Lists UL Recognized & CSA Certified configurations and performance capabilities as a Component Supplementary Protector.
Notes:
1
Requires branch circuit backup with a UL LISTED Type K5 or RK5 fuse (15A minimum) at no more than 4 times the rating of the protector.
2
Same as note 1, except that backup fuse is limited to 80A maximum.
3
2 pole protector required (with one pole per power line) for: 250/125 VAC, 125/250 VAC and 208Y/120 VAC Power Systems. 1 pole protector required for : 125 VAC, 1Ø Power System.
4
Satisfies the requirements of clause 11.2.8.2.5 of CSA STD C22.2 No 100 for the use of supplementary protectors with portable generators.
Lists UL Recognized, CSA, VDE & TUV Certified configurations & performance capabilities as a Component Supplementary
Protector.
Notes:
1
General Purpose Ratings for UL/CSA Only.
2
Requires branch circuit backup with a UL LISTED Type K5 or RK5 fuse (15A minimum) at no more than 4 times the rating of the protector.
3
Same as note 1, except that backup fuse is limited to 80 A maximum.
Table C:
Lists UL Recognized, CSA Certified configurations and performance capabilities as Protectors, Supplementary for Marine
Electrical and Fuel Systems (CCN/Guide PEQZ2, File E75596). Ignition Protected per UL 1500. UL Classified Small Craft Electrical Devices,
Marine in accordance with ISO 8846 (CCN/Guide UZMK, File MQ1515) as Marine Supplementary Protectors.
Notes:
1
Available with special catalog number only (consult factory).
2
2 pole protector required (with one pole per power line) for: 250/125 VAC, 125/250 VAC and 208Y/120 VAC Power Systems. 1 pole protector required for : 125 VAC, 1Ø Power System.
How do you beautify the interface of your own Windows Mobile-based applications? Including using C++ and C#? I hope you can give me some advice. Thank you!...
I would like to ask, when the Rosemount temperature transmitter was designed in principle, an op amp was designed at the power supply. I would like to know what the role of the op amp is in the power ...
I was confused at first about the downloading method of MSP430 microcontroller. Many people said that the downloading method used an emulator, such as UIF or PIF. I checked online and found that the e...
I have made wireless temperature detectors, wireless temperature information acquisition terminals and other things before, and later I also made wireless remote controls in bits and pieces, which can...