREMENT VERSION
B9C018 Fiber - Breakout Cable - Plenum
For more Information
please call
1-800-Belden1
Description:
FiberExpress Optical Fiber Breakout Cables are designed for low to medium fiber count in-building,
harsh-environment installations. Breakout or fanout cables offer a high degree of flexibility for backbone
and horizontal applications.
Physical Characteristics (Overall)
Fiber Type:
Number of Fibers:
Buffer Tube Material:
Breakout Element Diameter:
50 Micron (OM3)
12
Thermoplastic
.0787
Inner Jacket
Inner Jacket Color Code Chart:
Number Color
1
2
3
4
5
6
7
8
9
10
11
12
Blue
Orange
Green
Brown
Gray
White
Red
Black
Yellow
Violet
Pink
Aqua
Outer Jacket
Outer Jacket Material:
Outer Jacket Material
PVC - Polyvinyl Chloride
Strength Member
Strength Member Material:
Aramid Yarn
Overall Cable
Overall Nominal Diameter:
0.450 in.
Mechanical Characteristics (Overall)
Storage Temperature Range:
Installation Temperature Range:
Operating Temperature Range:
Bulk Cable Weight:
Min. Bend Radius/Minor Axis:
Min. Bend Radius for Long Term Application:
Max. Load for Installation:
-40°C To +75°C
0°C To +60°C
0°C To +70°C
93 lbs/1000 ft.
6.800 in.
4.500 in.
100 lbs.
Page 1 of 3
12-05-2012
Detailed Specifications & Technical Data
ENGLISH MEASUREMENT VERSION
B9C018 Fiber - Breakout Cable - Plenum
Max. Load for Long Term Application:
30 lbs.
Applicable Specifications and Agency Compliance (Overall)
Applicable Standards & Environmental Programs
NEC/(UL) Specification:
CEC/C(UL) Specification:
EU CE Mark:
EU Directive 2000/53/EC (ELV):
EU Directive 2002/95/EC (RoHS):
EU RoHS Compliance Date (mm/dd/yyyy):
EU Directive 2002/96/EC (WEEE):
EU Directive 2003/11/EC (BFR):
CA Prop 65 (CJ for Wire & Cable):
MII Order #39 (China RoHS):
OFNP
OFNP
Yes
Yes
Yes
12/17/2008
Yes
Yes
Yes
Yes
Flame Test
UL Flame Test:
CSA Flame Test:
UL910 Steiner Tunnel
FT6
Suitability
Suitability - Indoor:
Suitability - Outdoor:
Suitability - Aerial:
Suitability - Burial:
Sunlight Resistance:
Yes
No
No
No
No
Plenum/Non-Plenum
Plenum (Y/N):
Yes
Optical Characteristics (Overall)
Maximum Attenuation @ 850nm:
Maximum Attenuation @ 1300nm:
Minimum Bandwidth @ 850nm:
Minimum Bandwidth @ 1300nm:
Maximum Gigabit Ethernet Length @ 850nm:
Maximum Gigabit Ethernet Length @ 1300nm:
Fiber Coding MLT EMEA:
Fiber/Tube No. Color
1
2
3
4
5
6
7
8
9
10
11
12
Blue
Orange
Green
Brown
Slate
White
Red
Black
Yellow
Violet
Rose
Aqua
3.0 dB/km
1.2 dB/km
1500 MHz*km
500 MHz*km
1000 meters
550 meters
Related Documents:
Page 2 of 3
12-05-2012
Detailed Specifications & Technical Data
ENGLISH MEASUREMENT VERSION
B9C018 Fiber - Breakout Cable - Plenum
Breakout Cable.pdf
- Breakout Cable technical information.
Put Ups and Colors:
Item #
B9C018
Putup
1 FT
Ship Weight
0.000
Color
AQUA
Notes
Item Desc
BO2.0 12F OM3 OFNP TB
Revision Number: 3
© 2012 Belden, Inc
All Rights Reserved.
Revision Date: 12-05-2012
Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications
described herein are subject to error or omission and to change without notice, and the listing of such information and specifications does not
ensure product availability.
Belden provides the information and specifications herein on an "AS IS" basis, with no representations or warranties, whether express,
statutory or implied. In no event will Belden be liable for any damages (including consequential, indirect, incidental, special, punitive, or
exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether in an action under contract,
negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein.
All sales of Belden products are subject to Belden's standard terms and conditions of sale.
Belden believes this product to be in compliance with EU RoHS (Directive 2002/95/EC, 27-Jan-2003). Material manufactured prior to the
compliance date may be in stock at Belden facilities and in our Distributor’s inventory. The information provided in this Product Disclosure, and
the identification of materials listed as reportable or restricted within the Product Disclosure, is correct to the best of Belden’s knowledge,
information, and belief at the date of its publication. The information provided in this Product Disclosure is designed only as a general guide
for the safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. This Product Disclosure is not
to be considered a warranty or quality specification. Regulatory information is for guidance purposes only. Product users are responsible for
determining the applicability of legislation and regulations based on their individual usage of the product.
Belden declares this product to be in compliance with EU LVD (Low Voltage Directive 73/23/EEC), as amended by directive 93/68/EEC.
Page 3 of 3
12-05-2012