4
Industrial Control Transformers
International Series Control Transformers: 50 - 750 VA
Electromagnetic control components demand inrush
currents up to 10 times the transformers nominal rating
without sacrificing secondary voltage stability beyond
practical limits. The International series transformers fully
comply with IEC and NEMA standards and are available
with IEC touchproof covers (IP20).
Features
• Epoxy encapsulated for cooler operation
• Interleaved copper windings to reduce impedence
• 50/60 Hz
• 55°C Rise, 105°C insulation system for harsh,
heavy duty applications
• Exceeds IEC, NEMA, ANSI, NMTBA, JIC and
automotive standards
Certifications and Compliances
•
Listed: E77014
-
UL 506
-
CSA C22.2 No. 66
•
- IEC 61558-1, IEC 61558-2-2
• RoHS Compliant
E77014
Catalog Number
Field iNstalled optioNs
desCriptioNs
Related Products
• DIN Rail Power Supplies
• 63 Series Power Conditioners
• Surge Protective Devices
diN Circuit breaker mounting
sbediN
Field installed IEC fuse holder adaptor
kit
terminal Covers (two Covers per Kit)
ip20
Field installed primary and secondary
IEC Touch Proof Cover Kit.
190
Contact
Technical Services
at
(800) 377-4384
with any questions.
Visit our website at www.solahd.com.
Industrial Control Transformers
Selection Tables: International Series
group 1 – 208/240/415 Volt primary, 120/24 secondary, 50/60 Hz
200/230/400 Volt primary, 115/23 secondary, 50/60 Hz
Continuous instantaneous
Va
Va *
50
100
150
250
500
105
230
420
675
1600
Catalog Height Width depth
mtg Width
mtg depth
Number in (mm) in (mm) in (mm) W1 / W2 - in (mm) d1 / d2 - in (mm)
e050tC
e100tC
e150tC
2.96
(75.2)
3.39
4.36
(86.1) (110.7)
2.81 / 2.50
(71.4 / 63.5)
2.56 / 2.87
(65.0 / 72.9)
3.74 / 3.12
(95.0 / 79.3)
4.38 / 3.75
(111.3 / 95.3)
5.32 / 4.37
(135.1 / 111.0)
2.10 / N/A
(53.3 / N/A)
2.87 / 3.18
(72.9 / 80.8)
3.29 / 3.61
(83.6 / 91.7)
3.54 / N/A
(89.9 / N/A)
4.25 / 5.75
(108.0 / 146.1)
slot size
s1/s2 - in (mm)
.20 x .50 / .20 x .50
(5.08 x 12.7 / 5.08 x 12.7)
.20 x .65 / .20 x .33
(5.08 x 16.5 / 5.08 x 8.4)
.20 x .65 / .20 x .33
(5.08 x 16.5 / 5.08 x 8.4)
approx.
ship Weight
lbs (kg)
4.0 (1.82)
8.0 (3.67)
11.0 (5.00)
4
3.89
4.50
4.48
(98.8) (114.3) (113.8)
3.89
4.50
5.21
(98.8) (114.3) (132.3)
4.53
5.25
5.07
e250tC
(115.1) (133.4) (128.8)
5.56
6.38
6.93
e500tC
(141.2) (162.1) (176.0)
.31 x .85 / .31 x .85
15.0 (6.82)
(7.87 x 21.59 / 7.87 x 21.59
.31 x .03 / .31 x .85
30.0 (13.64)
(7.87 x .85 / 7.87 x 21.59)
* At 50% PF (Power Factor), 95% Nominal Secondary Voltage.
