Single-phase Solid State Relays for Heaters
G3PE
Slim Profile Industrial SSR with Heatsink
ideal for heater applications.
• Snubber circuit provides excellent short-term surge
absorption.
• 15A and 25A models have slim 22.5mm width.
• Zero cross or “fast turn on” models.
• DIN track or panel mounting possible.
• LED indicator standard on all single phase models.
• UL, CSA and TÜV approved
.
• RoHS compliant.
Refer to Safety Precautions
Ordering Information
■
List of Models
Number of
phases
Isolation
method
Operation
indicator
Rated input
voltage
Zero cross
function
Applicable load
*
Model
15 A, 100 to 240 VAC
G3PE-215B DC12-24
Yes
Single-phase
Phototriac
coupler
Yes (yellow)
12 to 24 VDC
No
25 A, 100 to 240 VAC
G3PE-225B DC12-24
35 A, 100 to 240 VAC
G3PE-235B DC12-24
45 A, 100 to 240 VAC
G3PE-245B DC12-24
15 A, 100 to 240 VAC
G3PE-215BL DC12-24
25 A, 100 to 240 VAC
G3PE-225BL DC12-24
35 A, 100 to 240 VAC
G3PE-235BL DC12-24
45 A, 100 to 240 VAC
G3PE-245BL DC12-24
*
The applicable load current depends on the ambient temperature. For details, refer to
Load Current vs. Ambient Temperature
in the
Engineering
Data section.
Single-phase Solid State Relays for Heaters
G3PE
427
Specifications
■
Ratings
Input (at an Ambient Temperature of 25°C)
Item
Model
G3PE-@@@B
G3PE-@@@BL
Rated voltage
12 to 24 VDC
Operating voltage range
9.6 to 30 VDC
Rated input current
7 mA max.
15 mA max.
Voltage level
Must operate voltage
9.6 VDC max.
Must release voltage
1.0 VDC max.
Output
Model
Item
Rated load voltage
Load voltage range
Applicable load current
*
Inrush current
Permissible I
2
t
(reference value)
Applicable load
(resistive load)
0.1 to 15 A
(at 40°C)
G3PE-215B(L) G3PE-225B(L) G3PE-235B(L) G3PE-245B(L)
100 to 240 VAC (50/60 Hz)
75 to 264 VAC (50/60 Hz)
0.1 to 25 A
(at 40°C)
0.5 to 35 A
(at 25°C)
0.5 to 45 A
(at 25°C)
150 A
220 A
(60 Hz, 1 cycle) (60 Hz, 1 cycle)
121A
2
s
3 kW
(at 200 VAC)
260A
2
s
5 kW
(at 200 VAC)
440 A
(60 Hz, 1 cycle)
1,260A
2
s
7 kW
(at 200 VAC)
9 kW
(at 200 VAC)
*
The applicable load current depends on the ambient temperature. For details, refer to
Load Current vs. Ambient Temperature
■
Characteristics
Model
Item
Operate time
Release time
Output ON voltage drop
Leakage current
Insulation resistance
Dielectric strength
Vibration resistance
Shock resistance
Ambient storage temperature
Ambient operating
temperature
Ambient operating humidity
Weight
G3PE-215B
G3PE-225B
G3PE-235B
G3PE-245B
G3PE-215BL
1 ms max.
G3PE-225BL
G3PE-235BL
G3PE-245BL
1/2 of load power source cycle + 1 ms max.
1/2 of load power source cycle + 1 ms max.
