economical solution to the challenge of load-applied
harmonics mitigation in three-phase power systems.
With a plug-and-play approach and more compact
dimensions than comparable products, they can be
quickly installed and easily commissioned. They
increase the reliability and service life of electric
installations, help utilize electric sytem capacity
better, and are the key to meet Power Quality
standards such as IEEE 519. Ecosine filters reshape
your distorted current back to the desired sinusoidal
waveform. Schaffner ecosine filters can be applied to
virtually any kind of power electronics with front-end
six-pulse rectifiers, 3-phase diode or thyristor bridges,
where harmonic current distortion needs to be
reduced to defined limits.
Technical specifications
Nominal operating voltage
Operating frequency
Nominal motor drive input power rating
Total harmonic current distortion THID*
Efficiency
High potential test voltage
Protection category
Cooling
Overload capability
Ambient temperature range
3 x 440 VAC to 500 VAC ±10%
50 Hz ±1 Hz
1.1 to 250 kW
<5% at rated power
>98% for rated voltage and power
P –> E 2160 VAC (1 s)
IP 00, IP 20
Internal fan cooling or external cooling**
1.6x rated current for 1 minute, once per hour
–25°C to +45°C fully operational
+45°C to +70°C derated operation***
–25°C to +85°C transport and storage
UL 94 V-2
Filter: UL 61800-5-1, EN 61800-5-1
Chokes: EN 61558-2-20 or EN 60076-6
>200,000 hours
100 kA
TN, TT, IT
OV III (IEC 60664-1 / UL 61800-5-1)
Typical applications
Equipment with front-end six-pulse rectifier
Motor drives
Factory automation equipment
Water/wastewater treatment facilities
Fan and pump applications
HVAC installations
Mission-critical processes
DC fast chargers
Flammability corresponding to
Design corresponding to
MTBF @ 45°C/500 V (Mil-HB-217F)
SCCR****
Earthing System
Overvoltage category
Typical electrical schematic
****System requirements: THVD <2%, line voltage unbalance <1%
** *
Note: performance specifications in this brochure refer to six-pulse diode rectifiers.
****SCR
rectifier front-ends will produce different results, dependent upon the firing angle of the thyristors.
THID ~5% at rated power for filter <6 kW
** Please check the inlet air flow required for cooling table on page 6 of this document.
*** I
derated
= I
nominal
*√((T
max-
T
amb
)/(T
max-
T
nominal
)) = I
nom
*√(70°C-T
amb
)/25°C
**** External UL-rated fuses required. Please consult the user manual.
2
Ecosine passive
Schaffner Group
Datasheets
25 Jun 2019
Filter selection table – IP 00 enclosure
Filter
Rated load power
@ 480 VAC/50 Hz
[kW]
1.1
2.2
4.4
5.5
7.5
11
15
19
22
30
37
45
55
75
90
110
132
160
200
250
Motor drive
input current
[Arms]***
1.5
3
5.5
10
13
16
24
32
38
45
60
75
90
110
150
180
210
260
320
400
Rated filter
input current
[Arms]
1.35
2.75
4.99
6.77
9.24
13.6
18.5
23.3
27.0
36.9
45.4
55.2
67.5
92.5
111
135
163
198
248
310
Weight
Typical
losses
Terminal
Frame
size
[kg]
5.8
8.4
11.3
14.0
16.9
20.9
28.2
32.0
36.0
47.5
53.9
63.1
66.8
88.1
120.1
140.6
160.9
181.1
216.8
256.7
[W]****
49
76
132
135
183
256
287
376
374
460
546
598
784
1036
1016
1083
1440
1412
1597
1745
110
110
112
112
112
112
113
113
113
115
115
115
115
115
116
116
118
118
118
118
A
A
B
B
C
C
D
D
D
E
E
E
F
F
G
G
H
H
H
H
FN 3450-1-110-E0_ _ _ _ _*
FN 3450-2-110-E0_ _ _ _ _*
FN 3450-4-112-E0_ _ _ _ _*
FN 3450-6-112-E0_ _ _ _ _*
FN 3450-8-112-E0_ _ _ _ _*
FN 3450-11-112-E0_ _ _ _ _*
FN 3450-15-113-E0_ _ _ _ _
FN 3450-19-113-E0_ _ _ _ _
FN 3450-22-113-E0_ _ _ _ _
FN 3450-30-115-E0_ _ _ _ _
FN 3450-37-115-E0_ _ _ _ _
FN 3450-45-115-E0_ _ _ _ _
FN 3450-55-115-E0_ _ _ _ _
FN 3450-75-115-E0_ _ _ _ _
FN 3450-90-116-E0_ _ _ _ _
FN 3450-110-116-E0_ _ _ _ _
FN 3450-132-118-E0_ _ _ _ _
FN 3450-160-118-E0_ _ _ _ _**
FN 3450-200-118-E0_ _ _ _ _**
FN 3450-250-118-E0_ _ _ _ _**
* Filter rating which does not require forced cooling or fan module
** Filter rating which does not require RC damping module for rectifiers with EMI filter
*** Motor drive input current without harmonic filter
**** Typical losses @ 45°C, 480V, 50Hz and rated load power
Filter power terminals
Terminal designation*
Screw thread
Flex wire AWG
Flex wire
Screw torque value
Max width**
cable lug
[mm
2
]
110
112
113
115
116
118
M3
M4
M6
M8
M8
M10
14-22
10-22
6-18
1/0-8
3/0-8
3/0-500 kcmil
0.4-2.5
0.4-6
0.75-16
10-50
10-95
95-240
[Nm]
0.5
1.2
3
8
8
10
[mm]
7
10
15
15
17
35
A
B, C
D
E, F
G
H
Frame size
* Recommended connector type: wire or cable lug for 110 to 113, only cable lug for 115 to 118
** To fulfill creepage/clearance acc. UL 61800-5-1 without additional protection (insulation). Creepage/clearance can vary depending on applicable standard and must
be reviewed by customer. Creepage/clearance may be reduced when additional protection (insulation) is provided.