group 2 – 208/240/415 Volt primary, 24 Volt secondary, 50/60 Hz
277/480 Volt primary, 24 Volt secondary, 60 Hz
200/230/400 Volt primary, 24 Volt secondary, 50/60 Hz
220/380 Volt primary, 23 Volt secondary, 50/60 Hz
Continuous instantaneous
Va
Va*
50
100
150
250
500
105
230
420
675
1600
Catalog Height Width depth
Number in (mm) in (mm) in (mm)
e050te
e100te
e150te
e250te
e500te
2.96
(75.2)
3.39
4.36
(86.1) (110.7)
mtg Width
W1 / W2
in (mm)
2.81 / 2.50
(71.4 / 63.5)
2.56 / 2.87
(65.0 / 72.9)
3.74 / 3.12
(95.0 / 79.3)
4.38 / 3.75
(111.3 / 95.3)
5.32 / 4.37
(135.1 / 111.0)
mtg depth
d1 / d2
in (mm)
2.10 / N/A
(53.3 / N/A)
2.87 / 3.18
(72.9 / 80.8)
3.29 / 3.61
(83.6 / 91.7)
3.54 / N/A
(89.9 / N/A)
4.25 / 5.75
(108.0 / 146.1)
slot size
s1/s2 - in (mm)
.20 x .50 / .20 x .50
(5.08 x 12.7 / 5.08 x 12.7)
.20 x .03 / .20 x .01
(5.08 x .65 / 5.08 x .33)
.20 x .03 / .20 x .01
(5.08 x .65 / 5.08 x .33)
.30 x .71 / .30 x .71
(7.87 x 18.0 / 7.87 x 18.0)
approx.
ship Weight
lbs (kg)
4.0 (1.82)
8.0 (3.67)
11.0 (5.00)
15.0 (6.82)
3.89
4.50
4.48
(98.8) (114.3) (113.8)
3.89
4.50
5.21
(98.8) (114.3) (132.3)
4.53
5.25
5.07
(115.1) (133.4) (128.8)
5.56
6.38
6.93
(141.2) (162.1) (176.0)
.30 x .85 / .30 x .85
30.0 (13.64)
(7.87 x 21.6 / 7.87 x 21.6)
Note: Fuse holders are not available for these voltage configurations.
* At 50% PF (Power Factor), 95% Nominal Secondary Voltage.
design style
mounting dimensions
profile
top View
Contact
Technical Services
at
(800) 377-4384
with any questions.
Visit our website at www.solahd.com.
191
4
Continuous instantaneous
Va
Va **
50
100
150
250
500
750
93
205
390
630
1200
2290
Industrial Control Transformers
Selection Tables: International Series -
continued
group 3 – 208/240/415/480/600 * Volt primary, 120 Volt secondary, 50/60 Hz
200/230/400/460/575 * Volt primary, 115 Volt secondary, 50/60 Hz
220/277 */380 Volt primary, 110 Volt secondary, 50/60 Hz
Catalog Height Width depth
mtg Width
mtg depth
Number in (mm) in (mm) in (mm) W1 / W2 - in (mm) d1 / d2 - in (mm)
e050tF
e100tF
e150tF
e250tF
e500tF
e750tF
2.96
(75.2)
3.39
4.36
(86.1) (110.7)
2.81 / 2.50
(71.4 / 63.5)
3.74 / 3.12
(95.0 / 79.3)
3.74 / 3.12
(95.0 / 79.3)
4.38 / 3.75
(111.3 / 95.3)
5.32 / 4.37
(135.1 / 111.0)
5.32 / 4.37
(135.1 / 111.0)
2.10 / N/A
(53.3 / N/A)
2.56 / 2.87
(65.0 / 73.0)
3.29 / 3.61
(83.6 / 91.7)
3.54 / N/A
(89.9 / N/A)
4.25 / 5.75
(108.0 / 146.1)
4.68 / 6.18
(118.9 / 157.0)
slot size
s1/s2 - in (mm)
.20 x .50 / .20 x .50
(5.08 x 12.7 / 5.08 x 12.7)
.20 x .65 / .20 x .33
(5.08 x 16.5 / 5.08 x 8.38)
.20 x .65 / .20 x .33
(5.08 x 16.5 / 5.08 x 8.38)
.31 x .71 / .31 x .71
(7.9 x 18.0 / 7.9 x 18.0)
.31 x .85 / .31 x .85
(7.9 x 21.6 / 7.9 x 21.6)
.31 x .85 / .31 x .85
(7.9 x 21.6 / 7.9 x 21.6)
approx.
