Power Entry Modules with Line Filter
https://www.schurter.com /PG06
KFC
IEC Appliance Inlet C14 with Filter, Fuseholder 1- or 2-pole (5x20 mm or 6.3x32 mm), optional Voltage Se-
lector (step switch)
with voltage selector
without voltage selector
C14
70° C
Approvals and Compliances
Description
- Panel Mount :
Screw-on mounting from front side
- 4 Functions :
Appliance Inlet Protection class I , Fuseholder with interchangeable
fuse drawer for Fuse-links 5x20 mm or 6.3x32 mm , with or without
voltage selector (step switch) , Line filter in standard and medical ver-
sion
- Quick connect terminals 4.8 x 0.8 mm
Characteristics
- All single elements are already wired
- The fuse drawer "Fingergrip" can be removed by hand
- Suitable for use in equipment according to IEC/UL 60950
Suitable for use in medical equipment according to IEC/UL 60601-1
Other versions on request
References
Weblinks
- Variant with notch for V-Lock mating Cordsets
Alternative: version without line filter
KEC
Alternative: Standard version
pdf datasheet, html-datasheet, General Product Information, Distributor-
Stock-Check, Accessories, Detailed request for product, Microsite
Unique Selling Proposition
-
-
-
-
Multifunctional power entry module
Suitable for various fuses
Highly resistant since fully potted
V-Lock cord retaining
Newly available variants corresponding to V-Lock mating cordset. The connector is equipped with a notch intended for use with the latching cordset.
The cord latching system prevents against accidental removal of the cordset.
Technical Data
Ratings IEC
Ratings UL/CSA
Leakage Current
Dielectric Strength
1 - 10 A @ Ta 40 °C / 250 VAC; 50 Hz
1 - 10 A @ Ta 40 °C / 125 VAC; 60 Hz
standard < 0.5 mA (250 V / 60 Hz)
medical < 5 µA (250 V / 60 Hz)
> 1.7 kVDC between L-N
> 2.7 kVDC between L/N-PE
Test voltage (2 sec)
-25 °C to 85 °C
25/085/21 acc. to IEC 60068-1
from front side IP 40 acc. to IEC 60529
Suitable for appliances with protection
class I acc. to IEC 61140
Quick connect terminals 4.8 x 0.8 mm
Screw: max 8 mm
Mounting screw torque max 0.5 Nm
Thermoplastic, black, UL 94V-0
appliance inlet/-outlet
C14 acc. to IEC 60320-1,
UL 498, CSA C22.2 no. 42 (for cold
conditions) pin-temperature 70 °C, 10 A,
Protection Class I
1 or 2 pole, Shocksafe category PC2
acc. to IEC 60127-6,
for fuse-links 5 x 20 or 6.3 x 32 mm
5 x 20: 2.5 W (1 pole)/ 2 W (2-pole) per
pole
6.3 x 32: 3.15 W (1 pole)/ 2.5 W (2-pole)
per pole
Admissible power acceptance at higher
ambient temperature see derating cur-
ves
optional, step, 3 pos.
Standard and Medical Version, IEC
60939, UL 1283, CSA C22.2 no. 8
Technical Details
> 1'700'000 h acc. to MIL-HB-217 F
Fuseholder
Allowable Operation Tempe-
rature
Climatic Category
IP-Protection
Protection Class
Terminal
Panel Thickness S
Material: Housing
Rated Power Acceptance @
Ta 23 °C
Power Acceptance @ Ta >
23°C
Voltage Selector
Line Filter
MTBF
Approvals and Compliances
Detailed information on product approvals, code requirements, usage instructions and detailed test conditions can be looked up in
Details about
Approvals
EMC Products
1
KFC
Approvals
Power Entry Modules with Line Filter
https://www.schurter.com /PG06
The approval mark is used by the testing authorities to certify compliance with the safety requirements placed on electronic products.
