SYSMAC CS-series Controller Link Units
CS1W-CLK
CSM_CS1W-CLK_DS_E_5_1
New Controller Link Units, Now
with 4,000 Send Words
• The Controller Link is an FA network that can send
and receive large amounts of data easily and at high
speed. The Controller Link supports data links that
enable sharing data between PLCs and computers
and a message service that enables sending and
receiving data whenever required.
• With Wired Controller Link Units, systems can be
flexibly built by using Repeater Units to enable T-
branches, long-distance wiring, and converting part of
the network to optical cable.
CS1W-CLK23
CS1W-CLK13
CS1W-CLK53
Features
Large-capacity data links are easily achieved without programming simply by setting data link tables.
Up to 20,000
*1
send/receive words can be set per node for Units (up to 62,000 words for Boards).
Data links can be performed with up to 4,000
*2
words per node while ensuring data concurrency.
User-set data link tables can be changed while data links are operating.
*3
Errors for the entire system can be monitored by using error diagnosis support software and a variety of status flags.
With the token ring mode of Optical Ring Controller Link Units/Boards, duplex communications paths enable communications to continue
normally even if the cable becomes disconnected.
•
Detecting locations of disconnection greatly shortens time required for maintenance.
•
Installing Controller Link Units in a CS1D system enables Duplex Communications Units to further enhance reliability.
*4
*1.
Supported for unit version 1.2 or later.
*2.
CS1W-CLK@3 and 3G8F7-CLK@3 are supported.
*3.
Supported for CS1W-CLK@3, 3G8F7-CLK@3, and models ending with "-V1" (CS1W-CLK12-V1
*5
and CS1W-CLK52-V1
*5
with lot numbers
0306@@_@@@ or later ).
*4.
Supported for CS1W-CLK13/CLK12-V1
*5
/CLK53/CLK52-V1
*5
and CS1D Duplex and Simplex Systems.
*5.
Discontinuation models in July 2012.
•
•
•
•
•
•
1
CS1W-CLK
System Configuration
Wired Controller Link Units
Basic Wiring (Daisy Chain Connections)
A
A
A
A
(1)
B
1 km Max. *
(1)
C
D
A
B
(2)
A
C
(1)
D
(1)
D
(1)
1 km Max. *
1 km Max. *
1 km Max. *
(1)
B
(1)
A
A
B
B
A
A
T-Branch Wiring and Partial Conversion to
Optical Cable
Long-distance Wiring
A
A
A: Wired Controller Link Unit
B: Wired Controller Link Support Board
C: Wire-to-Optical Repeater Unit
D: Wire-to-Wire Repeater Unit
*
At 500 kbits/s
(1): Twisted-pair cable
(2): Optical cable
Optical Controller Link Units
Token Ring Mode
A
A
B
Token Bus Mode
A
A
B
B
(1)
B
(1)
A
A
A
A
A
A
A: Optical Ring Controller Link Unit
B: Optical Ring Controller Link Support Board
(1): Optical cable
2
CS1W-CLK
Ordering Information
Controller Link Units
Unit
classifi-
cation
Specifications
Product
name
Communications
cable
Communications
type
Duplex
support
Max. Units
mountable per
CPU Unit
No. of unit
numbers
allocated
Current
consumption
(A)
5V
DC
26 V
DC
Model
Standards
Controller
Link
Unit
Wired shielded
twisted-pair cable
*1
No
8
1
0.33
−
CS1W-CLK23
CS1
CPU
Bus Unit
Controller
Link
Unit
Optical ring H-PCF
cable
*2
Data links and
message service
Yes. Unit
duplexing
and cable
loop back are
supported.
1
Non-duplex: 8,
Duplex: 11
(6 Units
comprising 3
sets of Duplex
Units + 5
Non-duplex
Units)
1
0.52
−
CS1W-CLK13
UC1, N, L,
CE
Controller
Link
Unit
Optical ring GI cable
*3
0.65
−
CS1W-CLK53
*1.
Use the following special cable for shielded, twisted-pair cable.
•
ESVC0.5×2C-13262 (Bando Electric Wire : Japanese Company)
•
ESNC0.5×2C-99-087B (Nihon Electric Wire & Cable Corporation : Japanese Company)
•
ESPC 1P×0.5mm
2
(Nagaoka Electric Wire Co.,Ltd. : Japanese Company)
•
Li2Y-FCY2×0.56qmm (Kromberg & Schubert, Komtec Department : German Company)
•
1×2×AWG-20PE+Tr.CUSN+PVC (Draka Cables Industrial : Spanish Company)
•
#9207 (Belden : US Company)
*2.
When using a wire-to-optical (H-PCF) cable, use a H-PCF cable (for both Controller Link and SYSMAC LINK) or a H-PCF optical fiber cable
with connector.
*3.
When using a wire-to-optical (GI) cable, use a GI optical cable that matches the specifications.
Accessories
The Optical Fiber Cable Bracket is included in CS1W-CLK13 and CS1W-CLK53.
3
CS1W-CLK
Controller Link Support Boards
Specifications
Product name
Controller Link
Support Board
for PCI Bus
Communications
cable
Wired shielded
twisted-pair cable
H-PCF optical model
GI optical model
Data links and message
service
Communications type
Accessories
•
CD-ROM
×
1
*
•
INSTALLATION GUIDE (W467)
×
1
•
Communications connector
×
1
•
CD-ROM
×
1
*
•
INSTALLATION GUIDE (W467)
×
1
•
Optical Fiber Cable Bracket
×
1
•
Power supply connector
×
1
Model
Standards
3G8F7-CLK23-E
3G8F7-CLK13-E
3G8F7-CLK53-E
CE
*
The CD-ROM contains the following software.