ship Weight
lbs (kg)
4.0 (1.82)
H1 H3
H4
200-277
H2 H4
X4
120 (415/208)
115 (400/200)
110 (380)
3.89
4.50
4.48
(98.8) (114.3) (113.8)
3.89
4.50
5.21
(98.8) (114.3) (132.3)
4.53
5.25
5.07
(115.1) (133.4) (128.8)
5.56
6.38
6.93
(141.2) (162.1) (176.0)
5.56
6.38
7.36
(141.2) (162.1) (187.0)
8.0 (3.67)
11.0 (5.00)
15.0 (6.82)
30.0 (13.64)
34.0 (15.45)
H1 H3
X3
H2
H3
380-600
H2 H4
120 (480/240)
115 (460/230)
110 (220)
X2
120 (600)
115 (575)
110 (277)
60 Hz
Only
H1
50/60 Hz
X1
0
* 60 Hz Only.
** At 50% PF (Power Factor), 95% Nominal Secondary Voltage.
group 4 – 240/415/480 Volt primary, 120/240 Volt secondary, 50/60 Hz
230/400/460 Volt primary, 115/230 Volt secondary, 50/60 Hz
220/380/440 Volt primary, 110/220 Volt secondary, 50/60 Hz
Continuous instantaneous
Va
Va*
50
100
150
250
500
750
110
235
470
730
1670
2250
Catalog Height Width depth
Number in (mm) in (mm) in (mm)
e050tH
e100tH
e150tH
e250tH
e500tH
e750tH
2.96
(75.2)
3.39
4.36
(86.1) (110.7)
mtg Width
W1 / W2
in (mm)
2.81 / 2.50
(71.4 / 63.5)
3.74 / 3.12
(95.0 / 79.3)
3.74 / 3.12
(95.0 / 79.3)
4.38 / 3.75
(111.3 / 95.3)
5.32 / 4.37
(135.1 / 111.0)
5.32 / 4.37
(135.1 / 111.0)
mtg depth
d1 / d2
in (mm)
2.10 / N/A
(53.3 / N/A)
2.56 / 2.87
(65.0 / 73.0)
3.29 / 3.61
(83.6 / 91.7)
3.54 / N/A
(89.9 / N/A)
4.25 / 5.75
(108.0 / 146.1)
4.68 / 6.18
(118.9 / 157.0)
slot size
s1/s2 - in (mm)
.20 x .50 / .20 x .50
(5.08 x 12.7 / 5.08 x 12.7)
.20 x .65 / .20 x .33
(5.08 x 16.5 / 5.08 x 8.38)
.20 x .65 / .20 x .33
(5.08 x 16.5 / 5.08 x 8.38)
.31 x .81 / .31 x .85
(7.9 x 20.59 / 7.9 x 18.0)
approx.
ship Weight
lbs (kg)
4.0 (1.82)
8.0 (3.67)
11.0 (5.00)
15.0 (6.82)
H1
0
50/60 Hz
0
H4
440/460/480
X4
120 (480/415/240)
115 (460/400/230)
110 (440/380/220)
3.89
4.50
4.48
(98.8) (114.3) (113.8)
3.89
4.50
5.21
(98.8) (114.3) (132.3)
4.53
5.25
5.07
(115.1) (133.4) (128.8)
5.56
6.38
6.93
(141.2) (162.1) (176.0)
5.56
6.38
7.36
(141.2) (162.1) (187.0)
H3
380/400/415
X1 X3 X2 X4
H2
220/230/240
X2
X3
240 (480/415/240)
230 (460/400/230)
220 (440/380/220)
X1 X3 X2 X4
X1
.31 x .85 / .31 x .85
30.0 (13.64)
(7.9 x 21.59 / 7.9 x 21.59)
.31 x .85 / .31 x .85
34.0 (15.45)
(7.9 x 21.59 / 7.9 x 21.59)
Note: Fuse holders are not available for these voltage configurations.
