Embedded Power for
Business-Critical Continuity
LPS100-M Series
150 Watts
Total Power:
Input Voltage:
# of Outputs:
80 - 150 Watts
90 - 264 Vac
Single
Rev. 03.30.10_29
LPS100-M Series
1 of 3
Special Features
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Medical and ITE safeties
Active power factor correction
2” x 4” footprint
Less than 1U high
EN61000-3-2 compliant
Remote sense
Power fail
Adjustable main output
Built-in Class B EMI filter
Overvoltage protection
Overload protection
Thermal overload protection
Isolated12 V Fan output
LPX50 Enclosure kit available
Electrical Specifications
Input
Input range:
Frequency:
Inrush current:
Efficiency:
EMI/RFI:
Safety ground
leakage current:
90 - 264 Vac; 120 - 300 Vdc
47-63 Hz
50 A max., cold start @ 25 °C
88% typical at full load
FCC Class B conducted; CISPR22 Class B conducted;
EN55022 Class B conducted; VDE0878PT3 Class B conducted
275 µA @ 50/60 Hz, 264 Vac input
Output
Maximum power:
Adjustment range:
Fan output:
Hold-up time:
Overload protection:
100 W for convection (80 W for LPS102-M);
150 W with 30 CFM forced air (120 W for LPS102-M)
± 10% minimum on the main outputs
12 V @ 1 A isolated, ± 10%
10 ms @ 150 W load, 120 Vac input
Short circuit protection on all outputs. Case overload
protected @ 110-160% above rating
Overvoltage protection: 15-35% above nominal output
Logical Control
Power failure:
Safety
•
•
•
•
•
•
TUV
UL
cULus
CB
CE
CQC
60950, 60601-1
60950, 60601-1
60950, 60601-1
Certificate & report
Mark (LVD)
Mark
Remote sense:
Open collector logic signal goes high 100-500 msec after main output; it
goes low at least 6 msec before loss of regulation
Compensates for 0.5 V lead drop min. Will operate without remote sense
connected. Reverse connection protected.
Embedded Power for
Business-Critical Continuity
Environmental Specifications
Operating temperature:
Storage temperature:
Electromagnetic
susceptibility:
Humidity:
Vibration:
MTBF calculated:
0° to 50 °C ambient derate each output as 2.5% per degree from 50° to 70 °C. -20 °C start up
-40 °C to +85 °C
Designed to meet EN61000-4;
-2, -3, -4, -5, -6, -8, -11 Level 3
Operating; non-condensing 10% to 95% RH
IEC68-2-6 to the levels of IEC721-3-2
534,000 hours at full load and 25 °C ambient conditions, 230 V input, Bellcore
Rev. 03.30.10_29
LPS100-M Series
2 of 3
Mechanical Drawing
M1
VR1
Output Voltage
Adjust Pot M2
1
4
8
SK203
SK2
GND
SK1 1
3
2.00"
(50.8)
1
3.73"
(94.7)
4.00"
(101.6)
0.10”
(2.5)
0.197” (5.0) Minimum
Standoff height
1.29"
(33.0)
1.72"
(43.8)
Mounting Hole
Ø0.16"[4.0] 4 Places
Max. Screw Head
Diameter .22” (5.6)
1
4
SK5
Embedded Power for
Business-Critical Continuity
Ordering Information
Model
Number
LPS102-M
LPS103-M
LPS104-M
LPS105-M
LPS108-M
Output
Voltage
5V
12 V
15 V
24 V
48 V
Minimum
Load
0A
0A
0A
0A
0A
Maximum Load
with Convection
Cooling
16 A
8.3 A
6.7 A
4.2 A
2.1 A
Maximum Load
with 30CFM
Peak Load Regulation
2
Forced Air
24 A
12.5 A
10 A
6.3 A
3.1 A
30 A
14 A
11 A
7A
3.5 A
± 2%
± 2%
± 2%
± 2%
± 2%
Ripple
P/P (PARD)
3
50 mV
120 mV
150 mV
240 mV
480 mV
Americas
5810 Van Allen Way
Carlsbad, CA 92008
USA
Telephone: +1 760 930 4600
Facsimile: +1 760 930 0698
Rev. 03.30.10_29
LPS100-M Series
3 of 3
Europe (UK)
