2
Uninterruptible Power Systems
S3K Mini-Tower Line-Interactive UPS
The S3K is an economical choice for those applications
requiring the performance of a sinewave output, line
interactive UPS with the mini-tower shape for cabinet
installations. The S3K Series protects against most severe
power disturbances through state-of-the-art, line-interactive
technology. Most power disturbance corrections are
accomplished without transferring to the internal battery.
Utility power is continually protected by the S3K Series UPS
and internal battery life is optimized.
The UPS has built in protection for under and over voltage
conditions including low-energy lightning surges introduced
on the input power source. All S3K Series UPS are provided
with an input circuit protector and surge protected data line
connectors. The S3K Series UPS is provided with a battery
test function. Should the battery fail this test, the UPS will
display a warning to indicate that the battery needs to be
replaced.
Applications
• Workstations
• PLCs
• Robotics and Process Control
• Industrial Automation Systems
• Automatic Service & Dispensing Equipment
Features
• Mini-Tower design for control cabinet installation.
• Automatic voltage regulation (AVR) topology saves
battery power for deep voltage sag situations.
• Sine wave output
• User replaceable, "hot swappable" batteries
(Downtime for battery replacement not required).
• RS-232 communications port
• Built-in surge protection
• Cold start capability (DC power on)
• Telephone/modem spike protection
• Power management software is included (UPSMON).
• 50/60 Hz auto sensing
• Fully digitized, microprocessor controlled
• Protects against most adverse power conditions
including:
- Frequency variations
- Surge
- Sags
- Spike
- Blackouts
- Over and under voltages
• Two year limited warranty
E179213
Certifications and Compliances
•
Listed, UPS Equipment
- UL 1778, CSA C22.2 No. 107.3
• IEC 60801-2, Level 4 / IEC 60801-4, Level 4 / ANSI
C62.41 Category A & B
Related Products
• Portable MCR Power Conditioners
• Surge Protective Devices
• Active Tracking
®
Filters
Battery Back-up Times Chart
Load % Watts
20
40
50
70
100
S3K700
45
21
14
9
5
S3K1000
37
18
13
8
4
S3K1600
27
12
10
6
3
Note: Back-up times are at 25°C with 100% capacity batteries and resistive
loads.
68
Contact
Technical Services
at
(800) 377-4384
with any questions.
Visit our website at www.solahd.com.
Uninterruptible Power Systems
2
Approx. Ship Weight
lbs (kg)
34.1 (15.50)
37.0 (16.80)
70.4 (32.00)
Selection Table
Capacity
(VA/W)
700/480
1000/750
1440/1200
Catalog
Number
S3K700
S3K1000
S3K1600
Volts, Frequency
(In/Out)
120/120, 50/60 Hz
120/120, 50/60 Hz
120/120, 50/60 Hz
Typical Back-up
Time (minutes)*
5/14
4/13
3/10
Input Plug/Output Receptacle
(Detached) 5-15P / (4)5-15R
(Detached) 5-15P / (4)5-15R
(Attached) 5-15P / (6)5-15R
* Full/Half Load (in minutes).
Specifications
Catalog Number
Power Rating (VA/Watts)
S3K700
700/480
S3K1000
1000/750
S3K1600
1440 */1200
8.90 x 6.70 x 17.70
(226.0 x 170.0 x 450.0)
14.00 x 12.00 x 22.25
(358.0 x 307.0 x 581.0)
70.4 (32.00)
Unit (H x W x D)
Shipping (H x W x D)
Approx. Shipping Weight - lbs (kg)
Voltage Range
Plug
Line to Boost Transfer
Line to Buck Transfer
Frequency
Voltage
Receptacles
Frequency
Waveform
Overload Warning
Overload Shutdown
Dimensions inches (mm)
8.30 x 5.50 x 17.20
(210.0 x 140.0 x 436.0)
11.75 x 10.50 x 19.20
(300.0 x 265.0 x 492.0)
34.1 (15.50)
37.0 (16.80)
Input AC Parameters
103-132 Vac
6 ft. detachable with NEMA 5-15P
Attached 5-15P
Maintains output to 120 Vac; -14%, when input is 120 Vac, -25%
Maintains output to 120 Vac; +10%, when input is 120 Vac, +23%
45-55 Hz or 55-65 Hz; auto sensing
Output AC Parameters
103 Vac to 132 Vac
(4) NEMA 5-15R
50 Hz or 60 Hz ±0.5%
Sine wave
100-110% Nominal
200% Nominal
Battery Parameters
Valve-regulated, non-spillable, lead acid
5/14
4 x 12 V x 7 AH
2-4 ms typical
See Battery Back-up Times Charts
4 Hours
to 90% rated capacity, after full discharge into resistive load
Environmental
0°C to +40°C
-15°C to +50°C
0% to 95%, non-condensing
Up to 10,000 ft. (3000 m) at 35°C without derating
<40 dBA, (beyond 1 m)
Standards
FCC Part 15, Subpart B, Class A
<45 dBA, (beyond 1 m)
4/13
3/10
6 x 12 V x 7 AH
(6) NEMA 5-15R
Type
Battery Time (mins) (FL/HL)
Qty. x Voltage x Rating
Transfer Time
Back-up Time
Recharge Time
Operating Temperature
Storage Temperature
Relative Humidity
Operating Elevation
Audible Noise
EMC
* Note: 1200W at 0.75 power factor equals 1600VA. Line cord limits total load to 1440 VA (max).
Contact
Technical Services
at
(800) 377-4384
with any questions.
Visit our website at www.solahd.com.