Approval Reference Type: KFC
Approval Logo
Certificates
VDE Approvals
UL Approvals
Certification Body
VDE
UL
Description
Certificate Number: 40004665 (FKO, FKP, FKQ, FKR)
UL File Number: E72928 (FKO, FKP, FKQ, FKR)
Product standards
Product standards that are referenced
Organization
Design
Designed according to
Designed according to
Designed according to
Designed according to
Designed according to
Designed according to
Designed according to
Designed according to
Standard
IEC 60320-1
IEC 60939
IEC 60127-6
IEC 61058-1
UL 498
UL 1283
CSA C22.2 no. 42
CSA C22.2 no. 8
Description
Appliance couplers for household and similar general purposes
Passive filters for suppressing electromagnetic interference
Miniature fuses. Part 6. Fuse-holders for miniature fuse-links
Switches for appliances. Part 1. General requirements
Standard for Attachment Plugs and Receptacles
Electromagnetic interference filters
General Use Receptacles, Attachment Plugs, and Similar Wiring Devices
Electromagnetic interference (EMI) filters
Application standards
Application standards where the product can be used
Organization
Design
Designed for applications acc.
Designed for applications acc.
Designed for applications acc.
Standard
IEC/UL 60950
IEC 60601-1
IEC 60335-1
Description
IEC 60950-1 includes the basic requirements for the safety of information
technologyequipment.
Medical electrical equipment - Part 1: General requirements for basic
safety and essential performance
Safety of electrical appliances for household and similar purposes. Meets
the requirements for appliances in unattended use. This includes the en-
hanced requirements of glow wire tests acc. to IEC 60695-2-12 and -13.
Compliances
The product complies with following Guide Lines
Identification
Details
CE declaration of conformity
Initiator
SCHURTER AG
Description
The CE marking declares that the product complies with the applicable
requirements laid down in the harmonisation of Community legislation on
its affixing in accordance with EU Regulation 765/2008.
EU Directive RoHS 2011/65/EU
The law SJ / T 11363-2006 (China RoHS) has been in force since 1 March
2007. It is similar to the EU directive RoHS.
On 1 June 2007, Regulation (EC) No 1907/2006 on the Registration,
Evaluation, Authorization and Restriction of Chemicals 1 (abbreviated as
"REACH") entered into force.
V-Lock system are based on a matching plug-dose combination. The
connector is equipped with a notch intended for use with the latching
cordset. The cord latching system prevents against accidental removal of
the cordset.
Suitable for use in medical equipment according to IEC/UL 60601-1
RoHS
China RoHS
REACH
SCHURTER AG
SCHURTER AG
SCHURTER AG
MicrositeV-Lock
SCHURTER AG
Medical Equipment
SCHURTER AG
2
EMC Products
Power Entry Modules with Line Filter
https://www.schurter.com /PG06
KFC
Dimension [mm]
30
R6
R 4.5
4.8x0.8
55
2
ø 3.2
M3/ø 3.6
ø 6.3x90°
230
42.2
- 0.1
58.3
40.7
50
R 3
-0.2
57.4
2.8
69.2
28.6
- 0.1
+0.2
0
R 3.1
27.3
Technical Data of Filter-Components
Rated Current
[A]
1
2
4
6
10
1
2
4
6
10
10
Filter-Type
Standard Version
Standard Version
Standard Version
Standard Version
Standard Version
Medical Version (M5)
Medical Version (M5)
Medical Version (M5)
Medical Version (M5)
Medical Version (M5)
Standard and Medical Version
Inductances
L [mH]
2 x 10
2x4
2 x 1.5
2 x 0.8
2 x 0.3
2 x 10
2x4
2 x 1.5
2 x 0.8
