silica filler housed in a fiberglass tube and plated endcaps.
An epoxy paint protects the fuse tube from the surround-
ing environment.
FEATURES:
• Standard Clip Center Lengths and Barrel Diameters.
The new line of Bussmann 15.5 kV medium voltage fuses
have standard clip center distances of 15 or 18 inches
and barrel diameters of 2 or 3 inches which allow fuses to
retrofit exisiting hardware.
• Blown Fuse Indication with Indicator.
• 100% Tested for Reliability.
All medium voltage fuses
are pulsed twice with 90% of their minimum melt I
2
t to
guarantee undamaged elements. This test does not affect
undamaged elements. A damaged element completely
opens when subjected to 90% of the minimum melt I
2
t,
allowing it to be detected by a resistance check.
• Full Range Fuses.
Bussmann medium voltage fuses
provide full range protection and are capable of interrupt-
ing fault currents of 50,000A sym.
• Time Current Curves and Dimensional Data:
MV155F1CB series, see page 2;
MV155F1DB and MV155F1DC series, see page 3.
• Peak Arc Voltage Curves and Peak Let-Through
Data,
see page 4.
• Fuse Clips,
see page 4.
† To order with the optional striker pin, see Part Number Construction chart below.
Part Number Construction
Medium Voltage
Example
MV
Voltage Rating
155
055 = 5.5 kV
155 = 15.5 kV
F
F = Full Range
Number of Barrels
1
1
2
Barrel Diameter
C
C = 2 inches
D = 3 inches
Clip Center Distance
B
A = 12 inches
B = 15 inches
C = 18 inches
Indication Type
X
X = Indicator only
S = Striker Pin
Ampere Rating
5E
2-26-03
SB03044
Form No. MV155
Page 1 of 5
Data Sheet: 6701
Bussmann
®
E-Rated Medium Voltage Fuses
For Transformer and Feeder Protection
15.5 kV - MV155F1CB Series
Time-Current Characteristics
Minimum Melt
AMPERE
RATING
5A
7A
10A
15A
20A
25A
30A
Time-Current Characteristics
Total Clearing
5A
7A
10A
15A
20A
25A
30A
MV155
100
100
AMPERE
RATING
10
10
TIME IN SECONDS
1
TIME IN SECONDS
1,000
7,000
100
10
1
.1
.1
.01
.01
1,000
7,000
Form No. MV155
Page 2 of 5
Data Sheet: 6701
CURRENT IN AMPERES
CURRENT IN AMPERES
MV155F1CBX
18.61"
17.77"
.21"
BUSSMANN
2.03"
.63"
Ø2.095"
INDICATOR
15.00"
CLIP CENTER
POSITION OF BLOWN
INDICATOR AFTER
OPERATING.
2-26-03
SB03044
100
10
Bussmann
®
E-Rated Medium Voltage Fuses
For Transformer and Feeder Protection
15.5 kV - MV155F1DB & MV155F1DC Series
Time-Current Characteristics
Minimum Melt
1000
MV155
Time-Current Characteristics
Total Clearing
1000
15A
20A
25A
30A
40A
50A
65A
80A
100A
125A
150A
175A
200A
50A
65A
80A
100A
100
100
10
10
TIME IN SECONDS
1
1
.1
.1
DOUBLE BARREL
FUSE ASSY.
SINGLE BARREL
FUSE ASSY.
TIME IN SECONDS
DOUBLE BARREL
FUSE ASSY.
SINGLE BARREL
FUSE ASSY.
.01
10000
20000
10
100
1000
1000
.01
100
10
CURRENT IN AMPERES
10000
20000
CURRENT IN AMPERES
MV155F1DBX
18.61"
17.77"
.21"
2.40"
.63"
BUSSMANN
Double Barrel
Dimensions
Ø2.96"
INDICATOR
Ø1.30"
Ø3.38"
15.00"
CLIP CENTER
POSITION OF BLOWN
INDICATOR AFTER
OPERATING.
125A
150A
175A
200A
3.50"
10A
15A
20A
25A
30A
40A
10A
6.68"
MV155F1DCX
21.61"
20.77"
.21"
BUSSMANN
2.40"
.63"
Ø2.96"
INDICATOR
Ø1.30"
Ø3.38"
18.00"
CLIP CENTER
POSITION OF BLOWN
INDICATOR AFTER
OPERATING.