* At 50% PF (Power Factor), 95% Nominal Secondary Voltage.
International Series - Fuse Recommendations
Primary Fusing: Consult local Electrical Code. Secondary Fusing: per IEC EN61558-2-2. * See 500 VA fuse rating for MC design.
Va
50
100
150
250
500
750
1000
1500
2000
* See 500 VA fuse rating for MC design.
maximum Current rating of Fuse
24 Vac
2
4
6
10
20
*
*
*
-
115 Vac
0.5
1
1.6
2
4
6
8
12
16
230 Vac
0.25
0.5
0.8
1
2
4
4
6
8
192
Contact
Technical Services
at
(800) 377-4384
with any questions.
Visit our website at www.solahd.com.
Industrial Control Transformers
ICE International Series: 750 - 2000 VA
International CE marked transformers include IP20
touchproof terminations and copper windings in an
encapsulated design. These units range from 750 to 2000
VA with 80
o
C temperature rise. The design is highly flexible
due to the use of the standardized primary coil for multiple
worldwide voltage combinations. CE marked and cULus
approval make the ICE International Series the perfect
choice for OEM export equipment.
Features
• IP20 Touch-Proof terminals
• Copper windings
• Epoxy encapsulated for cooler operation
and increased reliability
• 80
o
C rise temp, 130
o
C insulation system for harsh,
heavy-duty standards
• 50/60 Hz Frequency
• Meets or exceeds electrical requirements of NEMA,
ANSI and IEC
Certifications and Compliances
•
Listed: E77014
-
UL 506
-
CSA C22.2 No. 66
E77014
4
Design Style
•
-IEC 61558-1, IEC 61558-2-2
• RoHS Compliant
Related Products
• DIN Rail Power Supplies
• 63 Series Power Conditioners
• Surge Protective Devices
Top View
Profile
Contact
Technical Services
at
(800) 377-4384
with any questions.
Visit our website at www.solahd.com.
193
4
Selection Tables: International Series
Continuous instantaneous
Va
Va *
1000
1500
2000
2500
4200
6000
Catalog
Number
Industrial Control Transformers
group 5 – 240/415/480 Volt primary, 120/240 Volt secondary, 50/60 Hz
230/400/460 Volt primary, 115/230 Volt secondary, 50/60 Hz
220/380/440 Volt primary, 110/220 Volt secondary, 50/60 Hz
Height
in (mm)
5.63
(143.0)
5.63
(143.0)
5.63
(143.0)
Width
in (mm)
6.38
(162.1)
6.38
(162.1)
6.38
(162.1)
depth
in (mm)
6.00
(152.4)
6.75
(171.5)
7.75
(196.9)
mtg
Width
"W"
5.31
(135.0)
5.31
(135.0)
5.31
(135.0)
mtg depth
"d"
4.25
(108.0)
5.00
(127.0)
6.00
(152.4)
slot size -
inches (mm)
.31 x .69
(7.87 x 17.52)
.31 x .69
(7.87 x 17.52)
.31 x .69
(7.87 x 17.52)
approx.
ship Weight
lbs (kg)
25 (11.36)
32 (14.55)
X1 X3 X2 X4
H4
440/460/480
X4
120 (480/415/240)
115 (460/400/230)
110 (440/380/220)
H3
380/400/415
X1 X3 X2 X4
Ce1000tH
Ce1500tH
Ce2000tH
H2
220/230/240
X2
X3
240 (480/415/240)
230 (460/400/230)
220 (440/380/220)
37 (16.82)
H1
0
50/60 Hz
0
X1
* At 50% PF (Power Factor), 95% Nominal Secondary Voltage.
