3120-F511-P7T1-W02A-0.8A

Description
1 POLE(S), 0.8A, 250 V(AC), 50 V(DC), PANEL MOUNT, THERMAL CIRCUIT BREAKER,
CategoryCircuit protection    Circuit protection   
File Size441KB,5 Pages
ManufacturerE-T-A [E-T-A Circuit Breakers]
Download Datasheet Parametric View All

3120-F511-P7T1-W02A-0.8A Overview

1 POLE(S), 0.8A, 250 V(AC), 50 V(DC), PANEL MOUNT, THERMAL CIRCUIT BREAKER,

3120-F511-P7T1-W02A-0.8A Parametric

Parameter NameAttribute value
Objectid1145922093
Reach Compliance Codecompliant
Actuator typeROCKER
body width21 mm
body height33 mm
Body length or diameter48 mm
circuit functionMANUAL ON/OFF
Circuit protection typeTHERMAL CIRCUIT BREAKER
Installation featuresPANEL MOUNT
Number of poles1
Maximum operating temperature60 °C
Minimum operating temperature-30 °C
physical size48mm x 21mm x 33mm
Rated breaking capacity8 A
Rated current0.8 A
Rated voltage (AC)250 V
Rated voltage (DC)50 V
GuidelineCCC; CSA; UL; VDE
surface mountNO
Terminal shapeQUICK CONNECT
Thermal Overcurrent Circuit Breaker 3120-F...
Description
An extremely versatile range of rocker switch/thermal circuit breakers
(S-type TO CBE to EN 60934 with trip free mechanism) offering the choice
of single pole, double pole with single pole protection, and double pole
with protection on both poles. Designed for snap-in panel mounting with
versions available for three different panel cut-out sizes. Illumination is
optional and there is a range of colours and markings for the rocker.
Add on modules:
Under voltage release coil (for double pole versions only).
Magnetic trip coil for short circuit protection.
Magnetic trip coil for remote relay trip.
Auxiliary contacts for status signalling.
Approved to CBE standard EN 60934 (IEC 60934).
Meets the requirements regarding fire resistance of EN 60335-1 : 2007-02
Safety of household and similar electrical appliances.
3120-F3...F5
Typical applications
Technical data
Motors, transformers, solenoids, extra low voltage wiring systems, office
machines, electro-medical equipment, power supplies, communications
systems, medical equipment to EN 60601.
Standard current ratings and typical internal resistance values
Current rating
(A)
0.1
0.2
0.3
0.4
0.5
0.6
0.8
1
1.2
1.5
2
2.5
3
3.5
Internal
resistance
per pole (Ω)
94
24
12
5.30
4.20
2.90
1.50
0.9
0.80
0.45
0.27
0.0785
0.0595
0.0565
Current rating
(A)
4
4.5
5
6
7
8
10
12
14
15
16
18
20
Internal
resistance
per pole (Ω)
0.0435
0.0435
0.0325
0.0215
0.0165
0.0165
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
Dielectric strength
(IEC 60664 and 60664A)
operating area
between poles (2-pole)
Insulation resistance
Interrupting capacity I
cn
3120-F7
2
For further details please see chapter: Technical Information
Voltage rating
AC 240 V; DC 50 V
(AC 415 V to special order)
(UL: AC 250 V; DC 50 V)
Current ratings
0.1...20 A
(up to 30 A to special order, single pole only)
Typical life
AC 240 V:
DC 50 V:
DC 28 V:
AC 415 V:
AC 240 V:
0.1...20 A
0.1...4 A
4.5...16 A
0.1...20 A
0.1...16 A
0.1...16 A
17...20 A
DC 50 V:
0.1...16 A
17...20 A
Ambient temperature
Insulation co-ordination
(IEC 60664 and 60664 A
1-pole
30,000 operations at 1 x I
N
, inductive
30,000 operations at 1 x I
N
, inductive