2 x 0.3
2 x 0.3
Capacitance
CX [nF]
68
68
68
68
68
68
68
68
68
68
68
Capacitance
CY [nF]
2.2
2.2
2.2
2.2
2.2
-
-
-
-
-
2.2
R [MΩ]
-
-
-
-
-
1
1
1
1
1
1
Diagrams
Standard version
with voltage selector
Medical version (M5)
with voltage selector
L
1)
PE
N
Cx
X)
L1
Cy
L2
Cy
F1
3
2
1
L
2)
X)
L1
Cx
R
L2
F1
3
2
1
1)
PE
PE’
X)
F2
5
PE’
X)
F2
5
N
x) external connection to be made by the customer
1) Line
2) Load
x) external connection to be made by the customer
1) Line
2) Load
EMC Products
50
±0.15
2)
3
+0.2
KFC
Derating Curves
Fuses
5 x 20 mm (1-pole)
Admissible power
acceptance in Watt
2.5
2.0
1.5
1.0
0.5
0.0
0
20
40
60
80
100
I = 1.0 I
n
I = 0.7 I
n
I = << I
n
Power Entry Modules with Line Filter
https://www.schurter.com /PG06
Fuses
5 x 20 mm (2-pole, per pole)
Admissible power
acceptance in Watt
2.0
1.5
I = 1.0 I
n
1.0
I = 0.7 I
n
I = < < I
n
0.5
Fuses
6.3 x 32 mm (1-pole)
Admissible power
acceptance in Watt
3.15
2.5
2.0
1.5
1.0
0.5
0.0
0
20
40
60
80
100
Fuses
6.3 x 32 mm (2-pole, per pole)
Admissible power
acceptance in Watt
2.5
2.0
1.5
1.0
0.5
0.0
0
20
40
60
80
100
I = 1.0 I
n
I = 0.7 I
n
I = < < I
n
I = 1.0 I
n
I = 0.7 I
n
I = < < I
n
0.0
0
20
40
60
80
100
Ambient air temperature T
a
°C
Ambient air temperature T
a
°C
Ambient air temperature T
a
°C
Ambient air temperature T
a
°C
Attenuation Loss
Standard version
- - - - 50Ω differential mode _____ 50Ω common mode
1A
2A
4A
6A
10 A
Medical version (M5)
1A
2A
4A
6A
10 A
All Variants
Rated Current
[A]
Filter-Type
Fuseholder
Voltage Selector
V-Lock
Order Number
1
2
4
Standard Version
Standard Version
Standard Version
1-pole
1-pole
1-pole
-
-
-
4303.5011
4303.5012
4303.5013
4
EMC Products
Power Entry Modules with Line Filter
https://www.schurter.com /PG06
KFC
Rated Current
[A]
6
10
1
2
4
6
10
1
2
4
6
10
1
2
4
6
10
1
2
4
6
10
10
█
Most Popular.
Filter-Type
Standard Version
Standard Version
Standard Version
Standard Version
Standard Version
Standard Version
Standard Version
Standard Version
Standard Version
Standard Version
Standard Version
Standard Version
Standard Version
Standard Version
Standard Version
Standard Version
Standard Version
Medical Version (M5)
Medical Version (M5)
Medical Version (M5)
Medical Version (M5)
Medical Version (M5)
Medical Version (M5)
Fuseholder
1-pole
1-pole
1-pole
1-pole
1-pole
1-pole
1-pole
2-pole
2-pole
2-pole
2-pole
2-pole
2-pole
2-pole
2-pole
2-pole
2-pole
2-pole
2-pole
2-pole
2-pole
2-pole
2-pole
Voltage Selector
-
-
3 pos.
3 pos.
3 pos.
3 pos.
3 pos.
-
-
-
-
-
3 pos.
3 pos.
3 pos.
3 pos.
3 pos.
3 pos.
3 pos.
3 pos.
3 pos.
3 pos.
3 pos.
V-Lock
Order Number
4303.5014
4303.5015
4303.5031
4303.5032
4303.5033
4303.5034
4303.5035
4303.5001
4303.5002
4303.5003
4303.5004
4303.5005
4303.5021
4303.5022
4303.5023
4303.5024
4303.5025
4303.5221
4303.5223
4303.5225
4303.5227
█
█
█
█
█
█
█
█
l
4303.5209.21
4303.5229
█
Availability for all products can be searched real-time:https://www.schurter.com/en/Stock-Check/Stock-Check-SCHURTER
Packaging unit
Required Accessory
10 Pcs
Description
Fusedrawer 3
Fusedrawer for Fuse Links 5x20 mm resp. 6.3x32 mm
Fingergrip, 5 x 20, 2-pole, Voltage Selector
Fingergrip, 5 x 20, 2-pole, Voltage Selector, 100, 120, 220, 240
Fingergrip, 5 x 20, 2-pole, Voltage Selector, 110, 150, 220
Fingergrip, 5 x 20, 2-pole, Voltage Selector, 110, 220
4303.2014.00
4303.2014.01
4303.2014.02
4303.2014.03
...
EMC Products
5