Filter signal and earth terminals
Terminal type
Screw thread
Screw torque value
[Nm]
Signal
Earth (PE)
Earth (PE)
Earth (PE)
Earth (PE)
Earth (PE)
Earth (PE)
Earth (PE)
Earth (PE)
M3*
M5
M6
M6
M8
M8
M10
M10
M10
0.5
2.2
4
4
9
9
17
17
17
All
A
B
C
D
E
F
G
H
Frame size
* Max width cable lug = 7 mm
3
Ecosine passive
Schaffner Group
Datasheets
25 Jun 2019
Filter selection table – IP 20 enclosure
Filter
Rated load power
@ 480 VAC/50 Hz
[kW]
1.1
2.2
4
5.5
7.5
11
15
19
22
30
37
45
55
75
90
110
132
160
200
250
Motor drive
input current
[Arms]***
1.5
3
5.5
10
13
16
24
32
38
45
60
75
90
110
150
180
210
260
320
400
Rated filter
input current
[Arms]
1.35
2.75
4.99
6.77
9.24
13.6
18.5
23.3
27.0
36.9
45.4
55.2
67.5
92.5
111
135
163
198
248
310
Weight
Typical
losses
Terminal
Frame
size
[kg]
7
9
13
15
19
23
32
36
40
53
60
69
74
95
129
149
178
198
234
274
[W]****
49
76
132
135
183
256
287
376
374
460
546
598
784
1036
1016
1083
1440
1412
1597
1745
110
110
112
112
112
112
113
113
113
115
115
115
115
115
116
116
118
118
118
118
A
A
B
B
C
C
D
D
D
E
E
E
F
F
G
G
H
H
H
H
FN 3450-1-110-E2_ _ _ _ _*
FN 3450-2-110-E2_ _ _ _ _*
FN 3450-4-112-E2_ _ _ _ _*
FN 3450-6-112-E2_ _ _ _ _*
FN 3450-8-112-E2_ _ _ _ _*
FN 3450-11-112-E2_ _ _ _ _*
FN 3450-15-113-E2_ _ _ _ _
FN 3450-19-113-E2_ _ _ _ _
FN 3450-22-113-E2_ _ _ _ _
FN 3450-30-115-E2_ _ _ _ _
FN 3450-37-115-E2_ _ _ _ _
FN 3450-45-115-E2_ _ _ _ _
FN 3450-55-115-E2_ _ _ _ _
FN 3450-75-115-E2_ _ _ _ _
FN 3450-90-116-E2_ _ _ _ _
FN 3450-110-116-E2_ _ _ _ _
FN 3450-132-118-E2_ _ _ _ _
FN 3450-160-118-E2_ _ _ _ _**
FN 3450-200-118-E2_ _ _ _ _**
FN 3450-250-118-E2_ _ _ _ _**
* Filter rating which does not require forced cooling or fan module
** Filter rating which does not require RC damping module for rectifiers with EMI filter
*** Motor drive input current without harmonic filter
**** Typical losses @ 45°C, 480V, 50Hz and rated load power
Filter power terminals
Terminal designation*
Screw thread
Flex wire AWG
Flex wire
Screw torque value
Max width**
cable lug
[mm
2
]
110
112
113
115
116
118
M3
M4
M6
M8
M8
M10
14-22
10-22
6-18
1/0-8
3/0-8
3/0-500 kcmil
0.4-2.5
0.4-6
0.75-16
10-50
10-95
95-240
[Nm]
0.5
1.2
3
8
8
10
[mm]
7
10
15
15
17
35
A
B, C
D
E, F
G
H
Frame size
* Recommended connector type: wire or cable lug for 110 to 113, only cable lug for 115 to 118
** To fulfill creepage/clearance acc. UL 61800-5-1 without additional protection (insulation). Creepage/clearance can vary depending on applicable standard and must
be reviewed by customer. Creepage/clearance may be reduced when additional protection (insulation) is provided.