group 6 – 208/240/415/480/600 Volt primary, 120/240 Volt secondary, 50/60 Hz
200/230/400/460/575 Volt primary, 115/230 Volt secondary, 50/60 Hz
- /220/380/440/550 Volt primary, 110/220 Volt secondary, 50/60 Hz
Continuous instantaneous
Va
Va *
1000
1500
2000
2500
4200
6000
Catalog
Number
Ce1000mH
Ce1500mH
Ce2000mH
Height
in (mm)
5.63
(143.0)
5.63
(143.0)
5.63
(143.0)
Width
in (mm)
6.38
(162.1)
6.38
(162.1)
6.38
(162.1)
depth
in (mm)
6.00
(152.4)
6.75
(171.5)
7.75
(196.9)
mtg Width
"W"
in (mm)
5.31
(135.0)
5.31
(135.0)
5.31
(135.0)
mtg depth
"d"
in (mm)
4.25
(108.0)
5.00
(127.0)
6.00
(152.4)
slot size
in (mm)
.31 x .69
(7.87 x 17.52)
.31 x .69
(7.87 x 17.52)
.31 x .69
(7.87 x 17.52)
approx.
ship Weight
lbs (kg)
25.0 (11.36)
32.0 (14.55)
37.0 (16.82)
H6
550/575/600
X4
120 (600/480/415/240/208)
115 (575/460/400/230/200)
110 (550/440/380/220/ - )
H5
440/460/480
X1 X3 X2 X4
H4
380/400/415
X2
X3
240 (600/480/415/240/208)
230 (575/460/400/230/200)
220 (550/440/380/220/ - )
H3
220/230/240
X1 X3 X2 X4
H1
0
50/60 Hz
0
X1
* At 50% PF (Power Factor), 95% Nominal Secondary Voltage.
group 7 – 208/240/415/480/600 Volt primary, 120/ - /24 Volt secondary, 50/60 Hz
200/230/400/460/575 Volt primary, 115/24/23 Volt secondary, 50/60 Hz
- /220/380/440/550 Volt primary, 110/23/- Volt secondary, 50/60 Hz
Continuous instantaneous
Va
Va *
750
1000
1875
3000
Catalog
Number
Height
in (mm)
5.63
(143.0)
5.63
(143.0)
5.63
(143.0)
Width
in (mm)
6.38
(162.1)
6.38
(162.1)
6.38
(162.1)
depth
in (mm)
6.00
(152.4)
6.75
(171.5)
7.75
(196.9)
mtg Width
"W"
in (mm)
5.31
(135.0)
5.31
(135.0)
5.31
(135.0)
mtg depth
"d"
in (mm)
4.25
(108.0)
5.00
(127.0)
6.00
(152.4)
slot size
in (mm)
.31 x .69
(7.87 x 17.52)
.31 x .69
(7.87 x 17.52)
.31 x .69
(7.87 x 17.52)
approx.
ship Weight
lbs (kg)
25 (11.36)
32 (14.55)
H6
550/575/600
NC
X6
X5
H5
440/460/480
Ce750mC
Ce1000mC
Ce1500mC
H4
380/400/415
120 (600/480/415/240/208)
115 (575/460/400/230/200)
110 (550/440/380/220/ - )
X4
24 (575/460/400/230/200)
23 (550/440/380/220/ - )
H3
220/230/240
X3
24 (600/480/415/240/208)
H2
-200/208
1500
4500
37 (16.82)
H1
0
50/60 Hz
0
X2
X1
Notes: 24V output 500 VA maximum load. Fuse holders are not available for these voltage configurations.
* At 50% PF (Power Factor), 95% Nominal Secondary Voltage.
194
Contact
Technical Services
at
(800) 377-4384
with any questions.
Visit our website at www.solahd.com.