1. Peak current lasting < 30 seconds with a maximum 10% duty cycle.
2. At 25 °C including initial tolerance, line voltage, load currents and output voltages adjusted to factory settings.
3. Peak-to-peak with 20 mHz bandwidth and 10 µF (tantalum capacitor) in parallel with a 0.1 µF capacitor at rated line voltage
and load ranges.
Waterfront Business Park
Merry Hill, Dudley
West Midlands, DY5 1LX
United Kingdom
Telephone: +44 (0) 1384 842 211
Facsimile: +44 (0) 1384 843 355
Asia (HK)
Pin Assignments
Connector LPS100-M
SK1
Pin 1
Neutral
Pin 3
Line
SK2
Pin 1
Common
Pin 2
Common
Pin 3
Common
Pin 4
Common
Pin 5
+Vout
Pin 6
+Vout
Pin 7
+Vout
Pin 8
+Vout
SK203
Pin 1
Common
Pin 2
Power Fail
Pin 3
- Remote Sense
Pin 4
+ Remote Sense
SK5
Pin 1
+12 V Fan
Pin 2
+12 V Fan
Pin 3
Fan Return (Isolated)
Pin 4
Fan Return (Isolated)
Mating Connectors
AC Input (SK1): Molex P/N: 09-50-3031, Pins: 08-52-0072
or
Landwin P/N: 3060S0302, Pins: 3360T011P
AC Ground
Molex: 01-90020001
DC Output
Molex P/N: 09-50-3081, Pins: 08-52-0072
(SK2):
or
Landwin P/N: 3060S0802, Pins: 3360T011P
Remote Sense Molex P/N: 35155-0400, Pins: 08-70-0057
(SK203):
or
Landwin P/N: 2640S04A0, Pins: 2543T011P
Fan: (SK5):
Molex P/N: 22-01-1042, Pins: 08-70-0049
or
Landwin: P/N: 2510S04A0, Pins: 2543T011P
Emerson Network Power Connector Kit #70-841-025, includes all of the
above
14/F, Lu Plaza
2 Wing Yip Street
Kwun Tong, Kowloon
Hong Kong
Telephone: +852 2176 3333
Facsimile: +852 2176 3888
For global contact, visit:
www.Emerson.com/EmbeddedPower
techsupport.embeddedpower
@emerson.com
While every precaution has been taken to ensure
accuracy and completeness in this literature, Emerson
Network Power assumes no responsibility, and disclaims
all liability for damages resulting from use of this
information or for any errors or omissions.
Emerson Network Power.
The global leader in enabling
business-critical continuity.
AC Power
Connectivity
DC Power
Embedded Computing
Notes:
1. Specifications subject to change without notice.
2. All dimensions in inches (mm), tolerance is ±.02”.
3. mounting holes MH1, MH2 should be grounded for EMI
purpose
4. Mounting MH1 is safety ground connection
5. Specifications are for convection rating at factory settings
at 115 Vac input 25 °C unless otherwise stated.
6. This power supply requires mounting on metal standoffs
0.20” (5 m) in height.
7. For DC input an external DC safety rated fuse must be used.
8. Warranty: 2 year
9. Weight: 0.44 lb. / 0.20 kg
Embedded Power
Monitoring
Outside Plant
Power Switching & Controls
Precision Cooling
Racks & Integrated Cabinets
Services
Surge Protection
EmersonNetworkPower.com
Emerson Network Power and the Emerson
Network Power logo are trademarks and
service marks of Emerson Electric Co.