2-26-03
SB03044
Form No. MV155
Page 3 of 5
Data Sheet: 6701
Bussmann
®
E-Rated Medium Voltage Fuses
For Transformer and Feeder Protection
15.5 kV - Peak Arc Voltage & Peak Let-Through Data
Max. Peak Let-Through Current Curves
MV155
MAXIMUM PEAK ARC VOLTAGE FOR
"E" RATED FULL RANGE POWER FUSE
(BUSSMANN)
B
100
50
10
MAXIMUM LET-THROUGH (Peak Kiloamperes)
50A
30&40A
25A
20A
15A
07&10A
05A
MAXIMUM PEAK ARC VOLTAGE (KV)
100
200A
175A
150A
125A
100A
80A
65A
40
30
20
1
A
10
.1
.1
1
AVAILABLE CURRENT IN KILOAMPERES (RMS Symmetrical)
10
0
0
5
10
15
20
CIRCUIT VOLTAGE (KV)
Recommended Fuse Clips for Medium Voltage Fuses
Part
No.
Fuse
Clip Dimensions
Diameter
A
B
C
D
E
F
G
A3354710
A3354730
2”
3”
3.74”
4.13”
1.97”
2.44”
2.00”
3.00”
1.18” 4.53” 1.50” .39”
1.18” 5.63” 1.50” .39”
Fuseclips are for single barrel applications up to 200E only.
C
A
G
F
D
B
Form No. MV155
Page 4 of 5
Data Sheet: 6701
E
2-26-03
SB03044
Bussmann
®
E-Rated Medium Voltage Fuses
For Transformer and Feeder Protection
15.5 kV - Cross Reference Data
Catalog Number Cross Reference
Bussmann
MV155F1CBXxxxE
MV155F1DBXxxxE
MV155F1DCXxxxE
MV155F2DCXxxxE
Gould (New)
A155F1CORO-xxxE
A155F1DORO-xxxE
A155F1DORO-xxxE
A155F2DORO-xxxE
Gould (Old)
A1550X-xxxE-1B
A1550X-xxxE-1F
A1550X-xxxE-1D
A1550X-xxxE-1D
Westinghouse
----
15HLE-xxxE
----
----
----
9F62DDDxxx
----
----
General Electric
----
9F60FMHxxx
----
----
MV155
Bussmann Medium Voltage Cross Reference
Overall
Sym.
Length
kA
Manufacturer
18-3/4”
50
Bussmann
15.5 kV
17-3/100”
50
Gould†
18-3/4”
50
Bussmann
18-7/8”
40
Gould†
15.5 kV
3”
15”
18-7/8”
50
Westinghouse†
18-7/8”
40
General Electric†
3”
18”
21-3/4”
50
Bussmann
15.5 kV
21-3/4”
50
Gould†
† Gould, Westinghouse and General Electric are General Purpose Fuses.
kV
Dia.
2”
Clip
Center
15”
E Ratings Available
5
7
10 15
S S
S
S
S S
S
S
S
S
S
S
S = Single Barrel
D = Double Barrel
20
S
S
S
S
S
S
25
S
S
S
S
S
S
30
S
S
S
S
S
S
40
50
65
80
100 125 150 175
200 250 300 350 400 450
S
S
S
S
S
S
S
S
S
D
S
S
S
S
S
D
S
S
S
S
S
D
S
S
S
S
D
S
D
S
D
D
D
D
S
D
D
D
D
D
D
D
D
D
D
D
D
D
D
Current-limiting medium voltage fuses are classified into three categories:
Full Range
- defined by ANSI as “a fuse capable of interrupting all currents from the maximum rated interrupting current down to
the minimum continuous current that causes melting of the fusible element(s), when the fuse is applied at the maximum ambient
temperature specified by the manufacturer.” It is able to interrupt any normal 60 cycle current that will melt its element.
General Purpose
- defined by ANSI C37.40 as “a fuse capable of interrupting all currents from the maximum rated interrupting
current down to the current that causes melting of the fusible element in one hour.” Not all currents fall within this range. It is
possible to receive an overcurrent lower than the value given by the one hour criterion.