30,000 operations at 1 x I
N
, resistive
30,000 operations at 1 x I
N
, inductive
2-pole
10,000 operations at 1 x I
N
, inductive
50,000 operations at 1 x I
N
, inductive
30,000 operations at 1 x I
N
, inductive
50,000 operations at 1 x I
N
, inductive
10,000 operations at 1 x I
N
, inductive
-30...+60 °C (-22...+140 °F)
rated impulse
pollution
withstand voltage
degree
2.5 kV
2
reinforced insulation in operating area
Illumination voltage/power consumption
operating voltage
12 V DC
24 V DC
115 V AC
230 V AC
power consumption
Y+R
2 mA
2 mA
0.9 mA
0.9 mA
G
3.5 mA
3.5 mA
2.8 mA
2.8 mA
test voltage
AC 3,000 V
AC 1,500 V
> 100 MΩ (DC 500 V)
0.1...2 A 10 x I
N
2.5...20 A 250 A 2-pole, or 150 A 1-pole
Interrupting capacity (UL 1077)
I
N
1, 2-pole
1, 2-pole
Degree of protection
(IEC 60529/DIN 40050)
Vibration
0.1...20 A
0.1...20 A
U
N
AC 250 V
DC 50 V
I
nc
5000 A
1000 A
Approvals
Authority
VDE (EN 60934)
Voltage ratings
AC 240 V; DC 28 V
DC 50 V
DC 50 V
AC 250 V; DC 50 V
AC 250 V; DC 50 V
Current ratings
0.1...20 A
0.1...20 A
2-pole
0.1...10 A
1-pole
0.1...20 A
0.1...20 A
Shock
Corrosion
Humidity
Mass
UL, CSA
CCC
operating area IP40
(IP54 with water splash protection)
terminal area IP00
8 g (57-500 Hz), ± 0.61 mm (10-57 Hz)
to IEC 60068-2-6, test Fc
10 frequency cycles/axis
30 g (11 ms)
to IEC 60068-2-27, test Ea
96 hours at 5 % salt mist,
to IEC 60068-2-11, test Ka
240 hours at 95 % RH,
to IEC 60068-2-78, test Cab
approx. 33 g (double pole)
approx. 27 g (single pole)
Issue D
www.e-t-a.de
2
- 67
DSP memory issues
How to check memory allocation and current usage in ccs5.4?...
chenxingfkd DSP and ARM Processors
Can fellow engineers show me the State Grid standard charging pile billing control system based on TI AM3354?
[i=s] This post was last edited by jameswangsynnex on 2016-3-30 13:09 [/i] [b][font=宋体][size=24px] Can engineers show us the charging pile billing control system based on TI AM3354 of the State Grid s...
jameswangsynnex Energy Infrastructure?
Six Tips for Selecting PCB Components
Best Practices for PCB Design: Six Things to Consider When Making Component-Package-Based Selections All of the examples in this article were developed using the Multisim design environment, but the s...
中信华 PCB Design
Design Studies on Hybrid Excitation Motor for Main
Design Studies on Hybrid Excitation Motor for Main Spindle Drive in Machine Tools...
安_然 Analogue and Mixed Signal
stm32Cube4 light cube
[i=s]This post was last edited by weizhongc on 2016-5-5 18:04[/i] [font=宋体][size=4]I have played with many light cubes before, and the 888 light cube can control 4096 colors. Video link: [/size][/font...
xmb6954757 stm32/stm8

EEWorld
subscription
account

EEWorld
service
account

Automotive
development
circle

Robot
development
community

Index Files: 1709  654  2078  516  700  35  14  42  11  15 
Datasheet   0 1 2 3 4 5 6 7 8 9 A B C D E F G H I J K L M N O P Q R S T U V W X Y Z
Room 1530, 15th Floor, Building B, No. 18 Zhongguancun Street, Haidian District, Beijing Telephone: (010) 82350740 Postal Code: 100190
Copyright © 2005-2026 EEWORLD.com.cn, Inc. All rights reserved 京ICP证060456号 京ICP备10001474号-1 电信业务审批[2006]字第258号函 京公网安备 11010802033920号