EEWORLDEEWORLDEEWORLD

Part Number

Search

T2400.0010

Description
industrial relays dual overcurrent relay
CategoryTopical application    Mechanical and electrical/engineering/automation   
File Size127KB,1 Pages
ManufacturerLittelfuse
Websitehttp://www.littelfuse.com
Download Datasheet Compare View All

T2400.0010 Overview

industrial relays dual overcurrent relay

Protection Relays & Controls
Generator & Single-Function Protection–Overcurrent
T2400 SerieS
3-Phase Dual Overcurrent Relay
Description
The T2400 3-Phase Dual Overcurrent Relay includes two
combined overcurrent relays, designed for protection or
monitoring of generators and power transmissions. A typical
application is to use one of the overcurrent functions to trip the
generator circuit breaker, and the other overcurrent function to
trip a non-essential consumer.
The T2400 consists of two overcurrent circuits with similar
current settings and time delays. Each circuit detects the
highest of the 3 input currents and, if this exceeds the preset
level (0.5-1.4 x I
N
), the corresponding pick-up LED will indicate
and the delay timer will be started. After the preset time
(3-30 sec.) has expired, the corresponding output relay and
LED will be activated, provided that the current level was
exceeded for the entire delay time.
Simplified Circuit Diagram
1
2
3
11
12
13
14
15
16
II. OVERCURRENT
Features & Benefits
FeaTureS
Accepts high supply
voltage variation
10
9
8
7
6
5
4
U
SUPPLY
T2400
(3-Phase Dual
Overcurrent Relay)
I. OVERCURRENT
beneFiTS
Ensures correct operation in spite of voltage
supply fluctuations (fulfills marine class
requirement)
Provides quick and concise status information
Simplifies design and installation.
No need for PTs.
Economic solution for non-essential load
tripping, and occupying less space in the
switch panel
Protects the unit against high AC voltage and
currents from the installation including spikes
Easy installation
I
1
I
2
I
3
Visual indication of
power, pick-up, and
output trip
Direct line-line or line-
neutral voltage supply
(up to 690 Vac)
Combining 2 relays in
same enclosure
Galvanic isolated inputs
L1 L2 L3
Ordering Information
OrderinG
number
TerminalS
1-3
2-3
i
n
FuncTiOn
DIN-rail or screw-mount
& adjustment by
potentiometers
Specifications
Trip Level
Delay
Max. Voltage
Voltage Range
Consumption
0.5-1.4 x I
N
3-30 sec.
660 V
60-110%
Voltage 5 VA at U
N
Current 0.3 VA at I
N
Continuous Current
2 x I
N
Frequency Range
45-400 Hz
Output Relay
Normally de-energized
Contact Rating
AC: 400 V, 5 A, 2000 VA; DC: 150 V, 5 A, 150 W
Overall Accuracy
±5%
Repeatability
±1%
Operating Temperature
–20°C to + 70°C
Dielectric Test
2500 V, 50 Hz
EMC
CE according to EN50081-1, EN50082-1,
EN50081-2, EN50082-2
Approvals
Certified by major marine classification societies
Burn-in
50 hours before final test
Enclosure Material
Polycarbonate. Flame retardant
Weight
0.5 kg
Dimensions
H
70 mm (2.76”);
W
100 mm (3.94”);
D
115 mm (4.52”)
Installation
35 mm DIN rail or 4 mm (
3
/
16
”) screws
Rev: 4-A-050213
T2400.0010
T2400.0020
T2400.0030
T2400.0040
T2400.0050
T2400.0060
T2400.0070
T2400.0080
T2400.0090
230 V
450 V
110 V
450 V
480 V
450 V
450 V
5A
400 V 5 A
100 V 5 A
on relay 1,
400 V 5 A Latching outputon relay 1
6-60 sec. delay
415 V 5 A
400 V 1 A
400 V 5 A Latching output on relay 1,
normally energized relay 1
127 V 120 V 5 A
24 Vdc
5A
Latching output relays are reset by disconnecting the power supply.
Other supply voltages and combinations are available on request.
© 2013 Littelfuse Protection Relays & Controls
Littelfuse.com/t2400

T2400.0010 Related Products

T2400.0010 T2400.0060 T2400.0040 T2400.0050 T2400.0100
Description industrial relays dual overcurrent relay industrial relays dual overcurrent relay industrial relays dual overcurrent relay industrial relays dual overcurrent relay industrial relays dual overcurrent relay
How can I use a PDA to connect to a PC's database wirelessly?
I have stored an Access database locally on my PDA. Now I want to upload it to my PC and download data from my PC. I don't want to create an intermediate program to achieve this. I can access the PC d...
oupole Embedded System
LAN8720+SIM800 Industrial IoT RTU
RTU/DTU products seem to have been around since 2000. If you search on Taobao, you can find many products for around 200 yuan. This is also a product that has been made to death. After work, I rarely ...
lyzhangxiang RF/Wirelessly
How to remove the serial port feedback information of the development board
How to remove the automatic feedback information of the serial port of the development board s3c2410? For example, connect the development board and the PC, open the serial port software on the PC, an...
dhu2060427 Embedded System
Finally learned how to solder bga chips
When I soldered before, I just glued a few pins of the chip, and the jtag couldn't connect. Later, I tried a few more times, and the chip blew up almost every time. I was so scared that I didn't dare ...
zxq6 PCB Design
STM32 interrupt triggering problem
I used two external interrupts, but one of them was not triggered. Once the program was executed, it entered the interrupt. I don't understand why.Also, sometimes there is a fluctuation on the pin, wh...
juhao0122 stm32/stm8
Problems in developing mapx mobile in evb3.0
After searching online for a few days, I have summarized a few questions. Please give me some advice: 1. Does MapX Mobile support EVB3.0+PPC2002? (According to some people online who have done this, i...
zhangle8311 Embedded System

EEWorld
subscription
account

EEWorld
service
account

Automotive
development
circle

Robot
development
community

Index Files: 14  1833  824  151  1380  1  37  17  4  28 
Datasheet   0 1 2 3 4 5 6 7 8 9 A B C D E F G H I J K L M N O P Q R S T U V W X Y Z
Room 1530, 15th Floor, Building B, No. 18 Zhongguancun Street, Haidian District, Beijing Telephone: (010) 82350740 Postal Code: 100190
Copyright © 2005-2026 EEWORLD.com.cn, Inc. All rights reserved 京ICP证060456号 京ICP备10001474号-1 电信业务审批[2006]字第258号函 京公网安备 11010802033920号