Back-up
- defined by ANSI C37.40 as “a fuse capable of interrupting all currents from the maximum rated interrupting current
down to the rated minimum interrupting current.” The minimum rated interrupting current is the lowest current that the fuse will be
able to clear properly. This creates a need to place a low current interrupting device in series with the back-up rated fuse.
All Bussmann MV series medium voltage fuses are E-rated and offer Full Range Protection.
The only controlled copy of this Data Sheet is the electronic read-only version located on the Bussmann Network Drive. All other copies of this BIF document are by definition uncontrolled.This bulletin is intended to clear-
ly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change design or construction of any prod-
ucts and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected,
it should be tested by the user in all possible applications.
When I copy a large file in WinCE system, it seems that nothing happens when I want to cancel the copy. Although the progress bar is closed, the background copy process continues. I am confused! ! Is ...
The content of the short-term internship is the design of a DDS signal generator. The microcontroller teacher asked me to use 430. After checking the information for a few days, I am still confused. I...
Ten years ago, the slogan "Mobile phone, pager, business communication, none of them can be missing" was used for several years, and it was known as the essential weapon for the real "businessmen" at ...
[i=s] This post was last edited by 小盼abc on 2016-8-14 16:34 [/i] Why is Ub'e=Ib*rb'e in the high-frequency equivalent circuit of a triode? Logically, shouldn't the current flowing through rb'e be ie? ...
The msp430 processor in the DLP4710 module is mainly used to configure two display chips and drive the fan. Can this part be removed during mass production?...
Emergency hand-held lamps powered by 6V maintenance-free batteries are widely used in rural areas. The charger used is a transformer step-down and single diode half-wave rectifier, and the charging...[Details]
In
circuit design,
current
measurement
is widely used, and the main fields are divided into three categories: in measurement,
the electric meter
is used to measure the curre...[Details]
1 Introduction
A wide variety of communication cables and control cables are widely used in various instruments and control equipment. Whether the cable is well-conducted and
whether
th...[Details]
As a wireless broadband metropolitan area network standard, WiMAX technology has greater advantages than previous 3.5GHz MMDS products in terms of non-line-of-sight transmission and spectrum utiliz...[Details]
In this article, the high-performance DSP developed by TI can be used as an effective confidentiality method if it is applied to PC encryption cards.
As an effective network security solution,...[Details]
This paper designs a dot matrix LED text display screen that is easy to update, expandable, and low-cost. The way to reduce costs is
① Use the Bluetooth data transmission function of mobile ph...[Details]
To differentiate their products in a crowded and competitive market, manufacturers of handheld devices often consider battery life and power management as key selling points for cell phones, PDAs, ...[Details]
July 11, 2012, Beijing - Altera Corporation (NASDAQ: ALTR) today announced the launch of 40-Gbps Ethernet (40GbE) and 100-Gbps Ethernet (100GbE) intellectual property (IP) core products. These core...[Details]
Aromatic gases are widely present in food, medicine, cosmetics and various daily chemical products, such as snacks, liquor, spices, Chinese herbal medicines, plasters, perfumes, soaps, shampoos, et...[Details]
Contact resistance
is the resistance to current flow through a closed pair of contacts. This type of measurement is performed on devices such as connectors,
relays
, and switches. The...[Details]
1. Introduction to CIF Board
Fieldbus integration based on PC system
Whether it is a master or a slave, fieldbus has won unanimous praise in the field of PC-based automation. For more...[Details]
1 Introduction to HART Protocol
HART (Highway Addressable Remote Transducer), an open communication protocol for addressable remote sensor high-speed channels, was launched by Rosemen in the U...[Details]
MediaTek (2454) announced the acquisition of F-MStar (3697) and attracted the attention of IC design industry. This morning, Gartner Semiconductor Industry Research Director Hong Cenwei analyzed ...[Details]
PV inverter manufacturer SMA has launched its first DC arc fault circuit interrupter (AFCI) PV inverter and has received UL certification.
The new SunnyBoy AFCI inverter models include 3000-US...[Details]
The automotive lighting and signal control system is responsible for controlling the vehicle's lighting, signal lights, electric horns, reversing and brake buzzers. Traditional automotive lighting...[Details]