1.6 V (RMS) max.
10 mA max. (at 200 VAC)
100 MΩ min. (at 500 VDC)
2,500 VAC, 50/60 Hz for 1 min
10 to 55 to10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude) (Mounted to DIN track)
Destruction: 294 m/s
2
(Mounted to DIN track)
−30
to 100°C (with no icing or condensation)
−30
to 80°C (with no icing or condensation)
45% to 85%
Approx. 240 g
Approx. 400 g
Approx. 240 g
Approx. 400 g
428
Single-phase Solid State Relays for Heaters
G3PE
Engineering Data
Input Voltage vs. Input Impedance and Input Voltage vs. Input Current
G3PE-2@@B
Input current (mA)
Input impedance (kΩ)
10
9
8
7
6
5
4
3
2
1
0
0
5
10
15
20
25
30 35
Input voltage (V)
Input impedance
Input current
Ta = 25°C
G3PE-2@@BL
Input impedance (kΩ)
Input current (mA)
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0
5
Ta = 25°C
Input current
Input impedance
10
15
20
25
30 35
Input voltage (V)
Load Current vs. Ambient Temperature
G3PE-215B(L), G3PE-225B(L)
Load current (A)
30
25
G3PE-@25B(L)
20
G3PE-235B(L), G3PE-245B(L)
Load current (A)
50
45
40
35
30
G3PE-235B(L)
G3PE-245B(L)
15
G3PE-@15B(L)
10
7
20
18
17
14
10
0
−30
−20
0
20
40
60
80
100
Ambient temperature (°C)
0
−30
−20
0
20 25 40
60
80
100
Ambient temperature (°C)
Inrush Current Resistivity: Non-repetitive
Make sure the inrush current stays below the dashed line curve if it occurs repetitively.
G3PE-215B(L)
Inrush current (A. Peak)
250
G3PE-225B(L)
Inrush current (A. Peak)
250
G3PE-235B(L), G3PE-245B(L)
Inrush current (A. Peak)
500
200
200
400
150
150
300
100
100
200
50
50
100
0
10
30 50 100
300 500 1,000 3,000 5,000
Energized time (ms)
0
10
30 50 100
300 500 1,000 3,000 5,000
Energized time (ms)
0
10
30 50 100
300 500 1,000 3,000 5,000
Energized time (ms)
Single-phase Solid State Relays for Heaters
G3PE
429
Close Mounting (3 or 8 SSRs)
G3PE-215B(L)
Load current (A)
20
G3PE-225B(L)
Load current (A)
30
25
3 Relays
20
19
15
8 Relays
G3PE-235B(L)
Load current (A)
40
3 Relays
30
28
26
20
8 Relays
G3PE-245B(L)
Load current (A)
50
3 Relays
15
13
12
10
8 Relays
40
3 Relays
31
30
29
8 Relays
20
5.7
5
10
8
7
5
0
−40
11
10
11
10
0
−40
0
−40
−20
0
20
40
60
80 100
Ambient temperature (°C)
−20
0
20
40
60
80 100
Ambient temperature (°C)
0
−40
−20
0
20 25 40
60
80 100
Ambient temperature (°C)
−20
0
20 25
40
60
80 100
Ambient temperature (°C)
Close Mounting Example
DIN Track
■
Approvals
UL Recognized, CSA Certified and EN60947-4-3 (TÜV) approved
430
Single-phase Solid State Relays for Heaters
G3PE
Dimensions
Note:
All units are in millimeters unless otherwise indicated.
Solid State Relays
G3PE-215B(L)
G3PE-225B(L)
13
±0.2
Two, M4
Two,
4.6 dia.
100 max.
68
24
90
±0.2
84
Two,
M3.5
4.2
6.3
Note:
Without
terminal cover.
Mounting Holes
13
±0.3
4.6
×
5.6
elliptical hole
4.5
22.5 max.
Note:
With
terminal cover.
Terminal Arrangement/Internal Circuit Diagram
G3PE-5@@B
1
G3PE-2@@B
(+)
A1
1
(+)
A1
Output side
Output side
Input side
(100)
90
±0.3
(85)
(90)
A2
A2
Three, 4.5 dia.
or M4
2
)
−
(
2
)
−
(
G3PE-235B(L)
G3PE-245B(L)
25
±0.2
Two, M5
4.6 dia.
100 max.
68
24
90
±0.2
84
Two,
M3.5
6
13.5
4.6
×
5.6
elliptical hole
44.5 max.
Note:
Without
terminal cover.
Mounting Holes
25
±0.3
Note:
With
terminal cover.
Terminal Arrangement/Internal Circuit Diagram
G3PE-5@@B
1
G3PE-2@@B
(+)
A1
Input side
(+)
A1
Trigger circ
u
it
Trigger circ
u
it
Inp
u
t circ
u
it
Output side
Output side
Inp
u
t circ
u
it
1
Input side
(100)
90
±0.3
(85)
(90)
A2
A2
Three, 4.5 dia.
or M4
2
)
−
(
2
)
−
(
Single-phase Solid State Relays for Heaters
G3PE
Input side
Trigger circ
u
it
Trigger circ
u
it
Inp
u
t circ
u
it
Inp
u
t circ
u
it
431