Filter signal and earth terminals
Terminal type
Screw thread
Screw torque value
[Nm]
Signal
Earth (PE)
Earth (PE)
Earth (PE)
Earth (PE)
Earth (PE)
Earth (PE)
Earth (PE)
Earth (PE)
M3*
M5
M6
M6
M8
M8
M10
M10
M10
0.5
2.2
4
4
9
9
17
17
17
All
A
B
C
D
E
F
G
H
Frame size
* Max width cable lug = 7 mm
4
Ecosine passive
Schaffner Group
Datasheets
25 Jun 2019
Product selector
Table 1: Filter configurations if external air flow is available for cooling
(Filters do
not contain fan
and do
not contain aux. power supply)
E0XXXXX
- For rectifiers without DC-link
choke
E0XXJXX
- For rectifiers without DC-link
choke
- Filters contain trap disconnect
jumper
E0XXXRX
- For rectifiers without DC-link
choke and with EMI filter
- Filters contain RC damper
module
E0XXJRX
- For rectifiers without DC-link
choke and with EMI filter
- Filters contain RC damper
module and trap disconnect
jumper
5
Ecosine passive
Schaffner Group
Datasheets
25 Jun 2019
Table 2: Filter configurations with embedded ventilation
(Filters
contain fan
and
aux. power supply)
E0FAXXX and E2FAXXX
- For rectifiers without DC-link
choke
- Filters contain fan, aux. power
supply
E0FAJXX and E2FAJXX
- For rectifiers without DC-link
choke
- Filters contain fan, aux. power
supply and trap disconnect
jumper
E0FAXRX and E2FAXRX
- For rectifiers without DC-link
choke and with EMI filter
- Filters contain fan, aux. power
supply and RC damper module
E0FAJRX and E2FAJRX
- For rectifiers without DC-link
choke and with EMI filter
- Filters contain fan, aux. power
supply, RC damper module and
trap disconnect jumper
Table 3: Filter configurations if external aux. power supply for the fan is available
Can anyone provide Mitsubishi or Fanuc PLC software and introductory learning materials? Or the names of good related books. I want to learn some new knowledge recently....
[i=s]This post was last edited by webber310 on 2022-1-7 19:58[/i]3. Lighting Experiment
In the previous article, we introduced the hardware of BG22-EK4108A and the installation of the development envi...
CC1310 is a Sub-1G-capable SOC in TI Simplelink MCU series. In response to the application requirements of many customers who need to upgrade firmware via serial port, CC1310 has a built-in ROM-based ...
The current calculation formula is Ia=Ia*100/0*34D1B8*Ka*ct, where Ka is the calibration coefficient 1.2886. Ia*100/0*34D1B8 is not known what it means....
Huawei MATE 40 Ring Flash Protective Case Solution_Principle Analysis and Original Disassembly Comparison
Recently, Huawei launched a very unique protective case. The highlight of this protective case...
Emergency hand-held lamps powered by 6V maintenance-free batteries are widely used in rural areas. The charger used is a transformer step-down and single diode half-wave rectifier, and the charging...[Details]
All electronic design engineers and scientists have performed electrical signal analysis, or signal analysis for short. Through this basic measurement, they can gain insight into signal details and...[Details]
1. Introduction
At present, most lighting equipment still uses traditional energy for lighting. Making full use of solar energy as the energy supply for lighting equipment is of great si...[Details]
Overview:
This paper introduces a method of connecting a CAN-bus network with Ethernet to form a medium-sized remote monitoring/data transmission network.
CAN (Controller Area Network) is ...[Details]
1. Introduction to CIF Board
Fieldbus integration based on PC system
Whether it is a master or a slave, fieldbus has won unanimous praise in the field of PC-based automation. For more...[Details]
Many battery-powered systems require a visual indicator to show when the battery needs to be replaced. LEDs are commonly used for this purpose, but they consume at least 10mA of current. This con...[Details]
Liquid crystal display (LCD) panels have a wide range of applications, from small portable electronic devices to large fixed devices, including digital cameras, laptops, personal data assistants, d...[Details]
When the so-called "copycat phones" that flood the domestic mobile phone market move towards large screens, stereo amplifiers, touch controls, and even GPS navigation and mobile TV, the homogeneity...[Details]
Portable power applications are broad and varied. Products range from wireless sensor nodes with average power consumption of only a few microwatts to in-vehicle medical or data acquisition systems...[Details]
1 Introduction
Power supply ripple will interfere with the normal operation of electronic equipment, causing malfunctions such as computer crashes, data processing errors and control system fa...[Details]
LonWorks fieldbus technology is widely used, for example, in intelligent buildings, industrial control, environmental protection, etc. Echelon's LonWorks system has been used in the products of tho...[Details]
introduction
Sudan's Muglad Oilfield is a large oilfield jointly invested, developed and constructed by a four-party consortium of China, Malaysia, Canada and Sudan. It consists of 8 satellite...[Details]
The rotor of the brushless DC motor used in electric bicycles is composed of 30 to 40 pieces of NdFeB magnets. Since the surface magnetic field strength of NdFeB magnets exceeds 500mT, the position se...[Details]
For the past
15
years, many have predicted that
the
8
-bit microcontroller would soon be gone. However, this was one of the most miscalculated predictions in the el...[Details]
As the electromagnetic environment in space becomes increasingly complex, the shielded cables used to transmit weak signals in the test system are easily affected by external electromagnetic distur...[Details]