•
Controller Link (PCI) Driver
•
FinsGataway Version 2003 (PCI-CLK Edition)
•
FinsGataway Version 3 (PCI-CLK Edition)
•
Setup Diagnostic Utility
•
C Library
Repeater Units
Name
Controller Link
Repeater Unit
CS1W-RP
T01
PWR
T/R1
T/R2
Specifications
Wire-to-Wire Model
Wire-to-Optical (H-PCF) Model (See note 1.)
Wire-to-Optical (GI) Model (See note 2.)
CS1W-RPT01
CS1W-RPT02
CS1W-RPT03
Model
Standards
UC1, CE
SL1
TER SW
SW1
1 BAUD
2 RATE
ON
TER SW
SL2
DC24V
INPUT
Using Repeater Units enables T-branches and long-distance wiring for Wired Controller Link networks, 62-node configurations, and converting
part of the network to optical cable.
Note: 1.
When using wire-to-optical (H-PCF) cable, use a H-PCF cable (for both Controller Link and SYSMAC LINK) or a H-PCF optical fiber cable
with connector.
2.
When using wire-to-optical (GI) cable, use a GI optical cable (for Controller Link).
Relay Terminal Block
Name
Relay Terminal Blocks for
Wired Controller Link Units
Specifications
Model
Standards
Used for Wired Controller Link Units (set of 5)
CJ1W-TB101
−
Controller Link Units can be replaced without stopping the communications of the entire network if a Relay Terminal Block is installed in advance
on the Unit in a Wired Controller Link network. Relay Terminal Blocks cannot be used on Controller Link Support Boards.
Duplex Optical Fiber Cable (H-PCF Cable)
Name
Duplex Optical Fiber Cable
Application
Specifications
Model
CS1D-CN051
Standards
−
CS1W-CLK13 or
H-PCF cable for connecting Duplex Controller Link Units
CS1W-CLK12-V1
*
in a CS1D system Cable length: 50 cm
This cable is used to connect Units in active mode (ACT) and standby mode (STB) in a CS1D Duplex System.
*
Discontinuation models in July 2012.
4
CS1W-CLK
H-PCF Cables and Optical Connectors
Name
Application/construction
1
2
3
4
5
6
Specifications
Black
Black
Black
Black
10 m
50 m
100 m
500 m
1000 m
10 m
50 m
100 m
500 m
1000 m
Model
S3200-HCCB101
S3200-HCCB501
S3200-HCCB102
S3200-HCCB502
S3200-HCCB103
S3200-HCCO101
S3200-HCCO501
S3200-HCCO102
S3200-HCCO502
S3200-HCCO103
Standards
Optical Fiber Cables
Controller Link,
SYSMAC LINK,
SYSBUS
1. Optical fiber single-core cord
2. Tension member
(plastic-sheathed wire)
3. Filler (plastic)
4. Filler surrounding signal wires
(plastic, yarn, or fiber)
5. Holding tape (plastic)
6. Heat-resistant PV sheath
CS1W-CLK13
CS1W-CLK12-V1
*1
3G8F7-CLK13-E
3G8F7-CLK12-EV1
*1
CS1W-RPT02
CS1W-SLK11
3G8F7-SLK11-E
C200HW-SLK13/14
CS1W-CLK13
CS1W-CLK12-V1
*1
3G8F7-CLK13-E
3G8F7-CLK12-EV1
*1
CS1W-RPT02
3G8F7-SLK11-E
Two-core optical
cable with tension
member
Black
Orange
Orange
Orange
Orange
Orange
−
Controller Link:
Half lock
S3200-COCF2571
Optical
Connectors
(Crimp-cut)
SYSMAC LINK:
Controller Link:
Full lock
S3200-COCF2071
*2
SYSMAC LINK:
*1.
Discontinuation models in July 2012.
*2.
Full-lock Optical Connectors (Crimp-cut) (S3200-COCF2071) cannot be used with the CS1W-SLK11. Use a Half-lock Cable (S3200-
COCF2571) or a H-PCF Optical Fiber Cable with Connector (S3200-CN@@@-@@-@@).
H-PCF Optical Fiber Cables with Connectors (Black Composite Cables with Two-Optical Lines and Two Power Supply Lines)
Application
Appearance
Model
S3200-CN@@@-20-20
Controller Link,
SYSMAC LINK
S3200-CN@@@-20-25
S3200-CN@@@-25-25
Optical connectors for H-PCF Optical Cables with Connectors are adhesive polished.
−
Standards
Cable Length
The following cable lengths are available: 2 m, 5 m, 15 m, and 20 m. For lengths of 21 m or more, contact your OMRON sales representative.
Model Numbers
(1) 2 m, 5 m, 10 m, 15 m, or 20 m
(2) 21 m or longer
S3200-CN@@@
@@@-20-25
1.
2.
3.
S3200-CN-20-20
1.
3.
Specify the
cable length
in meters.
1.
H-PCF
Optical Fiber Cable
2.
Cable length
@@@
201
501
102
152
202
Length
2m
5m
10 m
15 m
20 m
3.
Connectors (both ends)
Number Connector lock
20
Full-lock
25
Half-lock
Cable length
5